14 

Software  

Data interface Modbus RTU and ESERA ASCII text protocol 

The Ethernet interface can be configured using the Windows ESERA program Config Tool 3. This program 
can be found in the download area of the ESERA online shop. 
 

14.1 

Configuration and Communication with 1-Wire Gateway 10

 

The 1-Wire Gateway 10 has extensive configuration and formatting options, which can be read out and 
operated with the ESERA Config Tool 3. 
Since communication between 1-Wire Gateway 10 and Config Tool 3 takes place via the open ESERA ASCII 
text protocol, you can also exchange data with any terminal program (e.g. Hercules or Putty) at any time via 
UDP / RTU with the 1-Wire Gateway 10 and carry out the configuration.  
Details about the communication commands can be found in the document "Programmer's Guide" in the 
download area of the article on our website, www.esera.de and within Config Tool 3. 
 

15 

Communication 

15.1 

ESERA ASCII Text Protocol / Programming Manual 

 The 1-Wire Gateway 10 provides two protocols. The ESERA text protocol in ASCII format can easily be used for 
configuration and analysis. Special attention has been paid here to good legibility and traceability for people. The 
ESERA text protocol works with "GET" and "SET" commands, which probably every programmer has already 
used in his own projects. 
The ESERA text protocol is completely open and documented. The current version of the programming manual 
can be found in the article download area of our website and via the configuration software ESERA Config Tool 3. 
 

15.2 

Modbus Protocol 

You can communicate with the 1-Wire Gateway 10 without switching over the ESERA Text or Modbus RTU 
protocol. The IP address and the port for the communication can be freely selected. The default settings are Port 
5000 and DHCP operation. 
The Modbus protocol has a standardized structure.The following is a small excerpt of the addressing overview. 
The complete addressing overview can be found in 

EXCEL

 format in the download area of the 1-Wire Gateway 

10. 

Extract Mode Address Description 

Description  

read address 

Number of words 
(16Bit) 

data type 

Gateway No. 

60000 

Word 

Article No. 

60001 

Word 

Firmware Version 

61000 

String 

Hardware Status 

61010 

String 

serial number 

61020 

String 

time 

61030 

String 

date 

61035 

String 

… 

 

 

 

 

1-Wire Bus Sensors  
and Actuators 

 

 

 

OWD 1 /1-Wire Module 

40100 

Integer 

 

40101,40102 

DWord 1 

 

40103,40104 

DWord 2 

 

40105,40106 

DWord 3 

 

40107,40108 

DWord 4 

 

40109,40110 

DWord 5 

 

40111,40112 

DWord 6 

 

40113,40114 

DWord 7 

 

40115,40116 

DWord 8 

 

 

 

 

OWD 2 /1-Wire Module

 

40200 

Integer 

 

40201,40202 

DWord 1 

 

40203,40204 

DWord 2 

 

… 

 

 

 
 

 

Summary of Contents for auto connect 11324

Page 1: ...are carried out with the ESERA Config Tool 3 You can find this software on the ESERA website Please observe the operating instructions for the ESERA Config Tool 3 which can be found within the Config Tool 3 software under the HELP SUPPORT tab 2 Product description Standard Modbus RTU Protocol You can communicate with your industrial controller e g PLC via standard Modbus RTU protocol with the 1 Wi...

Page 2: ...ndly software ESERA Config Tool 3 free of charge Within the software the complete documentation is always at your fingertips as it is automatically updated via the Internet The software is available via the download area of the article on our website and via the configuration software ESERA Config Tool 3 Please use only the USB interface for configuration System time Real time clock You do not hav...

Page 3: ...isplay LED The module has different display LED s Following the function of the displays 9 Wiring diagram module top side 1 Wire Bus 7 Ground 1 Wire 8 1 Wire Data 9 5V output 11 Reset Button module bottom voltage power supply 9 30VDC 1 Minus supply voltage 2 Plus supply voltage 10 Terminating resistor termination RS485 interface Within the 1 Wire Gateway 10 there is a termination or termination re...

Page 4: ...s enabled on the installed device As of firmware version V1 18_38 there is no need to press the Reset Button of the 1 Wire Controllers 1 Wire Gateways more necessary Recovery function Firmware Update If the update is faulty e g due to a power failure during the update you can use the recovery function To do this hold down the reset button located under hole 11 on the top of the module start the up...

Page 5: ...r guide complete or in part requires the written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH ESERA Automation 2020 www esera de 11324 V2 0 R1 0 Manual Page 5 of 8 13 Connection example 1 Wire Gateway 10 1 Wire Hub III sensors and actuators www esera de ...

Page 6: ...ed for configuration and analysis Special attention has been paid here to good legibility and traceability for people The ESERA text protocol works with GET and SET commands which probably every programmer has already used in his own projects The ESERA text protocol is completely open and documented The current version of the programming manual can be found in the article download area of our webs...

Page 7: ...y voltage and that electrical charges stored in the components inside the device have been discharged beforehand Live cables or wires to which the device component or assembly is connected must always be checked for insulation faults or breakages If a fault is detected in the supply line the device must be taken out of operation immediately until the defective line has been replaced When component...

Page 8: ...the purchaser shall be entitled to conversion or reduction ESERA GmbH accepts no liability for the constant and uninterrupted availability of ESERA GmbH nor for technical or electronic errors in the online offer We are constantly developing our products further and reserve the right to make changes and improvements to any of the products described in this documentation without prior notice If you ...

Reviews: