background image

40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10

9
8
7
6
5
4
3
2
1

1  2 

3  4  5  6  7  8  9  10  11  12  13  14

HORIZONTAL RUN

ft

VER

TIC

AL RISE

INSTALLATION

PROHIBITED

INSTALLATION

PROHIBITED

Figure 35. Possible Vent Configurations for Top 

Vented Vertical and Horizontal Terminations.

Initial Installation

QUALIFIED INSTALLERS ONLY

a

llowable

 c

o

-a

xial

 v

ent

 c

onfigurations

:

Figures 35 & 36 show the range of possible vent configurations if the unit is top or rear vented, for vertical 

and horizontal terminations. Any layout that remains within the shaded areas is acceptable. Having the 

fewest number of elbows is ideal, as they tend to disrupt air movement. Using 45˚ elbows is preferable to 

using 90˚ elbows. Also, a shorter vent system will perform better than a longer one. When top vented, the 

total length of horizontal vent pipe can not exceed 14 feet (4.27m) and the total vent length can not exceed 

44ft  (13.4m).  Any  combination  of  rise  and 

run can be used as long as it lays within the 

shaded area (a total of two (2) 90

˚

 elbows or 

four (4) 45

˚

 elbows can be used. In addition 

to what is shown, if a 90

˚

 elbow is used in 

the  horizontal  plane, 3  feet  (91.4cm)  must 

be subtracted from the allowable horizontal 

run (for each 45

˚

 elbow, 1½ feet must be 

subtracted).

Note:  Air  restrictors  (supplied  with  the 

unit)  are  required  for  vertical  venting  runs 

of 8ft (2.44m) or taller. See 

a

Ir

 r

estrIctor

 

s

ettIng

s for more information

Note: Minimum length of co-linear venting 

is 8ft (2.44m) and maximum length is 40ft 

(12.19m)

28

40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10

9
8
7
6
5
4
3
2
1

1  2  3  4  5  6  7  8  9   

HORIZONTAL RUN

ft

INSTALLATION

PROHIBITED

1

2

3

4

5

6

1

2

3

4

5

7

VER

TIC

AL RISE

HORIZONTAL RUN

Figure 36. Possible Vent Configurations 

for Rear Vented Vertical and Horizontal 

Terminations.

Summary of Contents for Q1C

Page 1: ...ing property damage personal injury or loss of life Installation and service must be performed by a qualified installer service agency or the gas supplier Version Française www enviro com fr html 4001609 W A R R A N T Y R E G I S T R A T I O N e n v i r o c o m w a r r a n t y Q1C D I R E C T V E N T F I R E P L A C E N O VA ...

Page 2: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Massachusetts installations Warning This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massac...

Page 3: ...t be performed by a qualified installer service agency or gas supplier This installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the Natural Gas and Propane Installation Code CSA B149 1 To prevent injury do not allow anyone who is unfamiliar with the stove to operate it To prevent injury if the pilot or pilot and burners h...

Page 4: ...ing Material 17 Standoffs 18 Corner Installation 19 Adjusting Install Depth 20 Mantle and Non Combustible Clearances 22 Direct Vent 23 Vent Termination Restrictions 24 Venting Clearances 25 Approved Venting Parts 25 Vent Configurations and Restrictor Settings 25 Horizontal Termination Rear Vent w No Rise 27 Allowable Co Axial Vent Configurations 28 Co Linear Venting Adapter Kit 50 2982 28 Air Rest...

Page 5: ... 33a 2014 VENTED GAS FIREPLACE HEATERS CAN CGA 2 17 M91 R2009 GAS FIRED APPLIANCES FOR HIGH ALTITUDES This ENVIRO Q1C Fireplace Has been certified for use with either natural or propane gases See rating label Is not for use with solid fuels Is approved for bedroom or bed sitting room IN CANADA must be installed with a listed wall thermostat IN USA see current ANSI Z223 1 for installation instructi...

Page 6: ...ause the safety screen to protroud past the front of the surround panel If a reduced install depth is required the extension brackets must be re moved Refer to Initial Installation Adjusting Install Depth for instructions 21 508mm 16 1 2 420mm 18 3 4 476mm 24 3 4 627mm 21 533mm 18 3 4 476mm 14 356mm 6 5 8 168mm 25 1 4 641mm 5 3 8 136mm 27 1 2 700mm 4 3 8 112mm 16 7 8 479mm 3 5 8 93mm 14 1 4 361mm ...

Page 7: ...HAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in...

Page 8: ...and mostly blue the fireplace is getting too much air Therefore the air shutter should be closed pulled out slightly until the correct flames are achieved Flames that are very orange with tall dark stringy tips are not getting enough air Open push in the venturi until the flames clean up If the venturi is opened or closed all the way and the correct flames cannot be attained turn off the gas and c...

Page 9: ... Figure 7 Fan Control Burner Lighting A Make sure the pilot is lit B Turn gas control knob COUNTER CLOCKWISE to ON C Flip the burner switch to ON D Turn HI LO knob to the desired flame height The blower will come on only when the fireplace is up to temperature approximately 15 minutes The speed of the fan can be changed by turning the fan control knob The blower will continue to operate automatica...

Page 10: ...the amount of use the glass should require cleaning no more than two or three times a season Do not clean the glass when it is hot Cleaning The Firebox Remove the coal set carefully as it is very fragile Gently remove all the coals and place on a paper towel Vacuum the bottom of the firebox thoroughly Carefully clean any dust off the coal set and remove any lint from the burner and pilot At this t...

Page 11: ...e Glass Door Removal In order to install the coal set and for regular cleaning the glass door must be removed There are two 2 door latch mechanisms on top the glass door as shown in Figure 8 Each latch has a hole at the front to use the door tool supplied with the unit to pull the mechanisms straight out and up When the top latches are unhooked lean the door forward and then lift it up out of the ...

Page 12: ...arts List 1 Orifice NG 46 DMS or LP 1 2 mm 1 Pilot Injector NG 0 62 mm LP 0 35 mm 1 Installation instruction sheet 1 Conversion label Carefully inspect all parts supplied with this conversion kit If any parts have been damaged or are missing contact your dealer distributor or courier company to have them replaced before starting this installation Burner Removal The burner may need to be removed fo...

Page 13: ...nit CAUTION The gas supply must be shut off prior to disconnecting the electrical power and before proceeding with the conversion Allow the valve and unit to cool down to room temperature 2 Remove the glass door as shown in the Maintenance and Service Glass Door Removal 3 Carefully remove the coal set 4 Remove the burner as shown in the Maintenance and Service Burner Removal 5 Convert the burner o...

Page 14: ...ase until the correct flame is achieved 13 Relight the main burner in both the HI and LO positions to verify proper burner ignition operation and proper flame appearance Confirm the inlet and manifold pressures are within the acceptable ranges as directed in section Intial Intallation Gas Line Connection and Testing If the Q1 has been installed at an altitude higher than 2000ft 610m it is required...

Page 15: ...touch the top and back standoffs but only the supplied insulating material can be placed between the frame and the standoffs A horizontal steel stud may be used at the height shown to support the bottom edge of the non combustible material see page 22 The gas line inch NPT should be Brought to the left side of the fireplace The location should be chosen so the fireplace will be at least 36 inches ...

Page 16: ... 28 screws total as shown in Figure 17 Vent Collar Base Plate Exhaust Spigot Cover Plate Figure 17 Vent Conversion Step 1 Locating Notch Step 2 Switch the removed parts around as shown in Figure 18 and re install all 28 screws To correctly install the base plate keep the locating notch on each side at the bottom Also note the exhaust spigot uses a lower set of holes when setup as a rear vent Figur...

Page 17: ...insulation are required Place the ceramic board on top of the unit first and then place the insulation on top of the ceramic board as shown in Figure 19 Top Vent When using the top vent configuration only the figerglass insulation is required Cut a notch in the insulation to fit around the vent collar and place on top of the unit as shown in Figure 20 Fiberglass Insulation Ceramic Board Figure 19 ...

Page 18: ... the thickness of the wall material The rear standoffs attach to the back corners of the unit and are not adjustable Combustible material can touch the standoffs but must not encroach past them If the Q1C is being installed into a pre existing masonary fireplace it is not necessary to use the standoffs Installation of the standoffs will require a T20 screwdriver Remove the installed screws in the ...

Page 19: ...e walls Figure 23 Dimensions for a corner installation rear vented Figure 24 Dimensions for a corner installation top vented 19 A B Outside W all I n s i d e W a l l C D E F Outside W all I n s i d e W a l l A B C D E F Corner Installation Dimensions Top or Rear Vent Dimension C Set 15 260mm Dimension E Set 25 641mm Minimal Panel 3 or 4 sided Dimension A 437 16 1103mm Dimension B 3011 16 779mm Dim...

Page 20: ...e the Top Extension to the Cabinet see Figure 26 2 Remove the five 5 screws on each Side Extension see Figure 26 Side Cabinet Extensions A DETAIL A Figure 26 Removing Extension Screws Step 3 5 on next page Figure 25 Q1 as Shipped Surround Panel Install Depth Surround Panel Install Depth Modern 14 25 in Modern 12 375 in Contemporary 14 25 in Contemporary 12 375 in Minimal 15 00 in Minimal 12 375 in...

Page 21: ...ckets re install the removed screws and install the standoffs as directed in the Initial Installation Standoffs section of the manual standoffs not required for insert applications 4 If using the biggest depth 3 or 4 sided minimal surround re install the extension brackets in the position noted in the Figure 28 5 Install the side standoffs if required onto the side extension brackets using the for...

Page 22: ...of door to side wall 1 2 12 7mm thick non combustible facing When installing the Q1C as a zero clearance fireplace the correct clearances and materials must be used Above Unit A minimum 10 of thick non combustible facing material with a R Value no less than 0 26 must be used see Figure 29 In Front of Unit A minimum 12 of 1 thick non combustible material with a R Value no less than 2 27 K value no ...

Page 23: ...ust be installed in the correct locations on the top of the Q1C Venting Fireplace Inserts When using the co linear venting adapter kit 50 2982 the Q1C may be installed and vented into any solid fuel fireplace that has been installed in accordance with the National Provincial State and local building codes and has been constructed of noncombustible materials Please reference the information in Tabl...

Page 24: ... may be opened C 12 in 30 cm Clearance from permanently closed window to prevent condensation D 24 in 60 cm Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 ft 60 cm from center line of terminal E 18 in 45 cm Clearance to unventilated soffit F 12 in 30 cm Clearance to outside corner G 12 in 30 cm Clearance to inside corner H 3 ft 91 cm within a h...

Page 25: ... 51 mm above and 1 38 mm on the sides and bottom When combustible materials are directly above a 90 elbow 3 76 mm of clearance are necessary Table 6 Vent Pipe Minimum Clearances Vertical Pipe to the Side Walls Horizontal Pipe to the Sides Bottom Above an Elbow Above the Unit Above an Elbow Not Above the Unit Above Horizontal Vent Pipe Wall Frame 8 203mm or less Hard Pipe 1 25 4 mm 1 38 1 mm 3 76 2...

Page 26: ...T 48 SV4L48 4D4 48 pipe length 945 4DT EL45 SV4EBR45 4D45B 45 elbow black 990 4DT EL90 SV4EBR90 4D90B 90 elbow black 950 4DT VS SV4VS Vinyl siding standoff sheild 942 4DT WT SV4RSN 4DWT Wall thimble 953 4DT SC SV4FC 4DSC Storm collar 963 4DT FS SV4BF 4DFSP Fire stop 988 4DT WS B SV4BM 4DWS Wall strap support band 970 4DT HKA SV0SHK 4DHTK1 Horizontal termination kit SD Basic Kit SEL Kit A SC Standa...

Page 27: ...ination Figure 33 Corner Rear Vent No Vertical Rise Approved through wall thimble The Q1C can be installed in rear vent applications with no vertical rise within the parameters as shown in Figures 33 and 34 Figure 34 Flat to Wall Rear Vent No Vertical Rise 7 18 cm Min vent length 24 61 cm Max vent length Approved horizontal termination Approved through wall thimble 27 ...

Page 28: ...the total length of horizontal vent pipe can not exceed 14 feet 4 27m and the total vent length can not exceed 44ft 13 4m Any combination of rise and run can be used as long as it lays within the shaded area a total of two 2 90 elbows or four 4 45 elbows can be used In addition to what is shown if a 90 elbow is used in the horizontal plane 3 feet 91 4cm must be subtracted from the allowable horizo...

Page 29: ...t the depth of the unit please refer the the Initial Installation Adjusting Install Depth section of the manual Note The co linear adapter kit can only be used in the top vent configuration WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury Adapter Kit Conten...

Page 30: ...onger be used Base Plate 4 Exhaust Spigot Cover Plate Vent Collar Figure 39 Removal of Co Axial Venting Step 2 Install the components supplied in the adapter kit as shown using the screws that had been removed from the unit in Step 1 The gasket on the bottom side the vent plate adapter and exhaust spigot flange gasket will be sandwiched together when properly installed Cover Plate 3 Exhaust Spigot...

Page 31: ... see Secondary Installation Optional Porcelain Panels Installation and Removal then remove the set screws as shown on each side of the firebox Next install the restrictors at the correct setting and tighten the set screws to hold them in place Air Restrictor Settings Length of Vertical Vent Propane Natural Gas Less than 8ft 2 44m co linear or co axial No Restriction Required No Restriction Require...

Page 32: ...The air gap prevents excessive heat from possibly melting the vinyl siding 5 Horizontal pipes must be supported every 3 feet 914 mm Plumber s all round strap will suffice 6 When running horizontal pipe clearances to combustibles must be maintained 1 inches 38 mm sides 1 inches 38 mm bottom and 2 inches 51 mm top Step 1 Set the fireplace in the desired location Check to determine if wall studs will...

Page 33: ...from the vent cap assembly to the outer wall of the vent pipe Bend any remaining portion of the strap back towards the vent cap Security Secure Vent uses a twist lock cap Step 5 Position the horizontal vent termination in the center of the 10 inches 25 4 cm square hole and attach to the exterior wall with the four screws provided The arrow on the vent termination should be pointing up Run a bead o...

Page 34: ...hing to the roof with roofing nails Use a non hardening sealant between the uphill edge of the flashing and the roof Insure the roofing material overlaps the top edge of the flashing Verify that you have at least the minimum clearance to combustibles at the roof line STEP 8 Continue to add pipe sections until the height of the vent cap meets the minimum code requirements Refer to Figure 44 and Tab...

Page 35: ...ing should be framed to 10 254 mm x 10 254 mm inside dimensions in the same manner as shown in Figure 32 4 Any occupied areas above the first floor including plumber s tape connected to wall strap Wall strap 45 elbows x2 closets and storage spaces which the vertical vent passes through must be enclosed The enclosure may be framed and sheet rocked with standard building materials However consult th...

Page 36: ... removal of smoke shelf or baffle removal of ember catches removal of log grate removal of viewing screen curtain and removal of doors THE ORIGINAL FIREPLACE MAY NEVER BE RETURNED TO SOLID FUEL USE IN THIS CONDITION Solid Fuel Fireplace Installation WARNING This fireplace has been converted for the use with a gas fireplace insert only and cannot be used for burning wood or solid fuels unless all o...

Page 37: ...osing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than psig 3 45 KPa Always check for gas leaks with a soap and water solution after completing the required pressure test TO TEST VALVE PRESSURES The pressure taps are located on the top right of the valve shown in Figure 49 Turn set screw 1 turn counter clockwise...

Page 38: ...For Electrical Installations or The National Electrical Code ANSI NFPA 70 in the US WARNING The electrical grounding instructions must be followed The fan kit is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong outlet DO NOT cut or remove the grounding prong from this plug CAUTION When servicing ...

Page 39: ...nal ledgestone panels installed NOTE The coal set is fragile and should be handled gently Figure 51 Empty firebox with burner installed Figure 52 Coal Bed Installation Step 1 Place the lower coal bed in the firebox by placing the rear of the bed on the back rest and front of the bed on the burner supports Make sure the front of the coal bed is touching the fingers at the front of each burner mount...

Page 40: ...the burner when correctly installed 40 Maintenance Once a year the coal set should be removed and checked for deterioration or large amounts of soot A small amount on the bottom side or in the holes of the coal set is normal Remove and replace the coal set in the same manner described above Cracks on the surface of the lower coal bed are normal and will not effect the performance If a new coal set...

Page 41: ...ned in the previous section 10 Re Install the glass door Secondary Installation Optional Porcelain Panels 50 2939 Installation and Removal Turn off the gas control knob and allow the unit to cool Please ensure that your porcelain panels have not been damaged To Install Panels 1 Remove the glass door by following the instruction in the Maintenance and Service Glass Door Removal section and remove t...

Page 42: ...the cabinet extensions are still installed Safety Screen Assembly 1 Attach the left right top bottom brackets onto the safety screen using a T20 screwdriver and the supplied sixteen 16 8 T20 screws see Figure 59 Do not over tighten the screws doing so could cause them to strip out of the screen frame 2 Lift the face upright in front of the fireplace with the four 4 hooks pointing towards the firep...

Page 43: ... check pilot head for damage Check thermocouple voltage at valve It must be greater than 5 mV If low replace thermocouple Air in gas line pilot dies while knob is depressed Bleed line Check gas line pressure Contact dealer Burners will not remain lit Problem with thermopile circuit Check gas line pressure Check for flame impingement on thermopile If low see Pilot will not remain lit Check thermopi...

Page 44: ... Assembly Standing Pilot EC 015 Pilot Assembly Gasket EC 021 13 S I T Nova Valve Convertible 50 1421 14 Heyco Strain Relief EC 044 15 Domestic Power Cord 115v EC 042 16 Coal Set 50 2937 17 Tube Burner 50 2992 18 Door Glass w Gasket 19 75 x 17 5in 50 2998 19 Door Complete 50 2990 20 Porcelain Liners Set 4 pieces 50 2939 21 Ceramic Brick Liner Set 3 pieces 50 2938 Ceramic Ledgstone Liner Set 3 piece...

Page 45: ...Parts Diagram 20 2 4 3 5 13 16 15 14 11 9 12 8 7 6 17 18 19 1 10 21 23 22 45 ...

Page 46: ...Notes 46 ...

Page 47: ... by you or the dealer including serial number Exclusions An expanded list of exclusions is available at www enviro com help warranty html This warranty does not cover Damage as a result of improper usage or abuse Damage caused from over firing due to incorrect setup or tampering Damage caused by incorrect installation To the Dealer Provide name address and telephone number of purchaser and date of...

Page 48: ...____________________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy NATURAL GAS NAT PROPANE LPG INLET GAS PRESSURE _________in wc MAIN BURNER ORIFICE __________ DMS PILOT ORIFICE _________OR________in diam INSTALLER S SIGNATURE _________________________________________...

Reviews: