background image

 

 

 

 

 
Enware Programmable Piezo Button is a touch-activated electronic switch that can be easily set to a desired timing. 
Its versatility allows it to be set again to a different program on site should there be any change of mind. 

The electronic button timing program offers the following features: 

 

The length of time you want the valve to turn on.  

 

Minimum length 3 seconds, maximum length 10 minutes. 

 

In increments of 3 seconds. (3, 6, 9, 12 .... etc) 

 

Factory default time is 6 seconds. 
 

 

The length of time you want the valve to stay off once stopped. 

 

Minimum length 0 seconds, maximum length 10 minutes Off Time. 

 

In increments of 3 seconds (3, 6, 9, 12 .... etc) 

 

Choose “0” (zero) if you do not want any Lockout time. (i.e. allow consecutive use.) 

 

This function prohibits the user from turning on the valve again for the set period of time - that is, the valve 
is “locked out” once turned off. It is useful when you want to limit the length of a shower to a set time and 
prevent consecutive use, excessive use or water wastage. The Lockout time becomes effective every time 
the switch turns off.  

 

 

Once turned on, this function allows the user to stop the flow of water even if the set Run Time has not 
finished yet. For example, a shower is set to run for 3 minutes but user decides to turn it off at 1 minute. 
(Note that any lockout time still applies once it is turned off.) 

 

Choose “Yes” if you want this function. 

 

Choose “No” if you want the water to flow for the set Run Time without interruption. 

 

Default factory setting is “No” (without Stop). 
 

 

Automatically activates the valve every 24 hrs and runs for the set Run Time, particularly useful for 
Legionella control and reducing the risk of bacteria growth in the water supply line. 

 

Choose “Yes” if you want the valve to automatically turn on every 24 hrs. 

 

Choose “No” if you do not want this function. 

 

Default factory setting is “No” (without 24 hr flush). 

 

 

Summary of Contents for EMD815

Page 1: ...I00224_JAN 2017 Call 1300 369 273 www enware com au Enware Australia Pty Limited 9 Endeavour Rd Caringbah NSW 2229 Australia Ph 61 2 8556 4000 Fax 61 2 8556 4055 ...

Page 2: ...DIMENSIONS NOT TO SCALE ...

Page 3: ...COMPONENTS ...

Page 4: ... ON Time in increments of 3 sec Solenoid Valve Brass For use with potable water only COMPLIANCE Enware products are to be installed in accordance with the Plumbing Code of Australia and AS NZS3500 Reference should also be made to the Australasian Health facility Guidelines AHFG ABCB and Local Government regulations when considering the choice of and the installation of these products NOTE Enware A...

Page 5: ...front panel from Shower Box taking care not to damage any cable while doing so Disconnect spade connectors from solenoid if they are connected 3 Secure the Shower Box to the internal cavity within the wall The Shower Box can be fixed to a masonry wall or wall frame using screws suitable for the fixing method Fixing screws not supplied When mounting the Shower Box take note of the minimum and maxim...

Page 6: ...e the isolation valves are closed prior to turning on Hot and Cold Water supplies The Isolation Valve spindle has a slot which should be in a vertical position when closed Use a 3mm Allen Key or flat head screw driver to turn the isolation valve 6 Loosely place handle on spline of mixer cartridge 7 Turn on Hot and Cold water supply and test for leaks within the pipework connection and Isolation Va...

Page 7: ...9 Connect power cable to piezo button Connect two spade connectors to the two side connectors of the solenoid ...

Page 8: ...re system is still functional 14 Seal any gaps between the wall cut out and the shower box with appropriate silicone sealant 15 Use foam seal supplied to seal between the wall surface and the back of the front plate Run a thin bead of silicone sealant along the back top edge of the front plate Place the Front Plate over the mixer and push firmly against the wall Secure using the 6 Allen key fixing...

Page 9: ...ctronic Piezo Button Program in the following section For Solenoid Servicing instructions refer to separate document Enware EMS804 24V Solenoid Service Maintenance Instructions_I00228 SPARE PARTS Solenoid 1 2 includes 2x 1 2 nipples EMS804 Transformer EMDS800 Extension Lead for Transformer 2m EMDS801 Extension Lead for Solenoid Molex Connectors EMFS313 4m EMFS314 2m Solenoid service kit 1 2 AC ENM...

Page 10: ... is locked out once turned off It is useful when you want to limit the length of a shower to a set time and prevent consecutive use excessive use or water wastage The Lockout time becomes effective every time the switch turns off Once turned on this function allows the user to stop the flow of water even if the set Run Time has not finished yet For example a shower is set to run for 3 minutes but ...

Page 11: ... the ON time by the indicated increments e g If program no 4 has been selected the increments are by 3 seconds each one press 3 sec 2 presses 6 sec and so on therefore pressing the switch 4 times will set the ON time to 12 seconds The RED LED blinks for each press of the switch 7 Now the ON time has been selected the GREEN LED will turn off and the RED LED will turn on The switch is now ready to s...

Page 12: ...arranty does not apply in respect of any damage or loss due to or arising from a Failure by you or any other person to follow any instructions for use including instructions and directions relating to the handling storage installation fitting connection adjustment or repair of the product published or provided by us b Failure by you or any other person responsible for the fitting installation or o...

Reviews: