5.3.3. Alarm point of alarm output 3 (Only SSI 9002)
Read the setting of alarm point for alarm output 3
SOH
D
D
STX
G
3
W
ETX
BCC
Answer of SSI 9002
STX
V or X
X
X
X
X
X
ETX
BCC
Set the alarm point of alarm output 3
SOH
D
D
STX
G
3
W
V or X
X
X
X
X
X
ETX
BCC
V
sign
positive: ‘ ‘ (ASCII 20h)
negative: ‘-’ (ASCII 2Dh)
X
alarm point
valid values
-99999 to 999999
Answer of SSI 9002
ACK
Example: Alarm point of alarm output 3 = - 5000
SOH
D
D
STX
G
3
W
-
0
5
0
0
0
ETX
BCC
5.3.4. Hysteresis of alarm output 3 (Only SSI 9002)
Read the setting of hysteresis for alarm output 3
SOH
D
D
STX
G
3
H
ETX
BCC
Answer of SSI 9002
STX
X
X
X
X
X
X
ETX
BCC
Set the hysteresis of alarm output 3
SOH
D
D
STX
G
3
H
0
0
X
X
X
X
ETX
BCC
X
hysteresis
valid valuese
000001 to 001000
Answer of SSI 9002
ACK
Example: Hysteresis of alarm output 3 = 125
SOH
D
D
STX
G
3
H
0
0
1
2
5
ETX
BCC
5. Commands of alarm output level (P-02)
25
ERMA-Electronic GmbH