background image

Art. No. 11211 
 

 

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of 
ESERA GmbH. Errors and technical modification subject to change. 



ESERA GmbH, ESERA-Automation 2020 

www.esera.de 

11211 V2.0 R1.0  Manual 

Page 1 of 7

 

 
 

User Guide 

1-Wire Dual S0 Counter Module 

 
 

  Professional Dual S0 counter module for recording energy meters,  

such as electricity, gas, water meters or wind sensors 

  Readout of meter values via 1-Wire Bus 

  Permanent data retention of meter values without operating voltage 

  Counter values can be reset 

  DIN rail housing with only 17mm width  

  Designed for control cabinet installation  

  Connection via screw terminals 

  Power supply 12VDC  

 
 
 
 
 
 
 
 
 
 
 
 

Introduction 

Before you start assembling the module and before you take the device into operation, please read these 
operating instructions carefully to the end, especially the section referring to the safety notes. 
 

Product description 

The Dual S0 counter module is designed for energy recording of two independent electricity, water and gas 
meters or wind turbines. All S0 devices manufactured according to DIN 43864 can be equipped with an isolated  
S0 interface can be connected. If in doubt, check the data sheet of your energy measuring device. 
After applying the operating voltage, the Dual S0 counter module is ready for operation. The integrated 
Counter modules count the input pulses continuously. The counter readings are transmitted via the 1-Wire 
Network from the memory of the Dual S0 counter module. The current number of pulses per  
Time unit can be calculated by delta formation. Typical readout intervals are in the range of  
1 - 3 minutes for electricity or gas meter. The Dual S0 counter module can be set to "zero" by pressing the reset 
button. 
 
The Dual S0 counter module is supplied by a 12V DC voltage. The working voltage of the 1-Wire data line is 
typically 5V. 
After failure of the operating voltage, previously counted input pulses are permanently stored internally.  
The Dual S0 counter module counts pulses which are generated by closing an input (falling edge).  
One green LED is available for each counter input. The respective LED lights up when the input is closed. A 
permanently closed input does not cause any further changes to the counter reading. 
 
 
 
 

Summary of Contents for 11211

Page 1: ...lectricity water and gas meters or wind turbines All S0 devices manufactured according to DIN 43864 can be equipped with an isolated S0 interface can be connected If in doubt check the data sheet of your energy measuring device After applying the operating voltage the Dual S0 counter module is ready for operation The integrated Counter modules count the input pulses continuously The counter readin...

Page 2: ... 4 3 HF EN 61000 4 4 Burst EN 61000 4 5 Surge EN 61000 6 1 Interference immunity EN 61000 6 3 Interference radiation RoHS 6 LED display The module has two yellow LED displays which flash when an input is being closed When the input is open a 5V power is measurable The edge is being counted during the closing of the input A continuously closed input does not cause a modification of the counter read...

Page 3: ...und for example on the Wikipedia website https en wikipedia org wiki Electricity_meter https de wikipedia org wiki S0 Schnittstelle 10 Data output 1 Wire Controller 1 Wire Gateway For the Dual S0 counter module the following data of the 32Bit counter values are output The 1 Wire interface of the Dual S0 counter module is controlled by standard commands for the DS2423 block and the data is read out...

Page 4: ...written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH ESERA Automation 2020 www esera de 11211 V2 0 R1 0 Manual Page 4 of 7 12 Connection example 1 Combination of AC meter and Dual S0 counter module 13 Connection example 2 Combination of three phase meter and Dual S0 counter module ...

Page 5: ...echnical modification subject to change ESERA GmbH ESERA Automation 2020 www esera de 11211 V2 0 R1 0 Manual Page 5 of 7 14 Connection example 3 Combination of wind sensor and Dual S0 counter module 15 Connection example 4 The following example shows the combination of 1 Wire Controller 20 1 Wire Gateway 20 Modbus 1 Wire Analog Input Module and 1 Wire S0 Dual Counter Module ...

Page 6: ...r applied Tools may only be used on devices components or assemblies when it is certain that the devices are disconnected from the power supply and electrical charges stored in the components inside the device have been discharged Live cables or wires to which the device or an assembly is connected must always be tested for insulation faults or breaks If an error is detected in the supply line the...

Page 7: ...urchase price refunded or a reduction of the purchase price ESERA GmbH accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical or electronic errors in the online offer We are constantly developing our products further and reserve the right to make changes and improvements to any of the products described in this documentation without prior notic...

Reviews: