ENVISION CONSOLE INSTALLATION MANUAL

LonWorks Name

SNVT Type

SNVT Index

SCPT Reference

SCPT Index

UCPT Index

Occupied Cooling Setpoint Input (Read/Write)

Standby Cooling Setpoint Input (Read/Write)

Unoccupied Cooling Setpoint Input (Read/Write)

Occupied Heating Setpoint Input (Read/Write)

Standby Heating Setpoint Input (Read/Write)

Unoccupied Heating Setpoint Input (Read/Write)

nciMinClgSetpt

SNVT_temp_p

105

4

Minimum Cooling Setpoint Input (Read/Write)

nciMaxHtgSetpt

SNVT_temp_p

105

3

Maximum Heating Setpoint Input (Read/Write)

nvoSpaceTemp

SNVT_temp_p

105

Space or Zone Temperature Value (Read Only)

nvoDischAirTemp

SNVT_temp_p

105

Discharge Air Temp

 Field Supplied Only

 (Read Only)

nvoEffClgSetpt

SNVT_temp_p

105

Effective Cooling Setpoint Value (Read Only)

nviSpaceTemp

SNVT_temp_p

105

Space or Zone Temperature Value Override(Write)

nvoEffHtgSetpt

SNVT_temp_p

105

Effective Heating Setpoint Value (Read Only)

nciAux5LevP

SNVT_lev_percent

81

Dehumidification Setpoint (Read/Write)

nciAux1Temp

SNVT_temp_p

105

147

Heating Freeze Protection Temperature Setpoint Value (Read/Write)

nciAux2Temp

SNVT_temp_p

105

148

Heating Freeze Protection Temperature Setpoint Value (Read/Write)

1st Stage Compressor Heating Output (Read Only)

1st Stage Compressor Cooling Output (Read Only)

Fan Output (Read Only)

Unit Mode of Operation (Read Only)

Unit Alarm mode (Read Only)

nciPropBand

SNVT_temp_diff_p

147

177

Heating/Cooling Prop Band Input (Read/Write)

nciRemoteSetptMin

SNVT_temp_diff_p

147

98

Warm/Cool Adjust Span (Read/Write)

nciRemoteSetptMax

SNVT_temp_diff_p

147

97

Warm/Cool Adjust Offset Value (Read/Write)

nciTempOffset

SNVT_temp_diff_p

147

11

Space or Zone Temperature Sensor Calibration Input (Read/Write)

nviSetpoint

SNVT_temp_p

105

General Setpoint Input (Read/Write)

nvoHtgFrzPro1Tmp

SNVT_temp_p

105

Heating Freeze Sensing Temperature Value (Read Only)

nvoHtgFrzSetpt

SNVT_temp_p

105

Heating Freeze Sensing Temperature Setpoint Value (Read Only)

nvoAlarms

SNVT_lev_cont

21

Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge 

Pressure alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze sensing 

alarm, 8=Faulty Freeze Sensor alarm,

9=Loss of Charge]

 (Read Only)

nvoPWMOut

SNVT_volt

44

ECM PWM Control signal value (Read Only)

nvoECMOvrd

SNVT_volt

44

ECM PWM Control signal Override (Read/Write)

nvoHumidity

SNVT_volt

44

Space Humidity value (Read Only)

nviAO2

SNVT_lev_percent

81

Spare PWM Output AO2 Command (Write)

nvoAO2

SNVT_lev_percent

81

Spare PWM Output AO2 Value (Read Only)

nciBypassTime

SNVT_time_min

123

SCPTbypassTime

34

Temporary Occupancy Time Period Input (Read/Write)

nvoEffectOccup

SNVT_occupancy

109

Effective Occupancy State (Read Only)

nviOccManCmd

SNVT_occupancy

109

Occupancy Override Command Input (Read/Write)

nviEmergOverride

SNVT_hvac_emerg

103

Emergency Override Input (Read/Write)

nvoFanStatus

SNVT_lev_disc

22

Fan Output Status (Read Only)

nvoAccStatus

SNVT_lev_disc

22

Accessory 2 Output Status (Read Only)

nvoLP_WVStatus

SNVT_lev_disc

22

Accessory 1 Output Status (Read Only)

nvoAlarmStatus

SNVT_lev_disc

22

Alarm Output Status (Read Only)

nviAlarmReset

SNVT_lev_disc

22

Alarm Reset Input (Read/Write)

nviFanSpeedCmd.StateSNVT_switch

95

Network equivelant of a thermostatic 'G' call. (Write)

nviComprEnable.State SNVT_switch

95

Network equivelant of a thermostatic 'Y1' call. (Write)

nviComprEnable.State SNVT_switch

95

Network equivelant of a thermostatic 'Y2' call. (Write)

nvoRV1Status

SNVT_lev_disc

22

Reversing Valve Output Status (Read Only)

nviOccSchedule

SNVT_tod_event

128

Occupancy Supervisory Scheduler Command Input (Read/Write)

nvoCompFanProv

SNVT_lev_disc

22

Compressor/Fan Proving Switch Status (Read Only)

nvoDirtyFilter

SNVT_lev_disc

22

Dirty Filter Switch Status (Read Only)

nvoComp2Status

SNVT_lev_disc

22

Compressor Hi Capacity Command Status (Read Only)

nviBO5

SNVT_lev_disc

22

Command for output BO5 used for Emg Heat-Interlocked with Fan DP9Read/Write)

nviBO9

SNVT_lev_disc

22

Command for output BO9(Read/Write)

nvoBO5

SNVT_lev_disc

22

Value output for BO5 used for Emg Heat (Read Only)

nvoBO9

SNVT_lev_disc

22

Value output for BO9 (Read Only)

nviDehumEna.State

SNVT_lev_disc

22

Dehumidification command-like a Humidistat (Read/Write)

Point Description

60

LonWorks

SCPTsetPnts

nciSetpoints

SNVT_temp_setpt

106

nvoUnitStatus

SNVT_hvac_type

112

LonWorks

Envision Console Controls

Summary of Contents for R-410A Residential

Page 1: ...formation Water Piping Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance Envision Console Installation Manual Geothermal Water Source Heat Pumps R 410A Refrigerant 0 75...

Page 2: ......

Page 3: ...Ground Water Systems 17 Electrical Connections 18 Auxiliary Heat Ratings 18 Unit Electrical Data 19 Fan Performance Table 19 Wiring Schematics 20 24 Envision Console Controls 25 39 Unit Startup Notes...

Page 4: ...Range 3 No Coating Extended Range Piping Option 4 No Coating Standard Range L Left R Right N A with chassis only Sound Kit A None Voltage B Blanket 0 208 230 60 1 2 265 60 1 Auxilliary Electric heat...

Page 5: ...the packag ing if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Wa...

Page 6: ...3 3 49 1 11 8 4 3 cm 127 0 31 1 65 2 23 4 88 9 15 6 8 3 124 7 29 8 10 9 09 12 15 18 4 0 5 7 8 1 3 2 6 47 B3 0 193B 47 B3 0 193B 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3 232 B 0 0 19 2 4 B6 C B7 B 0...

Page 7: ...1 2 5 49 1 11 8 4 3 cm 127 0 32 0 73 9 23 4 88 9 15 6 6 4 124 7 29 8 10 9 09 12 15 18 3 D3 AB71 AB 7 4 0 93 B 0 2 3 13 0 93 3253 4 35 A A6 E 6 7 8 1 4 3 2 5 0 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3...

Page 8: ...6 6 1 124 7 30 5 10 9 in 55 0 12 6 29 1 9 2 35 0 6 1 2 5 54 1 11 8 4 3 cm 139 7 32 0 73 9 23 4 88 9 15 6 6 4 137 4 29 8 10 9 09 12 15 18 47 B3 0 193B 47 B3 0 193B 2 3 1 6 7 8 4 0 5 0 756B 3BC B 4 B 3...

Page 9: ...2 4 1 7BG 0 B6 A723A 3 31B 71 63 B 23 0 7 3 3AA AE7B16 B7 4 B7 AE7B16 B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 E D B 53 B3 7 A 4F 3 B3 E AB B B7 A G B7 4CA32 4CA32 27A1 31B B7 0...

