background image

12

Notes in application examples:

P1 =  Output 1 - Pumpcontrol, P2 = Output 2 - Extra function 2, P3 = Output 3 - Extra function 1

S3 = Sensor 3, S4 = Sensor 4, S7= Sensor 7

1* = Sensor box 1, 2* = Sensor box 2

aPPl. 

aVailable  

for

Version

function 90c

electrical 

connection

settting

12

PuMP control heat circuit 1

Connect pump heat circ1 as P1

heat PuMP control 

(Primary heat source)

By floating temperature

Connect Heat Pump as P3

Menu 15.7.2  

Select: Heating circ 2

Settings in menu  6.1-6.6

aux. heat source control

By valve position

Connect Aux.heat source as P2

Menu 15.7.1 

  

Select: Position

Settings in menu 15.7.3 – 15.7.5

Connect sensor as sensor 3 in sensor 

box 2

13

PuMP control heat circuit 1

Connect pump heat circ1 as P1

doM hot Water control

By temperature control

Connect heat source as P2

Menu 15.7.2  

Select: Dom.Hot Water

Settings in menu 7.1-7.3

energy transfer control

Connect tank circ pump as P3

Menu 15.7.1  

Select: Energy transfer

Settings in menu 8.1-8.3

Connect sensor as sensor 3+4+7 in 

sensor box 2

14

PuMP control heat circuit 1

Connect pump heat circ1 as P1

PuMPcontr. heat circuit 2

By floating temperature

Connect heat source as P2 

Menu 15.7.2  

Select: Heating circ 2

Settings in menu 6.1-6.6

energy transfer control

Connect tank circ pump as P3

Menu 15.7.1  

Select: Energy transfer

Settings in menu 8.1-8.3

Connect sensor as sensor 3+4+7 in 

sensor box 2

Note: Heat circuit 2 must have a lower 

curve than Heat circuit 1

15

PuMP control heat circuit 1

Connect pump heat circ1 as P1

solar PuMP control

By floating temperature

Connect solar circ pump as P3

Menu 15.7.1  

Select: Solar

Settings in menu  9.1

PuMP control heat circuit 2

By floating temperature

Connect circulation pump as P2

Menu 15.7.2 

Select: Heating circ 2

Settings in menu 6.1-6.6

Connect sensor as sensor 3+4+7 in 

sensor box 2

Note: Heat circuit 2 must have the same 

curve as Heat circuit 1

16

PuMP control heat circuit 1

Connect pump heat circ1 as P1

PuMP solar control

By floating temperature

Connect solar circ pump as P3

Menu 15.7.1 

Select: Solar 

Settings in menu 9.1

doM hot Water control

By temperature control

Connect heat source as P2

Menu 15.7.2 

Select: Dom. Hot Water

Settings in menu 7.1-7.3

Connect sensor as sensor 3+4+7 in 

sensor box 2

17

PuMP control heat circuit 1

Connect pump heat circ1 as P1

doM hot Water control

By temperature control

Connect tank circ pump as P2

Menu 15.7.2 

Select: Dom.Hot Water

Settings in menu 7.1-7.3

heat source teMPerature control

By valve position

Connect heat source as P3

Menu 15.7.1  

Select: Position

Settings in menu 15.7.3 - 15.7.5

Connect sensor as sensor 3 in sensor 

box 2

Recommended setting:

15.7.3: 75%   15.7.4: 20 min  15.7.5: 0 min

18

PuMP control heat circuit 1

Connect pump heat circ1 as P1

loading PuMP control

By flue gas temperature controll

Connect loading pump as P3

Menu 15.7.1 

Select: Load pump 

Settings in menu 10.1-10.2

doM hot Water control

By temperature control

Connect heat source as P2

Menu 15.7.2 

Select: Dom. Hot Water

Settings in menu 7.1-7.3

Connect sensor as sensor 3+7 in sensor 

box 2.

Note: Sensor S7 must be replaced with 

sensor CRS215 to be able to handled 

higher flue gas temperature

Summary of Contents for 90C-1

Page 1: ...Please read these instructions in full before using the controller CONTrOLLER Series 90c VRG140 VRB140 VRG130 VRG230 3HG 3H 3G 4G 3F BIV T TM 3MG 4MG 5MG ADAPTER KIT VRG801 ADAPTER KIT VRG900 90C...

Page 2: ...5 Display and Input 5 Menu Sequence 5 Menu Structure 5 AVAILABLE IN VERSION MENU 90C 1 90C 2 90C 3 1 Measurement 6 90C 1 90C 2 90C 3 2 Statistics 6 90C 1 90C 2 90C 3 3 Operating Times 6 90C 1 90C 2 90...

Page 3: ...the unit or accessories that are not in perfect condition must be exchanged immediately Use only original spare parts and accessories from the manufacturer Markings made on the unit at the factory mus...

Page 4: ...th PE Blue Neutral N Brown Phase L Commissioning help Set Up Wizard The first time the controller is turned on and after the language and time are set a query appears as to whether you want to paramet...

Page 5: ...dditional information Back to previous screen ok confirm selection Confirm confirm setting Out door 0 C Flow 27 C Target fl 27 C Room 21 C Exit main menu 2 Statistics OK 1 Measurements 3 1 Time and da...

Page 6: ...ck continues to run for about 24 hours if the mains voltage is interrupted and after that has to be reset Menu 3 2 Daylight Saving Automaticly adjust clock f r daylight savings time Menu 3 3 Heating C...

Page 7: ...in will reset the 14 day reference program and start it at day 1 Menu 4 5 Domestic Hot Water Auto The Domestic Hot Water function is activated according to the schedule in menu 3 5 On The Domestic Hot...

Page 8: ...re values displayed for example due to cables which are to long or sensors which are not positioned optimally can be compensated for manu ally here The settings can be made for each individual sensor...

Page 9: ...ce flow temperature is raised or respectiveley lowered ac cording to the percent setting in room sensor If room sensor is set to 0 this function is deactivated Settings range 10 C to 30 C Default 20 C...

Page 10: ...ings in menu 15 7 3 15 7 5 4 PUMPCONTR HEAT CIRCUIT 1 Connect pump heat circ1 as P1 PUMPCONTR HEAT CIRCUIT 2 Activated when temperature at sensor 3 is lower than specified in menu 6 Connect pump heat...

Page 11: ...2 Activated when temperature at sensor 3 is lower than specified in menu 6 Connect pump heat circ 2 as P2 Menu 15 7 2 Select Heating circ 2 Settings in menu 6 1 6 6 HEAT SOURCE TEMPERATURE CONTROL By...

Page 12: ...heat circ1 as P1 SOLAR PUMP CONTROL By floating temperature Connect solar circ pump as P3 Menu 15 7 1 Select Solar Settings in menu 9 1 PUMP CONTROL HEAT CIRCUIT 2 By floating temperature Connect circ...

Page 13: ...P1 P2 P3 P1 S3 S4 P2 P3 S3 S4 1 2 S3 S4 P1 P2 P3 230 P1 P2 P3 2 1 S4 S3 S3 S4 230 P1 P2 P3 P1 S3 S4 2 1 S3 P1 P2 P3 230 P1 S4 S3 P2 P3 1 S4 2 S3 S4 P1 P2 P3 230 P1 P2 P3 2 1 S4 S3 90C 1 90C 2 90C 3 90...

Page 14: ...2 S3 S4 S7 230 P1 P2 P3 13 14 P1 S3 2 1 S3 230 P1 P2 P3 P1 P2 P3 1 2 S3 S3 230 P1 P2 P3 P1 P2 P3 S3 S4 S7 1 2 P3 P2 S3 S7 S4 P1 1 2 S4 P2 P1 S3 S7 P3 1 2 230 P1 P2 P3 S3 S7 15 16 S3 S4 S7 230 P1 P2 P...

Page 15: ...Art nr 9814 98140423 Ritn nr 9226 Utg B 1205 GB...

Reviews: