background image

52

section 6 

troubleshootinG

6.4.4  procedure for verifying calibration of digital meters.

Voltmeter

1.  Connect a digital meter known to be calibrated to the positive and negative output bus bars.  

2.  Compare  the  power  source  voltmeter  reading  to  the  calibrated  meter  reading.    Readings  should  match  within 

±0.75%.

Ammeter

1.  External to the power source, connect a precision shunt in series with the work lead(s). The best shunt is one with a 

value of 100 micro-ohms (50mV / 500A or 100mV / 1000A) and a calibrated tolerance of 0.25%.  

2.  Use a calibrated 4 ½ digit meter to measure the output of the shunt.  The amperage indicated with the external shunt 

and meter should match power source ammeter to within 0.75%.

6.5  control circuit interface using J1, J4 and J6 connectors

Interface to the EPP-601 control circuitry is made with connectors J1, J4 and J6 on the front panel.  J1 has 24 conductors, J4 

has 2 and J6 has 10.

J1-P and J1-G provide access to the galvanically isolated transistor output signal indicating an “Arc On” condition.  See 

Subsection 6.8, Arc Current Detector Circuits.  J1-L and J1-J are the inputs for the remote Voltage Reference Signal that 

commands the EPP-601 output current Subsection 6.9, Current Control Pot & Remote Vref.  J1-R and J1-Z supply 115V AC for 

remote controls.  See Subsection 6.6, Auxiliary Main Contactor (K3 and K33) & Solid State Contactor Circuits and Subsection 

6.10, Pilot Arc Hi/lo & Cut/mark Circuits.

J1-E and J1-F are the input connections for the Emergency Stop function.  For Emergency Stop to operate, the Jumper 

between TB8-18 and TB8-19 must be removed.

J1-S is the input to K8 that parallels S1 switch contact.  When 115V AC from J1-R is fed into J1-S, K8 activates placing the Pilot 

Arc in High.

J4-A and J4-B are from an isolated contact on the emergency stop (E-stop) switch.  This signal can be used by the plasma 

control to indicate the state of the E-stop switch on the power source.

Cut / Mark selection:  The power source defaults to Cutting mode when there is no signal fed into J1-C.  When 115V AC from 

J1-R is fed into J1-C, K11 is activated placing the EPP-601 in the Marking mode.  For more details concerning the operation 

of K11 and the Cut / Mark modes, refer to Subsection 6.10, High / Low Cut Current Modes and Mark Mode.

High / Low current ranges:   The power source defaults to low cutting current range (35-100A) when no signal is fed into 

J1-T.  High range (50A to maximum current rating) is selected whenever 115VAC is fed into J1-T by connecting J1-R to J1-T.

J6 connects to the water cooler.  J6-A and J6-B are 115VAC hot and neutral respectively.  This 115VAC activates the contac-

tor for the pump.  J6-C and J6-D connect to the flow switch.  The flow switch is closed when coolant is flowing.  J6-E and 

J6-H connect to the coolant level switch.  The switch is closed when the coolant reservoir contains sufficient coolant and 

it is open when the reservoir is low.

Summary of Contents for Plasmarc EPP-601

Page 1: ...EPP 601 Plasmarc RU 0558007979 06 2012...

Page 2: ...52 529...

Page 3: ......

Page 4: ...4...

Page 5: ...1 12 3 4 2 13 3 4 3 13 3 5 14 3 5 1 14 3 5 2 14 3 6 15 3 6 1 EPP 601 16 3 6 2 EPP 601 18 3 7 19 3 7 1 19 3 7 2 20 3 7 3 20 4 0 21 4 1 21 4 2 24 4 2 1 29 4 3 28 4 4 29 4 4 1 30 4 4 2 30 4 4 3 30 4 4 4...

Page 6: ...38 6 3 1 38 6 3 2 100 A 38 6 3 3 38 6 3 4 39 6 3 5 39 6 3 6 43 6 3 7 F1 F2 44 6 3 8 44 6 4 46 6 4 1 47 6 4 2 49 6 4 3 51 6 4 4 52 6 5 J1 J6 52 6 6 K3 54 6 7 K1A K1B K1C 55 6 8 56 6 9 U 57 6 10 58 6 1...