Page 10: ...47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA 3 2 3 3 7 5 1 0 E3 113AA 3 1 3AA 113AA 3 47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA 3...

Page 11: ...D3A B7 6 A3 97BA 1 23 A B3 2 7 1 31B7 47 B3 6 2G 0 F B7 3 31B 71 63 B B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 1 B 3 3 D3 4 113AA B 1 B 0 F 2 3 44 AE7B16 1 3AA 113AA 3 3 D32 4 1...

Page 12: ...47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA 3 2 3 3 7 5 1 0 E3 113AA 3 1 3AA 113AA 3 47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA...

Page 13: ...ate mounting height is increased by the thickness of the shims used Position backplate in desired equipment location To further reduce the operating sound level of the unit 1 8 inch thick rubber matti...

Page 14: ...o the units An air vent must be installed in the water distribution system The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve The pi...

Page 15: ...should be installed on both the supply and return water lines of the unit Flow control valves should be installed on the water discharge line It is recommended that P T ports be installed on the suppl...

Page 16: ...inet repositioning pieces 4 1 2 and 3 into the locations directly opposite the original positions Secure by replacing mounting brackets Note Be sure that louvers on the grille assembly are facing the...

Page 17: ...rotect the sys tem from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchange...

Page 18: ...pliance in your area Note For open loop groundwater systems or systems that do not contain an antifreeze solution set SW1 Switch 2 to the WELL position Refer to the Dip Switch Field Selection table Sl...

Page 19: ...L S X2 X1 W2 Field Connections Unit Connections 24 VAC COMMON COMPRESSOR REVERSING VALVE FAN LOCKOUT SIGNAL SHUTDOWN NIGHT SETBACK LOAD SHED Requires common connections or 24 VAC for activation Red Bl...

Page 20: ...500 fpm by 0 16 in wg Unit Electrical Data Model Rated Voltage Voltage Min Max Compressor Fan Motor FLA Total Unit FLA Min Circ Amp Max Fuse HACR MCC RLA LRA 09 208 230 60 1 197 253 6 4 4 1 21 0 0 50...

Page 21: ...White 20 Orange 14 Orange 21 Black 29 Red 30 Black Black 12 White 18 Red 11 Red 19 Red 17 24 V Accessory 24VAC Shutdown Red 15 Red 16 NOTE 1 T ST CC Compressor Contactor HP High Pressure Switch LP Low...

Page 22: ...ack 27 RB 4 2 5 Red EH T2 T1 L2 White White L1 EH Normal RV DT ON OFF Damper Sw Damper Motor D Fan Mode Sw 4 5 2 E1 E1 AQ Blk Wht 24 Blk Wht 23 Black 22 White 18 Blue T6 NOTE 2 3 1 RB 3 1 Black 37 Blu...

Page 23: ...ated ON Current fault or Output display mode activated Normal Standard timings Well Open loop freeze sensing setting 30 F Normal Unit status display Normal Standard thermostat operation Normal Standar...

Page 24: ...g information for specific thermostat hookup instructions Red Black 25 RB Gray 42 White 28 Black 29 Red 30 Damper Motor Off On DAMPER MODE DT D Blue Wht 35 MV Black 31 Red 32 Handi Box Ground Lug Unit...

Page 25: ...eeze protection Field Zone Sensor Wiring 3 Acc 1 output is cycled with the compressor 4 Acc 2 output is cycled with the fan 5 R C Y1 O and G inputs are for use with a wall mounted thermostat A23 A13 A...

Page 26: ...tional Medium User Interface MUI can be used as a field service tool Standalone Unit Mounted Digital Dial Sensor Remote Mounted Standard Thermostat Remote Mounted Sensor FX10 w N2 FX10 Control functio...

Page 27: ...he Versatec microprocessor board provides control of the entire unit as well as outputs for status modes faults and diagnostics The control system is a microprocessor based control board that is locat...

Page 28: ...e sensing fault bypass delay 2 minutes Power on delay 5 minutes Normal Control Timing Operational Logic Blower off delay 5 seconds Compressor on delay 2 seconds Short cycle delay 15 seconds Miniumum c...

Page 29: ...r Coil Low Temperature Freeze Sensing Condensate overflow sensing Lockout mode control Emergency shutdown mode Random start and short cycle protection Short Cycle Protection Allows a minimum compresso...

Page 30: ...talled emergency heat in the event that the compressor is locked out This input can also be commanded on from a BAS as needed An alarm history can be viewed through the MUI and will be held in memory...

Page 31: ...or becomes unreliable at any time compressor operation will immediately be suspended until the problem is corrected This should be displayed as an alarm on the BAS and the MUI This alarm will be repor...

Page 32: ...capacity for a minimum of 30 seconds before the full capacity com pressor output can be enabled During low capacity compressor operation the ECM2 blower will operate in medium speed and will operate...

Page 33: ...arm History Reporting If a fault occurs the fault will be recorded in history for display on the medium user interface in the History Menu Each fault type will be displayed in the history menu with a...

Page 34: ...ter to Air Welcome Info Status Temps Outputs Settings Maint Alarms Alm History WFI Envision Series PROFXENV XX 3 8 07 Info Run Mode Auto Eff Occup y Occ Y1 Input OFF Y2 Input OFF G Input OFF O Input O...

Page 35: ...p 0 Bad Sensor 0 Alm History NOTE This FX10 application implements an alarm history which is reset only by cycling power This history shows on the Alm History page Any alarm showing 4 events has occur...

Page 36: ...ting Freeze Sensing Temperature Value Read Only ADF 40 nvoHtgFrzSetpt Heating Freeze Sensing Temperature Setpoint Value Read Only ADF 41 nvoAlarms Alarms Enumerated 0 no alarms 1 condensate alarm 2 Co...

Page 37: ...Compressor low Suction Pressure alarm 4 Freeze sensing alarm 8 Faulty Freeze Sensor alarm 9 Loss of Charge Read Only nvoPWMOut SNVT_volt 44 ECM PWM Control signal value Read Only nvoECMOvrd SNVT_volt...

Page 38: ...9 Loss of Charge Read Only Analog Input 0 8 Present_Value 85 WFI ECM Cmd Output Present_Value ECM PWM Control signal value Read Only Analog Output 1 2 Present_Value 85 WFI ECM Fan Ovrd Present_Value...

Page 39: ...network to send space temperature values to the heat pump controller volatile these will supersede any temperature sensor connected to the space temperature Analog Input Analog Value Type 2 2 1 Occupi...

Page 40: ...k command equivalent of a thermostatic G call 14 3 Compressor Cmd Y1 Write allows a network command equivalent of a thermostatic Y1 call 14 4 Compressor Cmd Y2 Write allows a network command equivalen...

Page 41: ...able in five models with equipment rated fuses to provide addi tional circuit protection The fuses are panel mounted to allow easy inspection and removal without removing the cover on the disconnect C...

Page 42: ...ng setpoint must be set below room temperature 3 Be sure that the compressor and water control valve or loop pump s are activated 4 Verify that the water flow rate is correct by measuring the pressure...

Page 43: ...rmance based on entering air temperatures of 80 F DB 67 F WB Heating performance based on entering air temperature of 70 F DB Operating Limits F C F C Air Limits Min Ambient Air 45 7 2 45 7 2 Rated Am...

Page 44: ...85 for water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEATING CYCLE ANALYSIS EXPANSIO...

Page 45: ...09 1 2 1 0 0 9 0 8 0 7 0 6 1 8 2 3 2 2 2 0 1 9 1 8 2 5 3 8 3 7 3 5 3 3 3 1 12 1 5 0 9 0 8 0 7 0 6 0 5 2 3 1 7 1 5 1 4 1 3 1 1 3 5 3 0 2 7 2 5 2 4 2 2 15 2 0 1 7 1 6 1 5 1 4 1 3 3 0 3 3 3 2 3 0 2 9 2...

Page 46: ...ssure Note On open loop systems if the installation is in an area with a known high mineral content 125 PPM or greater in the water it is best to establish with the owner a periodic maintenance schedu...

Page 47: ......

Page 48: ...nace International Inc 9000 Conservation Way Fort Wayne IN 46809 www waterfurnace com WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFurnace has a policy of continu...

Reviews: