A firestop
is required
through the
rear wall.
23"
(584mm)
13
5
/
8
"
(346mm)
61" (1.55m)
minimum
Ceiling Height
Above the unit
&
84" (2.13m)
minimum
Ceiling Height in
Front of the unit
40
1
/
4
"
(1022mm)
Figure 12. Dimensions for Framing the Firebox.
We recommend
installing these
frame pieces
after the unit
is installed.
12
3
/
8
"
(315mm)
5
5
/
16
"
(135mm)
45
o
34
15
/
16
"
(887mm)
40
1
/4"
(1022mm)
Table 2. Framing Dimensions.
Firebox Framing
Depth
135⁄8”
34.6 cm
Width
23”
58.4 cm
Height
401⁄4”
102.2 cm
Figure 13. Dimensions for Top
Framing the Firebox.
The fireplace can be located along a wall,
raised or at floor level, or in a corner. There
are specific framing measurements for each
situation. The basic opening should have the
dimensions shown in Figure 12 and Table 2.
Refer to Figure 1 and Table 3 for the placement
of the gas and electrical inlets. When the basic
framing is done and the unit is installed the
three (3) top pieces of the framing should be
installed Figure 13.
Table 3. Inlet Placement Dimensions, refer to Figure 1.
Side Inlet: Gas Electrical
Distance back
6
3
/
16
”
15.8 cm
81⁄2
21.5 cm
Distance up
15⁄8”
4.1 cm
1
11
/
16
”
4.3 cm
Bottom Inlet: Gas Electrical
Distance back
5
9
/
16
”
14.1 cm
8
11
/
16
”
22.0 cm
Distance
from side
37⁄8”
9.8 cm
43⁄4”
12.1 cm
13
Initial Installation
QUALIFIED INSTALLERS ONLY
P
LACEMENT
AND
F
RAMING
:
The fireplace must have a strong and level surface to be placed on. The surface should be made of wood
or a non-combustible material, not carpet.
The framing boards may touch the top, side and back standoffs, but
no insulation or other material
can be placed between the frame and the standoffs.