8
NA0702P01 REV A
12/03/2019
5.5
Set Points Menus
Trouble Set Points and Run levels are accessed via the “Set Points” button in the Main Menu. Overpressure Amperage
and Run Limit may be edited via the trouble parameters panel. See sections 6.2.2 and 6.2.3 for more information
regarding these set points. Run levels 1-4 and the high level set point may be edited through the Run Levels menu. See
section 6.2.1 for more information regarding these set points. The arrows in the upper left will return the user to the
previous menu.
5.6
Options Menu
The options menu contains various options. The software version is displayed on this screen, and the user can access the
cold start and factory default options from this menu. In order to use these functions the buttons must be held for at
least 3 seconds (this is to prevent accidental deletion of operational data). See sections 6.2.4 and 6.2.6 for more
information regarding these options. The alarm light and buzzer can also be tested via this menu by simply holding the
respective button.
5.6.1
Voltage Data Menu
The Voltage Data Menu shows min/max/average voltages and overvoltage and brownout set points. These set points
are not editable. The min/max/average values may be reset by holding the “reset” button on the left for at least 3
seconds. The Voltage Data Menu is accessed via the options menu.
Figure 6 – Run Levels and Trouble Set Point Menus
Figure 7 – Options menu
Figure 7 – Options Menu
Figure 8 – Voltage Data Menu