esera automation 11228 V2 User Manual Download Page 5

 

 
 

 Art. No. 11228 V2  

 

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of 
ESERA GmbH. Errors and technical modification subject to change. 



ESERA GmbH, ESERA-Automation 2020 

www.esera.de 

11228 V2.0 R1.0  Manual 

Page 5 of 7 

8-fold digital input, pushbutton interface 

In addition to manual operation (top of module) and the 1-Wire interface, the module also features a 8-fold push-
button interface (8 x digital input) for switching the outputs.  
A short input signal (keystroke, 10-30VDC inputs) is sufficient to switch an output to the corresponding input.  
 
The 8-fold push-button interface is intended for switching lights or sockets in living areas, e.g. by means of light 
switches or motion detectors with pulse output. This ensures very fast switching even without system control. 
The pulse control, comparable to an automatic staircase lighting controller, allows any number of light scanners 
and motion detectors to be connected in parallel.  
For further details on the ESERA-Automation lighting system please refer to our website: 

https://www.esera.de/smart-home/anwendungsbeispiele/lichtsteuerung/

 

 
In addition to light scanners, any other pulse control signal can be used to switch the outputs. 
All three interfaces, manual mode, 1-Wire and push-button interface, operate in parallel on the outputs. An output 
switched e.g. by the 1-Wire interface can be switched off or on manually or via the push-button interface. 
 
Light scanners for light on/off control can be connected to the push-button interface. Normal photoelectric 
proximity switches from all switch manufacturers can be used for this purpose. 
Inside the module, a µcontroller is responsible for querying the pushbuttons, the 1-wire interface and controlling 
the relays. The push-button interface is interrogated via edge interrogation. 
 

10 

Software / Control 

The 1-Wire interface of the 8-fold digital output 8/8 is controlled by standard commands for the device DS2408. 
The pushbutton interface and the relay status are output via the DS2408 variables. Outputs switched via the 
push-button interface or manual mode can be read back via the 1-wire interface. 
 

11 

Control per 1-Wire Controller / 1-Wire Gateway 

The 1-Wire interface of the 8-fold digital output 8/8 is controlled by standard commands for the device DS2408. 
The outputs switched via the push-button interface or manual mode can be read back via the 1-wire interface. 
The 8-fold High Power switching module can easily be controlled via a 1-Wire Controller / 1-Wire Gateway. Two 
commands are available for this purpose. Below are the two commands. 
 

11.1 

Switching of one output relay 

To switch a relay output, use the following command to set only the selected output to 0 or 1. 

 
Command: SET,OWD,OUT,OWD-number, output, value 

 
Example: set,owd,out,2,1,1 => OWD number 2, output 2 is switched to "On". After switching the output, the new 
status is output as confirmation. 

 

11.2 

Switching of all output relays (PORT) 

There are applications where it is necessary to switch all outputs with one command.  
With one command, all outputs of the 1-Wire module are set to a certain state, which means that the previous 
relay status is overwritten. 
The 1-Wire Controller / 1-Wire Gateway takes over the adaptation of commands to the connected 1-Wire 8-fold 
digital output 8/8. 
 
The output value is output as decimal value 0-254. Each relay output has a value that is summed.  
Output 1 = 1, Output 2 = 2, Output 3 = 4, Output 4 = 8, Output 5 = 16, Output 6 = 32,  
Output 7 = 64, output 8 = 128. 
If, for example, you want to switch outputs 1, 3 and 5 to 1, add the output values together.  
Here e.g. 1 + 4 + 16 = 21 
All other relay outputs are switched to 0. If all outputs are to be set to 0 or switched off, the output value is 0. 
Permissible output values for 1-Wire digital outputs: 0 

– 255 

 
 

Summary of Contents for 11228 V2

Page 1: ...the 8 fold digital output 8 8 and put the device into operation please read these operating instructions carefully through to the end especially the section referring on safety instructions 2 Product...

Page 2: ...4 Technical data Switching channels 8 switching relay NO separate inputs per channel Switching voltage 10 250V DC or AC voltage Switching current Max 16A for 3 seconds 10A continuous current per outpu...

Page 3: ...put 19 Relay 1 output 20 Relay 2 input 21 Relay 2 output 22 Relay 3 input 23 Relay 3 output 24 Relay 4 input 25 Relay 4 output 29 GND ground button input 30 Button 1 input 10 30VDC 31 Push button 2 in...

Page 4: ...r off Several outputs can be switched in one cycle After a waiting time of approx 2 seconds the system automatically switches to normal operation mode the PWR LED lights up permanently again and the s...

Page 5: ...push button interface is interrogated via edge interrogation 10 Software Control The 1 Wire interface of the 8 fold digital output 8 8 is controlled by standard commands for the device DS2408 The pus...

Page 6: ...may only be operated at the specified voltages and ambient conditions The device is intended for installation inside a control cabinet as a stationary device 14 Disposal note Do not dispose of the de...

Page 7: ...ar and normal wear and tear Customer claims for damages for example for non performance fault in contracting breach of secondary contractual obligations consequential damages damages resulting from un...

Reviews: