![EPS 35 320 200 Instruction Manual Download Page 28](http://html.mh-extra.com/html/eps/35-320-200/35-320-200_instruction-manual_2418424028.webp)
28
© 2006, Elektro-Automatik GmbH & Co. KG
Irrtümer und Änderungen vorbehalten
EN
Instruction Manual
EL 3000 A Series
Date: 12-05-2011
About the device
2.2 Device specific data
Mains input
Mains voltage
115V/230V switchable
115V/230V switchable
Mains frequency
50/60Hz
50/60Hz
Mains fuse
M0.63A
M0.63A
DC input
Input voltage U
nom
160V
400V
Input power P
nom
400W
400W
Input current I
nom
60A
25A
Overvoltage protection threshold
1.1 * U
nom
1.1 * U
nom
max. allowed input voltage
180V
450V
Voltage control
Adjustment range
0…160V
0…400V
Display resolution
100mV
100mV
Accuracy**
<0.1% of U
nom
<0.1% of U
nom
Current control
Adjustment range
0…60A
0…25A
Display resolution
10mA
10mA
Accuracy**
<0.2% of I
nom
<0.2% of I
nom
Power control
Adjustment range
0…400W
0…400W
Display resolution
0.1W
0.1W
Accuracy**
<2% of P
nom
<2% of P
nom
Resistance control
Adjustment range 1
0…10
Ω
0…40
Ω
Display resolution
10m
Ω
10m
Ω
Accuracy**
<2% of resistance range,
0.3% of range of current
<2% of resistance range,
0.3% of range of current
Adjustment range 2
10…400
Ω
40…800
Ω
Display resolution
100m
Ω
100m
Ω
Accuracy**
<2% of resistance range,
0.3% of range of current
<2% of resistance range,
0.3% of range of current
Dynamic values
Current rise and fall time***
<50us
<50us
Levels
2 adjustable levels per control mode
2 adjustable levels per control mode
Times (pulsed operation)
2 adjustable, 50us..100s
2 adjustable, 50us..100s
Rise/Fall time
adjustable, 30us…200ms
adjustable, 30us…200ms
Accuracy**
<10%
<10%
Trigger input*
yes, for external level switching
yes, for external level switching
Battery test feature
Modes
Current/Power/Resistance
Current/Power/Resistance
Battery protection
Discharge threshold voltage adjustable
Discharge threshold voltage adjustable
Display
Time and comsumed battery capacity
Time and comsumed battery capacity
Display
2 x 40 characters, illuminated
2 x 40 characters, illuminated
Analogue interface*
Set value inputs
0...10V for U / I / P / R (0...100%)
0...10V for U / I / P / R (0...100%)
Monitor outputs
0...10V for U / I (0...100%)
0...10V for U / I (0...100%)
Control signals
internal/external, Input on/off, R-Mode 10/400
Ω
internal/external, Input on/off, R-Mode 40/800
Ω
Error signals
Overvoltage / Overtemperature
Overvoltage / Overtemperature
Outputs
Reference voltage
Reference voltage
Cooling
Type
Temperature controlled fans
Temperature controlled fans
Ambient temperature
0…40°C
0…40°C
Terminals
Load input
Front side, safety sockets
Front side, safety sockets
Sense input
Rear side, 4pole screw clamp
Rear side, 4pole screw clamp
Trigger output
Rear side, 4pole screw clamp
Rear side, 4pole screw clamp
Analogue interface
Front side, 15pole Sub-D socket
Front side, 15pole Sub-D socket
Dimensions W x H x D
240 x 120 x 300mm
240 x 120 x 300mm
Weight
6kg
6kg
Article number
35 320 200
35 320 201
Supported interface cards
CAN, USB, RS232, GPIB, Ethernet
CAN, USB, RS232, GPIB, Ethernet
* for technical specification see section "8. Analogue interface"
*** Rise and fall time are defined at 10%...90% and 90%...10% of the nominal value
All single values, which specify a tolerance are typical values
EL3160-60A
EL 3400-25A
** Accuracy is defined as the max. allowed difference between actual value and set value, always related to the nominal value.
Example: nom. value is 60A and accuracy is given with 0.2%. A set value of 20A may thus result in an actual value of 19.88A...20.12A.