Page 7: ...7 1 1 0 ESAB 1 B 2 3 4 5 IP 12 60 IP 23S 15 15...

Page 8: ...8 1...

Page 9: ...7733 0558007734 0558007735 3 380 380 400 460 575 3 217 217 206 179 143 50 50 50 60 60 A 142 8 142 8 142 7 142 6 142 4 128 5 128 5 128 4 128 4 128 2 90 90 90 90 90 4 0 AWG 4 0 AWG 4 0 AWG 3 0 AWG 1 0 A...

Page 10: ...10 2 2 3 850 1143 mm 45 00 946 mm 37 25 1022 mm 40 25...

Page 11: ...11 3 3 1 3 2 3 3 1 EPP 601...

Page 12: ...12 3 3 4 3 4 1 EPP 601 3 I U x I x 0 68 U 2 2 EPP 601...

Page 13: ...13 2 2 3 4 2 EPP 601 12 7 1 EPP 601 2 3 4 5 6 3 4 3 1 3 2 1 2 3 3 TB4 TB6...

Page 14: ...14 3 5 3 5 1 600 4 0 AWG 400 600 100 4 0 AWG 600 100 3 3 5 2 1 2 3 UL 4 1...

Page 15: ...15 3 EPP 600 3 6 100 100 600 4 0 AWG 600 14 AWG EPP 601 600 100 4 0 AWG 600 600 4 0 AWG...

Page 16: ...16 3 1 2 3 4 5 HIGH LOW LOW 6 HIGH LOW HIGH 7 0 00 10 00 J1 G 0 00 10 00 J1 P x 160 EPP 601 3 6 1 EPP 601 EPP 601...

Page 17: ...17 3 EPP 601 EPP 601 EPP 601 3 6 1 EPP 601 600 100 EPP 601 EPP 601 EPP 601 600 4 0 AWG 600 4 0 AWG 600 14 AWG 600 4 0 AWG 600 4 0 AWG 600 4 0 AWG...

Page 18: ...18 3 EPP 601 20 100 1000 A 10 20 10 1 2 A K12 B TB7 7 and TB7 8 HI LOW 3 6 2 EPP 601 EPP 601 1 U 2 I 20 x U I 10 x U 3 Low I 20 x U 100 I 10 x U 4 High I 160 x U 100 Low...

Page 19: ...19 3 3 7 24 8 3 7 1 4 647032...

Page 20: ...20 3 4 3 7 2 647032 2010549 3 7 3 647257 2062105...

Page 21: ...21 4 4 1 2 H 3 T1 300 375 300U120 0 0 10 0 I U x 80 High S T T T L1 L2 T T1 T1 425 250 R R EPP 601...

Page 22: ...Versus Output Voltage 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 0 50 100 150 200 250 300 350 Output Voltage Volts RMS Ripple Current Amperes Choppers Synchronized and Switchng in Unison 10KHz Ripple Cho...

Page 23: ...23 U U EPP 601 430 K10 380 400 50 380 360 4 EPP 601 4 1 T1 300 375 T1 375 300 375 EPP 601 10000 25000 430 375 4 1...

Page 24: ...24 4 4 2 A Main Power Contactor On Over Temp Fault 10 Power Reset Fault Current Dial EPP 601 EPP 601 10 100 A 50 600 A B Panel Remote PANEL REMOTE...

Page 25: ...25 4 24 8 HIGH LOW 100 EPP 601 LOW 4 2 EPP 601 100 A 600 J1 R J1 T EPP 601 TB8 1 TB8 2 TB8 E Stop Connector J4 A J4 B E Stop Button B...

Page 26: ...26 4 Actual Preset Actual Preset S4 Actual Preset Actual Up OUTPUT AMMETER Preset Down U 0 00 10 00 CURRENT POTENTIOMETER Panel Remote Panel Up J1 J J1 L Panel Remote Remote Down 4 2...

Page 27: ...50 600 J1 EPP 601 115 J1 T J1 R 0 625 50 600 7 50 9 00 475 EPP 601 2 J1 R 115 J1 M 50 10 100 J1 EPP 601 1 00 10 100 10 00 U 50 600 0 625 7 50 7 50 680 360 K12 R60 R67 10 100 A 100 10 A R60 R67 SW2 5...

