background image

Phone Order

  0466 909 653

Email Order

  [email protected]

Fax Order

  07 3041 3232

Order Online 

  www.olct.co

indicating that the charging process is complete. 

Note:   

The charge stored  in the insulation will  be  discharged automatically  when  the  test button  is  released.   

Be careful not to turn the range switch knob while the test button is pressed, or the instrument will be damaged. 
 

b). Measurements at 2000M

Ω

/1000V 

Some specifications require testing at 1000V.    This voltage must also be selected where the supply voltage of 
the installation is between 500V and 1000V.    First, set the range switch to 1000V and then proceed as indicated 
in an above 500V test.  The above note also applies to testing at 1000V.  In addition the following applies. 

Note:

  Make sure that the circuit under test does not include components which will be damaged by the applied 

1000V.  Many normal components of an installation are 

likely to be damaged if tested at 1000V.    Examples are 

power  factor  correction  capacitors,  low  voltage  mineral  insulated  cables,  electronic  light  dimmers,  electronic 
ballasts and starters for fluorescent lamps etc… 
 

c). Lock power on Feature   

For hands free operation a lock power on feature is incorporated on the press to test button.  Set the LOCK 
button to lock test voltage.  Pressing it again will switch the LOCK function off. 
 

5.  LOW RESISTANCE (CONTINUITY) MEASUREMENTS 

a). Set the range switch to the 200

Ω

  position. 

b). Connect the red test lead to the 

Ω

 

terminal and black to the COM terminal. 

c). Connect the tips of the test leads to both ends of the circuit under test.    Read resistance in 

Ω

  on the LCD. 

d). When the resistance on the circuit is below approximately 40

Ω

, it will be indicated by a continuous beep. 

 

6.  AC/DC VOLTAGE MEASUREMENTS 

a). Set the range switch to ACV or DCV position 
b). Connect red test lead to “

Ω

” terminal and black test lead to terminal “COM”. 

b)  Connect test prods of test leads IN PARALLEL to the circuit being measured. 
c)  Read the voltage value on LCD. 
 

7.  POWER TOOLS AND SMALL APPLIANCES 

This test would also apply to other similar equipment that has a line cord.    For double insulated power tools, the 
megohmmeter  lead  shown  connected  to  the  housing  would  be  connected  to  some  metal  part  lf  the  tool  (e.g. 
chuck, blade). 
Note:  The switch of the device must be in the “ON” position and the main power should be disconnected. 
 

MOTORS 
AC

 - Disconnect the motor from the line by disconnecting the wires at the motor terminals or by opening the main 

switch.    If the main switch is used and the motor also has a starter then the starter must be held, by some means, 
in the “ON” position.    In the latter case, the measured resistance will include the resistance of the motor, wire 
and all other components between the motor and the main switch.  If a weakness is indicated, the motor and 
other components should be checked individually. If the motor is disconnected at the motor terminals, connect 
one megohmmeter lead to the grounded motor housing and the other lead to one of the motor leads.   

DC

  -  Disconnect  the  motor  from  the  line.  To  test  the  brush  rigging,  field  coils  and  armature  -  connect  one 

megohmmeter lead to the grounded motor housing and the other lead to the brush on the commutator.  If the 
resistance  measurement  indicates  a  weakness,  raise  the  brushes  off  the  commutator  and  separately  test  the 
armature, field coils and brush rigging by connecting one megohmmeter lead to each of them individually, leaving 
the other connected to the grounded motor housing. The above also applies to DC Generators.   
 
 

Summary of Contents for 550

Page 1: ... continuity disconnect circuit from main power supply and all loads from the circuit Safety symbols Caution refer to this manual before using the meter Dangerous voltages Meter is protected throughout by double insulation or reinforced insulation When servicing use only specified replacement parts CE Comply with EN 61010 1 1 SPECIFICATIONS 1 1 General Information Environment conditions Installatio...

Page 2: ...Overload Protection 200Ω 0 1 Ω 4 5V 200k Ω 0 1k Ω 1 2 3 0V 250Vrms Continuity Beeper Range Resolution Operation Resistance Max open Circuit Voltage Overload Protection 0 1 Ω Resistance 40Ω 4 5V 250Vrms Short circuit current 200mA DC Voltage Range Resolution Accuracy Input Impedance Overload Protection 1000V 1V 0 8 3 10MΩ 1000Vrms AC Voltage 40Hz 400Hz Range Resolution Accuracy Input Impedance Over...

Page 3: ...connected The indicator should read 00 0 Ω When the leads are not connected the display will read infinity indicated by 1 This will ensure that test lead are in good working condition 4 INSULATION RESISTANCE MEASUREMENTS a Measurements at 200M Ω 250V This is the voltage used for the majority of insulation resistance tests on normal installation requirement To measure insulation resistance press th...

Page 4: ...tely 40 Ω it will be indicated by a continuous beep 6 AC DC VOLTAGE MEASUREMENTS a Set the range switch to ACV or DCV position b Connect red test lead to V Ω terminal and black test lead to terminal COM b Connect test prods of test leads IN PARALLEL to the circuit being measured c Read the voltage value on LCD 7 POWER TOOLS AND SMALL APPLIANCES This test would also apply to other similar equipment...

Page 5: ...lead sheath by connecting one megohmmeter lead to a ground and or lead sheather and the other megohmmeter lead to each of the conductors in turn Check insulation resistance between conductors by connecting megohmmeter leads to conductors in pairs For after sale service please send to Electronic Specialties Inc 139 Elizabeth Ln Genoa City WI 53128 Phone 262 279 1400 Fax 262 279 1300 For more qualit...

Reviews: