6
GB
- for the terminals 5 and 6 is:
max = 0.5 Nm
advisable = 0.33 Nm
Fig. 7/A
ESR/ESR-T TERMINAL BLOCK
Table 2
ESR-T
Fuse
Model
Manuf.
model
Ferraz
6600.CP.URGB.14.51/20
12 - 240
Bussmann
FWP.20A.14F
Ferraz
6600.CP.URGB.14.51/32
18 - 240
Bussmann
FWP.30A.14F
9) For connect the devices to the power line, use
appropriate sized wires with 75 °C (167 °F) mini-
mum temperature rating. The following table shows
the recommended sizes:
Nominal
f
wires
AWG
current
(mm
2
)
12 A
2.5
14
18 A
4
12
25 A
6
10
40 A
10
8
60 A
16
6
80 A
25 (*)
4
(*) without wire terminal
10) The torque for tightening the terminals 1, 2
and earth of ESR-T and ESR is:
- for ESR-T and ESR 25
max = 0.8 Nm
advisable = 0.7 Nm
- for ESR 40, 60 and 80
max = 2 Nm
advisable = 1.5 Nm