NOTE!
The power source can be powered from a generator. For more information,
contact authorised ESAB service personnel.
Check that the unit is connected to the correct mains power supply voltage, and that it is
protected by the correct fuse size. A protective earth connection must be made, in
accordance with regulations.
A.
Rating plate with supply connection data
Recommended fuse sizes and minimum cable areas
Mig 4004i Pulse/Mig 4004i Pulse WeldCloud™
Mains voltage
380-460 V, +/- 10%, 3~50/60 Hz
Mains cable area
4G4 mm
2
Phase current I
eff
U
in
380 V
20 A
Fuse
anti-surge
20 A
Fuse
MCB-surge type C
25 A
Phase current I
eff
U
in
400 V
19.2 A
Fuse
anti-surge
20 A
Fuse
MCB-surge type C
25 A
Phase current I
eff
U
in
415 V
18 A
Fuse
anti-surge
20 A
Fuse
MCB-surge type C
20 A
Phase current I
eff
U
in
440 V
17.6 A
Fuse
anti-surge
20 A
Fuse
MCB-surge type C
20 A
Phase current I
eff
U
in
460 V
17 A
Fuse
anti-surge
20 A
Fuse
MCB-surge type C
20 A
NOTE!
The mains cable areas and fuse sizes as shown above are in accordance with
Swedish regulations. For other regions, supply cables must be suitable for the
application and meet local and national regulations.