Page 28: ...uses 50 of the cutting current to start dwell and then gradually less than a second achieve full current The ESP 400C is factory shipped with this feature enabled The default settings are Minimum Sta...

Page 29: ...29 4 4 4 EPP 601 5 A 50 800 2 2 I 80 U I 10 U 800 I 80 U I 10 U...

Page 30: ...30 4 4 1 4 1 2 SW1 PCB1 4 4 2 1 4 SW2 PCB1 2 1 2 2 4 3 8 4 16 2 4 4 3 5 8 SW2 5 A 5 40 A 6 20 A 7 10 A 8 5 A 5 8 0 A 0 A 0 A 0 A 5 A 5 A 1 2 3 4 5 6 7 8 SW2 SW1 1 2 3 4 5 6 7 8 SW2 SW2 1 2 3 4 5 6 7 8...

Page 31: ...31 4 4 4 4 38 4 4 5 PCB1 7 50 800 250 800 1200 90 80 70 60 50 40 30 20 10 0 0 1 2 3 4 5 6 7 8 9 10 SW1 SW2...

Page 32: ...100 150 200 250 300 350 400 450 0 100 200 300 400 500 600 700 4 4 5 1 EPP 450 U I 431 I 80 x U U 7 000 U 6 000 U 1 000 U 1 00 min U 4 000 U 0 625 U 10 00 max U 2 000 U 7 500 U 3 000 U 5 000 U 5 00 U 3...

Page 33: ...nce On This Equipment Should Only Be Performed By Trained Personnel 5 2 Cleaning Regularly scheduled cleaning of the power source is required to help keep the unit running trouble free The frequency o...

Page 34: ...assages clear of dust and other obstructions WARNING caution 5 3 Lubrication Some units are equipped with oil tubes on the fans These fans should be oiled after 1 year of service All other EPP 601s ha...

Page 35: ...LEDsonPCB1 locatedbehindthecoverwiththe EPP label problems can be diagnosed NOTE It is normal for momentary light ing flashing of the fault indicator and LED 3 when a contactor on signal is applied at...

Page 36: ...line Excessive Ripple Power Source is shut down LED 4 yellow High Bus Fault Illuminates when input line voltage is too high for proper operation approximately 20 above nominal line voltage rating Pow...

Page 37: ...when the current from the left side chopper is too high 400 amps Measured by the left hall sensor Power source is shut down LED 10 _ red Left IGBT Unsaturated Fault Illuminates when left IGBT is not f...

Page 38: ...e Faulty fan s Replace fans 6 3 1 No output with contactor signal applied 6 3 2 Output limited to 100A Problem Possible Cause Action Powersourcewillnotgoover 100A High current range signal missing Ext...

Page 39: ...ut power Maintain phase voltage imbalance of less than 5 Momentary loss of one phase of input power Restore and maintain input power within 10 nominal Faulty control PCB1 Replace PCB1 P N 0558038313 L...

Page 40: ...24 LED 9 red Left Over Current Note If operation at 400A or less is possible then the Right side is not working Cuttingatover400A withafaultyrightside right side output 0 See faulty right side Left cu...

Page 41: ...cure connector Shorted Freewheeling Diode s Replace freewheeling diode s Loose or unplugged P1 connector at the left PWM Drive PCB Secure P1 Loose or unplugged P10 connector at PCB1 Secure P10 Faulty...

Page 42: ...t pot set too high Lower the current setting Faulty left PWM Drive PCB Replace left PWM Drive PCB P N 0558038324 High remote current signal Decrease remote current signal Faulty PCB1 Replace PCB1 P N...

Page 43: ...too low Increase current pot setting Start current pot located behind the cover for the control PCB is set too low Increase the start current post setting to 7 Arc does not start There is no arc at t...

Page 44: ...plugged connector at left PWM Drive PCB PCB2 Secure connector Faulty left PWM Drive PCB Replace right PWM Drive PCB P N 0558038324 Check voltage between P5 1 and P5 2 at the left PWM Drive PCB PCB2 Sh...

Page 45: ...n Refer to fault light illumination section Current setting too low Increase current setting Remote current signal removed during cut Fix remote current signal Problem Possible Cause Action Output cur...

Page 46: ...surface If a PC board is found to be a problem check with your ESAB distributor for a replacement Provide the distributor with the part number of the board as well as the serial number of the power so...

Page 47: ...rneath 8 Remove one of the bolts holding the right side of the front panel to the base Loosen the second bolt Of these two bolts remove the bolt on the left and loosen the bold on the right 9 Swing th...

Page 48: ...BR A Bus A reading of 2 ohms or less indicates one or more shorted diodes Replace all Diodes on POS Plate 2 If fuses F8 and or F9 were open in the first step make two more ohmmeter readings A Measure...

Page 49: ...Tag and lock any disconnect switch to prevent accidental activation B Remove the top panel to gain access to the modules located in the top rear of the power source C Clean the compartment containing...

Page 50: ...due to over heating D Insert the four M6 mounting bolts but do not tighten Leave them loose a few turns Be certain that the threads from the mounting bolts do not bend the edges of the thermal pad cl...

Page 51: ...conductor cable The breakout point should be physically at the middle of the shunt The breakout point is the place where the conductors exit from the outer insulation jacket The black and clear insul...

Page 52: ...tate Contactor Circuits and Subsection 6 10 Pilot Arc Hi lo Cut mark Circuits J1 E and J1 F are the input connections for the Emergency Stop function For Emergency Stop to operate the Jumper between T...

Page 53: ...J1 L J1 J REMOTE CUTTING CURRENT REFERENCE VOLTAGE Vref Icut Vref x 80 EPP 450 POWER SOURCE 0 10V Vref LEVEL SWITCH OK K15 LO J1 Y CONTACTOR FOR PUMP FAN H J1 D J1 E J1 H J1 C J1 A J1 B CONTROL COOLAN...

Page 54: ...the remote Contactor Signal is present The 115V AC Contactor Signal is fed to TB1 9 TB7 8 and resistors R45 and R45 A These resistors reduce the 115V to approximately 16V AC fed into the Control PC B...

Page 55: ...nce the K1 s are closed the contacts of the Starting Contactor K2 are bypassed and full primary line power is supplied to the Main Transformer through the contacts of the K1 s Because the starting seq...

Page 56: ...TOP LOOP MUST BE CLOSED FOR POWER SOURCE TO FUNCTION 21 F M TB8 18 E STOP TB8 19 J4 A J1 E TO T2 X3 TO CB2 2 A 24 VAC E STOP BUTTON J1 F J4 B S5 115 VAC K2 K2 K2 E STOP EMERGENCY STOP MAIN CONTACTOR K...

Page 57: ...stand a maximum peak voltage of 150V It can switch a maximum of 50 mA The transistor turns on whenever the arc current through the Work Lead exceeds 5A Pilot arcs not establishing main arcs will not t...

Page 58: ...Board contains two inputs for VREF High Speed and Normal When the negative of the VREF signal is fed into the High Speed input P8 3 the EPP 601 will respond to a change in VREF within 10 mS When the n...

Page 59: ...currents required for marking In the Cutting mode the minimum stable output current is 50A in the high current range 35A in the low current range and 10A in the marking mode In the marking mode the no...

Page 60: ...PC Board to change the switching frequency from 10 KHz to 25 KHz The higher switching frequency results in the more power dissipation by the heat sinks on PCB 3 Therefore in the LOW current mode a sma...

Page 61: ...the back page of this manual for a list of customer service phone numbers 7 2 Ordering Items listed in the following Bill of Materials that do not have a part number shown are not available from ESAB...

Page 62: ...notes...

Page 63: ...ded E stop information throughout manual Included Replacement Parts section in Schematic Wiring Diagram package Changed power supply name from EPP 600 to EPP 601 3 Revision 08 2010 Updated with new DO...

Page 64: ...30 55 North and South America ARGENTINA CONARCO Buenos Aires Tel 54 11 4 753 4039 Fax 54 11 4 753 6313 BRAZIL ESAB S A Contagem MG Tel 55 31 2191 4333 Fax 55 31 2191 4440 CANADA ESAB Group Canada Inc...

Reviews: