![Envirotec ES D15-HP Installation, Operation & Maintenance Manual Download Page 6](http://html1.mh-extra.com/html/envirotec/es-d15-hp/es-d15-hp_installation-operation-and-maintenance-manual_2416189006.webp)
Page
6
IM,
O&M Instructions – Heat Pump
6.
0 Air Curtain
Performa
n
ce Data
AIR CURTAIN MODEL
ES
D-ES15-HP (Type D 1500 HP)
OUTDOOR UNIT
RAV-
SP1104AT-E
CAPACITY CODE
HP
4
Heating Capacity
kW
10.3
Heating COP
kW/kW
3.11
Standard Air Flow
l/s
630
Standard Air Flow
m
3
/h
2268
Fan Motor Power (min.-max.)
kW
0.185-0.335
Fan Motor Current (max.)
A
4.3
Power Input Indoor
kW
0.32
Power Input Outdoor
kW
3.00
Power Input System
kW
3.32
System Run Current
A
13.91
AIR CURTAIN UNIVERSAL
ES
Type D 1500 HP
Door Width
mm
1500
Maximum Door Height
m
3.0
Sound Pressure Level
dBA
54
Sound Power Level
dBA
69
Pipe Connections Gas Side
mm - ”
22.2 - 7/8
Pipe Connections Liquid Side
mm - ”
15.9 - 5/8
Height/Width/Depth
mm
340/1500/520
Weight
kg
73
Power Cable From Outdoor To Indoor
3 core + earth
OUTDOOR UNIT
RAV-
SP1104AT-E
Heating Capacity
kW
2.4 - 13.0
Heating Power Input
kW
2.52
Operating Range Cooling/Heating
°C
43 to -15/15 to -15
Standard Air Flow
l/s
1683
Standard Air Flow
m
3
/h
6060
Sound Pressure Level Cooling/Heating
dBA
49/50
Sound Power Level Cooling/Heating
dBA
66/67
Refrigerant Base Charge/Chargeless To
kg/m
3/1/30
Refrigerant Additional Charge Main Liquid Side
g/m
40
Minimum/maximum piping length
m
3/75
Height Difference Outdoor To Indoor
m
±30
Pipe Connections Gas Side
mm - ”
15.9 - 5/8
Pipe Connections Liquid Side
mm - ”
9.5 - 3/8
Drain Port Connector Hose Inner Diameter
mm
16
Height/Width/Depth
mm
1340/900/320
Total Weight
kg
93
Maximum Run Current
A
10.43
Power Supply
1 phase 230 V 50 Hz
Suggested Fused Supply
A
16
Performance data for heating is laboratory tested to standard EN14511:2011 air curtain operating at high fan speed, outdoor air
temperature 7
º
C DB/6
º
C WB and indoor air temperature 20
º