Envirowise XT155H Installation Instructions

SERVICE

Troubleshooting (Continued)

  Symptom 

Possible Reason 

Troubleshooting Procedure

 

Troubleshooting Procedure for Performance  

Related Issues
This method of diagnosis is used to function 

check the internal components in the dehumidi-

fier. This is to be used when a performance issue 

is suspected.
1.  Set the humidity controller all the way to the 

most humid setting or off position – Did the 

unit shut off?

2.  If yes, turn the fan setting to the ON position – 

does the fan start?

3.  If fan starts, leave in the fan ON position and 

set the humidity all the way to driest setting. 

May have to wait 5 minutes for the compressor 

to start.

4.  Listen for a distinct buzzing/humming sound 

of a compressor starting up – do you hear this 

noise?

5.  If compressor is running and continues to run, 

after about 15 minutes you should feel a slight 

increase in air temperature being discharged 

out of the discharge air side of the unit.

6.  If so, depending on your environmental  

conditions (temp/Rh%), you should see some 

water production out of the hose within  

30 minutes or so. (Note: If the room  

temperature is 55 degrees or below and/or  

in area of low relative humidity, the  

dehumidifier will produce little to no water.)

7.  Collecting the water removed in a 24 hour period 

will give a measurement of performance. 

 

WARNING!

 

ELECTRICAL SHOCK HAZARD:

  

ELECTRICAL POWER MUST BE PRESENT 

TO PERFORM SOME TESTS. THESE TESTS 

SHOULD BE PERFORMED BY A QUALIFIED 

SERVICE PERSON.

Fan is not running. 

Dehumidification  

or fan is being 

called for.

1.  Loose connection in  

fan circuit.

2.  Obstruction prevents 

fan impeller rotation.

3. Defective fan.
4. Defective fan relay.

Low dehumidification 

capacity (evaporator 

is frosted  

continuously).  

Dehumidification is 

being called for.

1.  Defrost thermostat loose 

or defective.

2. Low refrigerant charge.
3.  Dirty air filter(s) or air flow 

restricted.

4.  Excessively restrictive 

ducting connected to unit.

No ventilation. 

Ventilation is being 

called for.

1.  Loose connection in  

ventilation control circuit.

2.  Loose connection in 

damper power circuit.

3.  Defective fresh air 

damper.

Dehumidifier  

removes some  

water, but not as 

much as expected. 

1.  Air temperature and/or 

humidity have dropped. 

2.  Humidity meter and/or 

thermometer used are  

out of calibration.

3.  Unit has entered defrost 

cycle. 

4.  Dirty air filter(s) or air flow 

is restricted. 

5.  Defective defrost  

thermostat. 

6. Low refrigerant charge. 
7.  Air leak such as loose 

cover or ducting leaks. 

8. Defective compressor. 
9. Restrictive ducting. 

Summary of Contents for XT155H

Page 1: ...de the ultimate in comfort health and property protection through Dehumidification Fresh Air Ventilation Optional Air Filtration TS 978 9 18 Rev A P N EDHUM155 Serial No Install Date Installing Dealer...

Page 2: ...Determine Ventilation Requirements 14 Controls 15 Filter Instructions 18 Optional Accessories 19 Service 20 Troubleshooting 20 TABLE OF CONTENTS Ingersoll Rand is committed to manufacturing quality p...

Page 3: ...USE PROPERTY DAMAGE OR INJURY INSTALLATION SERVICE AND MAINTENANCE MUST BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN DEHUMIDIFIER IS HEAVY HANDLE WITH CARE AND FOLLOW INSTALLATION INSTRUCTIONS DO NO...

Page 4: ...Pints Day 123 Pints Day Efficiency 7 3 Pints kWh 6 0 Pints kWh Duct Connections 6 Round Inlet 10 Round Inlet 10 Oval Outlet Air Filter MERV 11 Mini Pleat Efficiency 65 ASHRAE Dust Spot Size 16 x 20 x...

Page 5: ...cation Considerations Allow sufficient clearance to handle the unit s overall dimensions as well as the necessary return and supply ductwork to the unit Allow sufficient clearance for filter removal a...

Page 6: ...using the screws provided The 6 duct should be capped if fresh air is not desired If setting up the unit to provide fresh air ventilation see page 14 Return Air Inlet Attach 10 diameter duct collar t...

Page 7: ...e relative humidity such as near HVAC supply registers near exterior doors on an outside wall near a window or near a water source The screw terminals on the Envirowise XT155H and the control are labe...

Page 8: ...e Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to close the float switch The pump also contains a safety float switch The white leads from...

Page 9: ...structure Use a minimum 10 diameter round or equivalent rectangular duct for total duct lengths of up to 25 Use a minimum 12 diameter round or equivalent rectangular duct for longer lengths Grills or...

Page 10: ...em thermostat control with integrated Dehumidification software should be located remotely from the dehumidifier and placed in a central location Attic Installation Dedicated Return to HVAC Return Duc...

Page 11: ...Motorized Damper Envirowise Supply HVAC Return to HVAC Supply GENERAL SET UP Recommended HVAC Ducting Installations The HVAC fan must be interlocked from the system control to turn on when the dehumi...

Page 12: ...to utilize multiple rooms to allow air inside the structure to properly circulate Proper air distribution is important to ensure even humidity control and heat distribution throughout the structure A...

Page 13: ...and outside air conditions When a 6 motorized damper is used a digital control is required It may be necessary to use 8 duct work if additional fresh air is required over 150 CFM In cold climates or a...

Page 14: ...ecord the required CFM ____________ Determine Ventilation Requirements The MINIMUM ventilation requirement is calculated using ASHRAE 62 2 2016 Use one or both of the options below to determine your v...

Page 15: ...tallation Guide for instructions on setting up AUX1 contacts on relay panel for Ventilator operation and AUX2 contacts for dehumidifier operation See TCont 824 Installation Guide for instructions on s...

Page 16: ...cle Timer Automatic fan cycling to ensure dry and clean coils Auto Reboot Resumes operation with prior settings in the event of power failure Envirowise D30 Digital Control Wiring Controls See D30 man...

Page 17: ...ol DMPR 24VAC Power Transformer Neutral Side Spare Terminal Open Terminal Block Control Operation Compressor ON Fan ON Make contact between 24V and DEHU terminals Compressor OFF Fan ON Make contact be...

Page 18: ...NG THE FILTER Step 1 The filter door is attached to the cabinet by three hinges Release the latch from the cabinet by pulling it towards the front of the unit The filter door will swing open to gain a...

Page 19: ...D30 Control W Remote E4037878 MERV 11 Filters 4 Pack E4037885 MERV 11 Filters 12 Pack E4037887 MERV 14 Filter Housing E4037891 MERV 14 Filters 3 Pack E4037905 Pump Kit E4037872 Hang Kit E4037861 6 Mo...

Page 20: ...ogether the fan only should run Disconnect when complete 8 Jumper a wire from the 24V and DEHU terminal fan and compressor should run Disconnect when complete 9 If this test works then the field contr...

Page 21: ...or in area of low relative humidity the dehumidifier will produce little to no water 7 Collecting the water removed in a 24 hour period will give a measurement of performance WARNING ELECTRICAL SHOCK...

Page 22: ...onnections at control and unit 4 Reset circuit breaker button on dehumidifier WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL POWER MUST BE PRESENT TO PERFORM SOME TESTS THESE TESTS SHOULD BE PERFORMED BY...

Page 23: ...23 Envirowise XT155H Installation Instructions...

Page 24: ...perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingersoll Rand has a policy...

Reviews: