STARTING UP AND PROGRAMMING
62
Installation Manual
Programming the gate run ("
P3
"), operators without encoder
Before programming the run, adjust the
maximum thrust in accordance with the weight
and size of the gate (see “Maximum thrust
adjustment (parameter
A6
)” on page 64).
Failure to do so will mean the control board
cannot correctly detect any halting of the gate.
O
Before programming the gate open/close,
ensure the turning direction of the operator is
correct (see “Initial Conditions Programming
(D1= “
C
”)” on page 60).
1
Press ENTER to access the programming menus. The
display lights up and D1 flashes.
2
Press the buttons ^ and V until D1 shows the letter
P
flashing. Press ENTER to confirm. D2 flashes.
3
Press the buttons ^ and
V
until the required D2
parameter appears (D2=
3
).
4
Press ENTER. The gate carries out a reset and
Oç
flashes in the display. Leaf 1 starts to open by itself.
5
Press ST1 to start slowdown for leaf 1 when
opening.
6
Leaf 1 automatically stops opening when reaching
the opening stopper or the FCA.
7
Press ST1 to start opening leaf 2.
8
Press ST1 to start slowdown for leaf 2 when
opening.
9
Leaf 2 automatically stops opening when reaching
the opening stopper or the FCA.
10
Press ST1 to start closing leaf 2.
11
Press ST1 to start slowdown for leaf 2 when closing.
12
Leaf 2 automatically stops closing when reaching
the closing stopper or the FCC.
13
Press ST1 to start closing leaf 1.
14
Press ST1 to start slowdown for leaf 1 when closing.
15
Leaf 1 automatically stops closing when reaching
the closing stopper or the FCC.
16
When programming is finished, D3-D4 stop flashing
(remain static) and D2 flashes.
17
Press ESC to return to the previous display.
Main Functions Programming (D1= “
F
”)
1
Press ENTER to access the programming menus. The
display lights up and D1 flashes.
2
Press the buttons ^ and
V
until D1 shows the letter
F
flashing. Press ENTER to confirm. D2 flashes.
3
Press the buttons ^ and
V
until the required D2
parameter appears. Press ENTER to confirm. D3 and
D4 flash.
4
Press the buttons ^ and
V
until the required D3 and
D4 value appears (see chart). Press ENTER to
confirm.
5
Press ESC to return to the previous display.
Operating mode, programmed using
F1
, can be
modified using
A9
(see “Advanced Functions
Programming (D1= “
A
”)” on page 63).
D1
D2
D3
D4
P
3
O
ç
Programming the gate run
D1 D2 Parameter
D3
D4
Pre-
determined
option
Options or values
F
1
F u n c t i o n i n g m o d e
a
(opening mode is modified
using
A9
)
0
1
...
3
01
01
: automatic closing, collective opening
02
: step-by-step closing, step-by-step opening
03
: dead man mode
2
Standby in automatic mode
0..5.
0...9
03
59
= 59 sec;
2.5
= 2 min. 50 sec., etc
3
Pedestrian opening (%)
0...5
0
40
00
: pedestrian opening is not carried out,
10
: 10% of total opening, etc
4
Pedestrian closing mode
0
1
,
2
01
01
: automatic,
02
: step-by-step
a.
For further details, see “Functioning modes”
on page 49.