background image

Wilo

= Factory settings

Factory setting

Variable differential 
pressure - Δp-v

Constant differential 
pressure - Δp-c

Constant speed

PUMP CURVE
I, II, III

CONTROL MODE

NORMAL 
OPERATION

FAULT

NORMAL 
OPERATION

FAULT

CONTROL MODE
Variable differential 
pressure - Δp-v

Constant differential 
pressure - Δp-c

Constant speed

PUMP CURVE
I, II, III

Wilo Display

LED display

Hold

Hold

Status

Locked

 8 sec

Unlocked

Factory 
setting

Venting

 1 sec

 1 sec

 10 min

Manual
restart

Factory
setting

 30sec

Hold

 8 sec

Hold

 3 sec

Hold

 6 sec

Hold

+

1

.

4.

3.

2.

LED 
Indicator

Meaning

Diagnostic

Cause

Remedy

lights green Pump in 

operation

Pump runs 
according its 
setting

Normal operation

blinks red/
green

Pump in 
function but 
stopped

Pump restarts 
by itself after 
the fault is 
disappeared

1.

 Undervoltage U<160 V

or Overvoltage U>253 V

2. 

Modul overheating:

temperatur inside motor 
too high

1. 

Check voltage supply

195 V < U < 253 V 

2. 

Check water and 

ambient temperature

blinks red

Pump out of 
function

Pump stopped 
(blocked)

Pump does not restart by 
itself due to a permanent 
failure

Change pump

blinks 
orange

Pump out of 
function

Pump stopped

Pump is not starting

Change pump

LED off

No power 
supply

No voltage on 
electronics

1. 

Pump is not connected

to power supply

2.

 LED is damaged

3.

 Electronics are damaged

1. 

Check cable connection 

2.

 Check if pump is running 

3.

 Change pump

http://www.esbe.eu/global/en/

products/circulation units

 WILO - Faults, Causes and 

Remedies 

LED display

click

Control mode

Pump curve

RecomendedAlt.

1

Constant speed

II

Constant speed

I

Variable differential 

III

Variable differential 

II

I

III

6

II

I

III

2

3

4

5

7

8

9

Click

Click

Recommended Alternative

LED display

Control mode

Pump curve

Constant speed

Constant speed

Variable differential 
pressure Δp-v

Variable differential 
pressure Δp-v

Variable differential 
pressure Δp-v

Constant differential
pressure Δp-v

Constant differential
pressure Δp-v

Constant differential
pressure Δp-v

Constant speed

Settings navigations

Pump Settings

6

Summary of Contents for GDA200 Series

Page 1: ...xx PN10 ESBE System Units CIRCULATION UNIT DN25 DN32 Mtrl nr 98141121 Ritn nr 7951 vers A Rev 2022 12 01 Series GDA200 Series GRA200 Series GFA200 Series GBA200 Series GRC200 125 321 58 250 0º 36 0 º Pull Pull 2 Remove insulation ESBE AB Bruksgatan 22 SE 333 75 Reftele www esbe eu Remove actuator controller Series GRA2xx GBA211 GRC2xx LVD 2014 35 EU EMC 2014 30 EU RoHS 2011 65 EU ErP 2009 125 EU P...

Page 2: ...fixed temperature Series GFA211 GFA212 CCW N CW bk bu bn L bn N bu PE gn Electric installation www esbe eu SERIES VTA370 VTA570 Fit supply pipes 40 50Nm c c 125mm Adjust wallbracket Assembling on wall 4 Assemble insulation 30mm Assemble actuator controller Series GRA2xx GBA211 GRC2xx 0 20 MINUTES Commissioning Flow Filling and venting Open White mark indicate check valve position 45o Filling and ve...

Page 3: ...53 V 2 Check water and ambient temperature blinks red Pump out of function Pump stopped blocked Pump does not restart by itself due to a permanent failure Change pump blinks orange Pump out of function Pump stopped Pump is not starting Change pump LED off No power supply No voltage on electronics 1 Pump is not connected to power supply 2 LED is damaged 3 Electronics are damaged 1 Check cable conne...

Page 4: ...3 xx 70 MODE UPM3 xx 50 UPM3 xx 70 MODE UPM3 xx 50 UPM3 xx 70 MODE FAULT DISPLAY SOLUTION Wilo Push button LEDs Grundfos Display http www esbe eu global en products circulation units Grundfos Faults Display and Solutions No 2 2 1 ON 230 V 5 mm 0 Off 1 On RED YELLOW 160 V ON L PE N RED YELLOW 2 3 4 230 V ON 1 0 Off 1 On RED YELLOW OFF 0 V SYSTEM CONTROLLER PWM A C B 0 Off 1 On L PE N ...

Reviews: