SGOES Infrared Combustible Gas Detector
820-0006
Operating Manual
Page 22
6.0 Troubleshooting
Table 6.1
—Troubleshooting Guide - Display Faults
Fault Condition
Description
Solution
No Status LED
No power supply
Detach the base with the cable entry from the SGOES enclosure
and make sure that the terminals are supplied with a voltage of
24±6 VDC.
Constant fault
alarm
The space between the receiver
and the mirror is blocked or dirty
Turn off the power and clean the optical components with
alcohol and a scratch resistant cloth or chamois
Constant GAS
alarm when
there are no gas
in the air
Calibration error
Perform calibration procedure
The SGOES does not contain any user-serviceable parts. Any repair of the
SGOES should be performed by ESP Safety personnel. Any attempt to repair or
service the SGOES by unauthorized personnel will void the product warranty.