2. Product Overview
2.1 Specifications
Model
1KVAS-RT
1KVAH-RT
2KVAS-RT
2KVAH-RT
3KVAS-RT
3KVAH-RT
Rated Capacity
1KVA / 900W
2KVA / 1800W
3KVA / 2700W
Input
Rated input voltage
208Vac / 220Vac / 230Vac / 240Vac
Rated input frequency
50Hz / 60Hz (auto-sense)
Input voltage range
110 ~ 176Vac (power derating linearly between 50% and 100% load);
176 ~ 280Vac (no derating); 280 ~ 300Vac (power derating 50%)
Input frequency range
40 ~ 70Hz
PFC
≥ 0.99
THDI
≤ 6%
Bypass voltage range
-25% ~ +15% (settable)
Output
Output voltage
208Vac / 220Vac / 230Vac / 240Vac (settable)
Voltage accuracy
± 1%
Output PF
0.9
Inverter overload
capability
105% ~ 125% load: transfer to bypass in 1 min;
125% ~ 150% load: transfer to bypass in 30s;
> 150% load: transfer to bypass in 300 ms;
Load crest
3:1
From mains mode
to BAT mode
0 ms (transfer time)
From mains mode
to bypass
4 ms (typical)
Efficiency
Line mode
90%
91%
92%
BAT mode
85%
86%
87%
ECO mode
95%
96%
97%