EW0526A2_en - rev. A 

Oxygen detectors 

 URS40SI 

05/10/2020 

Gas detection systems for industrial environments 

3/4

 

 

Mechanical 
Installation 

 

Oxygen excess 

Since  oxygen  weighs  more  or  less  the  same  as  air,  unless  there  is  forced  or  natural  air 
circulation, it tends to spread at the point of the leak. 
So, the excess oxygen detectors must be installed near any likely leakage points, in order to 
detect the excess oxygen as quickly as possible. 

Oxygen deficiency 

Detection of oxygen deficiency has the purpose of indirectly detecting the presence of other 
gases that deplete the oxygen in the air, therefore causing asphyxiation problems, for example. 
In  this  case,  the  detectors  must  be  located  at  the  breathing  height  of  the  occupants  in  the 
premises. Take into consideration the following specific installation guidelines, as well as the 
above instructions, for location of the detectors. 

The detectors must be installed: 

1.  where accidental gas leakages are possible 
2.  at least 1.5m away from heat sources or from vent holes 
3.  not in spaces where ventilation is poor and where gas pockets may form 
4.  away from hindrances to natural gas flow 
5.  away from equipment that may leak gas during normal operations 
6.  in environments with a temperature range of  -20°C to 50°C and relative humidity below 

90% (non-condensing) 

7.  Disconnect equipment from the power supply when mounting and dismantling detectors. 

 

Environmental 
compatibility 
and disposal 

 

 

This product has been designed and constructed using materials and processes that take into 
account the environmental issue. Refer to the following notes for disposal of the product at the 
end of its working life, or when it is replaced: 

-

  for disposal purposes, this product is classified as an electric and electronic device: do not 

dispose of it with normal household waste, in particular as regards the printed circuit 

-

  comply with all local laws in force 

-

  as far as possible reuse basic materials to keep environmental impact to a minimum 

-

  use local depots and waste recycling companies, or contact the supplier or manufacturer to 

return  used  products  or  to  ask  for  information  on  environmental  compatibility  and  waste 
disposal 

-

 

the product packaging can be reused. Keep it for future use or to return the product to the 
supplier.

 

Electrical installation 
and configuration 

 

 

 
 

 
 

 

 

Terminal board and 
electrical connections 
 
 
 
 
 

 

 
 
 
 

Cabling:

 

 
 

CAUTION:  Make the area safe and ensure that the device power supply is off before 

cabling and configuration operations.

 

Install the sensor in compliance with laws in force. 
1“ NPT cable glands are used for cable entry. 
Ground the sensor using the internal grounding system. 
Refer to the Control Unit manual for all cabling information (cable type and specifications, bus 
topology, length of connections etc.) and configuration. 

 

 

 

 

 

 

 

 

 

 

 
 

Depending on the connecting distance, use at least 4-core cable, min. diameter 0.75mm

2

 up 

to 100m, 1mm

2

 up to 200m, 1.5mm

2

 up to 500m. 

Use shielded cable where there is a risk of electromagnetic interference.

 

Grounding 
connection 

Termination 
jumper 

Configuration key 

Cable connection 

Status LED 

Sensing element 

Power supply  
and BUS  
connector  

12Vdc Power Supply Input

 

BUS Input 

 

  12V  

    

+

 

BUS 

Shield 

 BUS  

    

+

 