11228 V2.0 R1.0  Manual 

Page 3 of 7 

 

Connection plan 

The connection plan is available in our web 
shop as a separate document. 

Note: A pre-fuse must be provided. 
 
Connection module topside:

 

 

18 = Relay 1, input 
19 = Relay 1, output 
20 = Relay 2, input 
21 = Relay 2, output  
22 = Relay 3, input 
23 = Relay 3, output 
24 = Relay 4, input 
25 = Relay 4, output  
 
29 = GND (ground) button input 
30 = Button 1, input 10-30VDC 
31 = Push button 2, input 10-30VDC 
32 = Push button 3, input 10-30VDC 
33 = Push button 4, input 10-30VDC 
 
26 - 28 and 34, 35 not assigned 
 
 

Module bottom side: 

1 = Relay 8, input 
2 = Relay 8, output 
3 = Relay 7, input 
4 = Relay 7, output  
5 = Relay 6, input 
6 = Relay 6, output 
7 = Relay 5, input 
8 = Relay 5, output 
9, 14 not assigned 

 

10 = Push button 8, input 10-30VDC 
11 = Push button 7, input 10-30VDC 
12 = Push button 6, input 10-30VDC 
13 = Push button 5, input 10-30VDC 
 
15 = GND 1-Wire Bus 
16 = Data 1-Wire Bus 
17 = +12V DC max. 270mA 

 

Summary of Contents for 11228 V2

Page 1: ...the 8 fold digital output 8 8 and put the device into operation please read these operating instructions carefully through to the end especially the section referring on safety instructions 2 Product...

Page 2: ...4 Technical data Switching channels 8 switching relay NO separate inputs per channel Switching voltage 10 250V DC or AC voltage Switching current Max 16A for 3 seconds 10A continuous current per outpu...

Page 3: ...put 19 Relay 1 output 20 Relay 2 input 21 Relay 2 output 22 Relay 3 input 23 Relay 3 output 24 Relay 4 input 25 Relay 4 output 29 GND ground button input 30 Button 1 input 10 30VDC 31 Push button 2 in...

Page 4: ...r off Several outputs can be switched in one cycle After a waiting time of approx 2 seconds the system automatically switches to normal operation mode the PWR LED lights up permanently again and the s...

Page 5: ...push button interface is interrogated via edge interrogation 10 Software Control The 1 Wire interface of the 8 fold digital output 8 8 is controlled by standard commands for the device DS2408 The pus...

Page 6: ...may only be operated at the specified voltages and ambient conditions The device is intended for installation inside a control cabinet as a stationary device 14 Disposal note Do not dispose of the de...

Page 7: ...ar and normal wear and tear Customer claims for damages for example for non performance fault in contracting breach of secondary contractual obligations consequential damages damages resulting from un...

Reviews: