Epcom SF6200MA User Manual Download Page 8

11

4 Device function description

The bellowed is front panel introduction for controller SF6200MA ( for SF6200MS
detailed function, please refer to SF6200MAas they are with same front panel printing ):

Figure 4- 1 SF6200MAfront panel design sketch

4.1 Front panel function description

Indicator and status description:

AC POWER: 110V AC indicator,green on means normal , orange on means
AC power off.

DC POWER: DC po w e r indicator light, green on means 24V power connected ,
orange on means out of connect to DC 24V,light off means without configuration for
DC power.

PAGING: remote control microphone indicator, green light means that the remote
control microphone is paging the zone from the host.

SYS FAULT: orange indicates the host is faulty, flashing indicates that the host has a
new fault.

NET FAULT: green means the network is normal, orange means the network is
with failure.

EMC MIC:light off if well connected, green means PPT is paging, orange means PPT
is with failure.

Volume potentiometer:

MONOROR: Monitor volume adjustment.

EMC MIC: PPT microphone volume adjustment.

REBLE: Treble adjustment.

BASS:: Bass adjustment.

ENERGENCY: emergency broadcast button, press to select

ALERT MSG

or

EVAC MSG to

broadcast emergency voice message,

EVAC MSG is prior to ALERT

Summary of Contents for SF6200MA

Page 1: ...ANUAL VOICE EVACUATION PUBLIC ADDRESS SYSTEM SF6200MA SF6200MS Thanks for using EPCOM Voice Evacuation Public Address System For better operation please read this manual carefully before operating the...

Page 2: ...1 Electrical Specifications 6 3 2 Performance Specifications 6 4 Device function description 11 4 1 Front panel function description 11 4 2 Rear panel function description 12 5 Operation Instructions...

Page 3: ...3 1 Product renderings 1 1 SF6200MA Product design sketch 2U FIGURE 1 1 SF6200MAProduct renderings 1 2 SF6200MS Product design sketch 2U FIGURE 1 2 SF6200MSProduct renderings...

Page 4: ...32 remote microphones allow to change the priority level 2 channel of remote MIC online interface with 24 V power using standard RJ 45 network port and CAT 5 network cable achieving lone distance tra...

Page 5: ...status of each partition speaker loop open circuit short circuit overcurrent impedance change The real time indication function of the system status 8 ways short circuit level trigger manner 3 way di...

Page 6: ...200Hz 10kHz Input impedance 1k Signal to noise ratio 70dB Unbalanced audio input Sensitivity of 350mV Frequency response 80Hz 16kHz Impedance 10k Signal to noise ratio 70dB Balanced line input Sensiti...

Page 7: ...MIC console CAN interface Baud rate of 38400bps Supports up to 20 remote MIC consoles Trigger input Short circuit mode short circuit Mechanical indicators Size L W H 484 350 88 mm 19 wide 2U Net weigh...

Page 8: ...thout configuration for DC power PAGING remote control microphone indicator green light means that the remote control microphone is paging the zone from the host SYS FAULT orange indicates the host is...

Page 9: ...volume adjustment knob 4 2 Rear panel function description Figure 4 2 SF6200MArear panel design sketch ON for power on OFF for power off DC POWER 24V DC input interface pay attention to positive and...

Page 10: ...l output a short circuit signal Emergency Rest Input when short circuit signal is input the fire alarm emergency status will be reset IMPEDANCE The button of impedance Calibration when it is pressed t...

Page 11: ...rgency function 1 Emergency voice function 1 Manually press the EMERGENCY button red light flashes 2 Press alert msg button on host panel to play alert voice language information the response is decid...

Page 12: ...en LINE7 indicator turn on means select MP3 1 Sound source play of each zone a The current selected audio source for MP3 turn on according zone can play MP3 sound source press all zone button all zone...

Page 13: ...m detection power 500W Installation of the new device requires sampling the speaker impedance the specific operation is as follows 1 Install new equipment connect speakers for each zone 2 Press impeda...

Page 14: ...ance 25 change detection sampling 30W speaker impedance plus or minus 7W press system fault self test button on the front panel the indicate light is orange and computer status is fault Then connected...

Page 15: ...ton to turn on or off the monitor Light on means amplifier monitor is turn on light off means amplifier monitor is turn off 5 7 IP address Reset Press the IP reset button to reset the host IP address...

Page 16: ...tch Settings Voice Evacuation Controller Address 1 2 3 4 5 6 7 8 1 0 0 0 0 0 0 0 1 0 1 0 0 0 0 0 0 2 1 1 0 0 0 0 0 0 3 0 0 1 0 0 0 0 0 4 1 0 1 0 0 0 0 0 5 0 1 1 0 0 0 0 0 6 1 1 1 0 0 0 0 0 7 0 0 0 1 0...

Page 17: ...20 0 0 1 1 0 0 0 0 12 1 0 1 1 0 0 0 0 13 1 1 1 0 0 0 0 14 1 1 1 1 0 0 0 0 15 0 0 0 0 1 0 0 0 16 1 0 0 0 1 0 0 0 17 0 1 0 0 1 0 0 0 18 1 1 0 0 1 0 0 0 19...

Page 18: ...Version 0 1...