GD350A series high-performance multifunction VFD
-164-
Function
code
Name
Description
Default Modify
corresponds to the rated slip frequency
△
f of
motor 1.
Setting range: 0.0–200.0%
P04.10
Low-frequency
oscillation control
factor of motor 1
In space voltage vector control mode, the
motor, especially the large-power motor, may
experience current oscillation at certain
frequencies, which may cause unstable motor
running, or even VFD overcurrent. You can
adjust the two function codes properly to
eliminate such phenomenon.
Setting range of P04.10: 0–100
Setting range of P04.11: 0–100
Setting range of P04.12: 0.00Hz–P00.03
(Max. output frequency)
10
○
P04.11
High-frequency
oscillation control
factor of motor 1
10
○
P04.12
Oscillation control
threshold of motor 1
30.00Hz
○
P04.13
V/F curve setting of
motor 2
This group of function code defines the V/F
curve of motor 2 to meet the needs of different
loads.
0: Straight-line V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve (power of 1.3)
3: Torque-down V/F curve (power of 1.7)
4: Torque-down V/F curve (power of 2.0)
5: Customized V/F curve (V/F separation)
Note: Refer to the description for P04.00.
0
◎
P04.14
Torque boost of
motor 2
Note: Refer to the descriptions for P04.01 and
P04.02.
Setting range of P04.14: 0.0%: (automatic);
0.1%–10.0%
Setting range of P04.15: 0.0%–50.0% (of the
rated frequency of motor 2)
0.0%
○
P04.15
Torque boost cut-off
of motor 2
20.0%
○
P04.16
V/F frequency point
1 of motor 2
Note: Refer to the descriptions for P04.03–
P04.08.
Setting range of P04.16: 0.00Hz– P04.18
Setting range of P04.17: 0.0%–110.0% (of the
rated voltage of motor 2)
Setting range of P04.18: P04.16– P04.20
Setting range of P04.19: 0.0%–110.0% (of the
0.00Hz
○
P04.17
V/F voltage point 1
of motor 2
00.0%
○
P04.18
V/F frequency point
2 of motor 2
0.00Hz
○
P04.19 V/F voltage point 2
00.0%
○