Enware Programmable Piezo Button is a touch-activated electronic switch that can be easily set to a desired timing.
Its versatility allows it to be set again to a different program on site should there be any change of mind.
The electronic button timing program offers the following features:
The length of time you want the valve to turn on.
Minimum length 3 seconds, maximum length 10 minutes.
In increments of 3 seconds. (3, 6, 9, 12 .... etc)
Factory default time is 6 seconds.
The length of time you want the valve to stay off once stopped.
Minimum length 0 seconds, maximum length 10 minutes Off Time.
In increments of 3 seconds (3, 6, 9, 12 .... etc)
Choose “0” (zero) if you do not want any Lockout time. (i.e. allow consecutive use.)
This function prohibits the user from turning on the valve again for the set period of time - that is, the valve
is “locked out” once turned off. It is useful when you want to limit the length of a shower to a set time and
prevent consecutive use, excessive use or water wastage. The Lockout time becomes effective every time
the switch turns off.
Once turned on, this function allows the user to stop the flow of water even if the set Run Time has not
finished yet. For example, a shower is set to run for 3 minutes but user decides to turn it off at 1 minute.
(Note that any lockout time still applies once it is turned off.)
Choose “Yes” if you want this function.
Choose “No” if you want the water to flow for the set Run Time without interruption.
Default factory setting is “No” (without Stop).
Automatically activates the valve every 24 hrs and runs for the set Run Time, particularly useful for
Legionella control and reducing the risk of bacteria growth in the water supply line.
Choose “Yes” if you want the valve to automatically turn on every 24 hrs.
Choose “No” if you do not want this function.
Default factory setting is “No” (without 24 hr flush).