Note: The characteristics may vary depending on the model of the equipment
Protection
When the battery reaches its lower limit of operational voltage, the UPS will automatically shut off, when the power is restored, the UPS will automatically energize to continue its
operation.
Battery overload protection
When the mains supply is restored, the UPS charger will begin to charge the battery and will stop charging when it reaches the upper limit of the battery's operating voltage range in order
to extend the battery life.
Short circuit protection: when the UPS is in battery mode and a short circuit occurs, the UPS will shut down immediately. When in AC mode, the protection fuse will blow so after the short
circuit has been repaired, switch to battery mode.
Phase and frequency detector: in AC mode, the UPS system will automatically detect the waveform of the phase and input frequency to make sure that same waveform and frequency are
preset in the output voltage, and which will energize to the computer equipment in order to minimize inferences and avoid damage to said equipment.
Important security measures
KEEP THIS MANUAL
CAUTION:
· To prevent risks of fire or electric shock, install in areas free of conductive
contaminants such as temperature and humidity.
·
Do not cover the UPS vents to prevent overheating.Avoid exposing it
directly to sunlight or near excessive sources of heat.
·
Do not connect non-computer equipment, such as medical equipment,
microwaves or vacuum cleaners.
·
No conecte el UPS a su propia salida.
·
Do not allow any liquid to spill or insert metallic objects into the UPS.
·
In an emergency, press the off button and disconnect the UPS.
·
Do not connect the UPS to a multiple outlet or surge suppressor.
·
If the UPS is metal encapsulated, its physical ground connection is required to
reduce the leakage current to less than 3 ma.
·
To avoid possible electric shock, even with the UPS disconnected, considerable
voltages may be present because the battery is connected to the circuit.
· It is required to disconnect the battery to be able to service or maintain it as many
times as necessary by authorized personnel.
·
When it is required to replace the battery, it must be of the same type and with
the same characteristics. Recycle disposable batteries.
·
When servicing the UPS: remove rings, watches and / or any metal object on your
arms and hands, use tools with an insulating handle or gloves.
·
Do not leave tools on top of the battery.
Installation and software operation
Only for models with communication port
Procedure for software installation and UPS monitoring:
1.- Connect the UPS and the computer to the communication ports via the interface cable.
2.- Insert the CD-ROM into the disk reader or run the program on the PC that you have downloaded for this model. Select the installation icon (installation or file.exe) and follow the
command instructions that appear on the screen until the end
Maintenance
Preventive maintenance that prolongs the useful life of the UPS
Perform monthly revisionof the following recommendations:
1.- Check the slits where the UPS air circulates are not blocked.
2.- Remove dust and objects from the UPS surface.
3.- Check the terminals of the battery that are well annealed and the insulator of the connector in good condition, replace it (s) if necessary.
4.- Check the humidity and temperature in the area where it is located.
5.- Periodically disconnect the UPS from the outlet for 5 minutes, if in this period of time there are no variations in the alarm tones during the 40 seconds and no tone after, the UPS
5.-
is working normally. In case of any alarm, it is time to give service.
Battery maintenance
A maintenance-free battery made of lead and acid is electrically connected to the UPS. An adverse residential environment, continuous extreme discharges, high temperatures, etc., will
dramatically reduce the battery life. It will also be reduced, even if it is not in service. That is why it is recommended to discharge the battery (leave it in battery mode until the UPS is turned
off) every 3 months. When the battery life is about to expire, it will present a series of malfunctions.