ERNITEC Eagle PIR-045 Manual Download Page 3

PIR-045

PASSIVE INFRARED DETECTOR

2800-00006                                                                                                                                                                                       Page 3 of 10

Typical horizontal alignment of PIR-045

Horizontal alignment should be done in a way to avoid unwanted signals being generated by targets (branches, bushes,

fences) likely to be moved by wind (see Fig. 2 below). Movement within the field of view will reduce the sensitivity of the PIR-

045 by increasing the alarm threshold level and may lead to unwanted alarms.

Top view

45 m

4 m

Fig. 2

 

When walk testing the unit, the threshold level will increase as a result of the signal generated by the target and

decrease exponentially in time after the event. To make sure that original sensitivity is reached, wait at least for 3

minutes between each crossing or disable the ATD function by setting DIP - Switch 3 to „off“.

If the Installation software is used for monitored walk tests and the DIP – switches 1 and 2 are set to software settings (on –

on), the nominal threshold level can be reset by pressing 

[n]

. Alternatively the threshold level can be kept to its minimum

value by changing the configuration of the ATD for this test (see annex 3 for details).

Sensitivity Settings

The various settings of the PIR-045 are made by means of multiple DIP - switches on the connector board.

The

 DIP – Switches 1 and 2

 are for 

sensitivity setting

 depending on the required detection performance. If the maximum

required range is less than the nominal range of the detector, it is recommended to reduce the overall sensitivity to reduce

nuisance alarms.

*) With the DIP - switches 1 and 2  both set to „on“, the overall sensitivity is 100% factory setting but can be changed with the

installation software (see annex 3 for details).

If the sensitivity is adjusted with the installation software, the programmed value will remain active also following a power

off.

Operation of the PIR-045 with overall sensitivity set to more than 100% is not recommended in outdoor applications as

the nuisance alarm rate could increase significantly.

Switch

Overall

1 and 2

Sensitivity

off – off

  40 %

off – on

  75 %

on – off

100 %

on – on

Software Settings

*) 20 … 140 %

Summary of Contents for Eagle PIR-045

Page 1: ...nwanted alarms The universal bracket is equally suited for wall mounting using screws or pole mounting using steel bands through the slots It is very important that the cover of the PIR 045 is securel...

Page 2: ...the field of view is terminated by a natural or artificial background at the end of the range Vertical alignment is optimal when the upper edge of the field of view is at 1 5 to 2 5 m above ground at...

Page 3: ...n be reset by pressing n Alternatively the threshold level can be kept to its minimum value by changing the configuration of the ATD for this test see annex 3 for details Sensitivity Settings The vari...

Page 4: ...his detector model Alarm Time Alarm time and count per event is determined by the duration of the detected event and depends on the shape and amplitude of the alarm signal Individual alarm pulses have...

Page 5: ...ult of RF interference lightning shock waves or birds flying across the field of view close to the unit a possible alarm will be rejected This means also that a very fast movement directly in front of...

Page 6: ...s cannot be achieved masking of the PIR 045 cannot be excluded Detection is a function of thermal contrast speed and size of a target crossing the field of view Contrast conditions can vary significan...

Page 7: ...Night OFF Memory set enable LED disable Day OFF If memory was set LED flashes 2 Hz Day ON Walk test indication LED enable Night ON X Memory reset LED stop flashing B A Cover switch Day Night Not used...

Page 8: ...Configuration For this the use of the interface module PIR IF485A is recommended see section 12 above The test socket carries V GND and the two RS 485 ports A and B The detector needs to be opened fo...

Page 9: ...ation moving in the wind and or other sources of disturbance it is possible that unwanted alarms occur Monitoring and interpreting the information supplied by the installation software will help findi...

Page 10: ...l be generated and saved as DDMMYYAB BMP where AB is used for identification of files within one day This function is not possible when the display is frozen n to reset the thresholds to the minimum v...

Reviews: