Enviro G39GI Owner'S Manual Download Page 27

27

Initial Installation

QUALIFIED INSTALLERS ONLY

Figure 38A: Option 2 

Option 4: Open Chase (built-out installations) - 

This could be considered the most discreet option 

when considering the CSS. The chase must be constructed in a way that stops short of the ceiling, leaving 

it totally vented above. Minimum framing dimensions must be followed when constructing this option and 

not to deviated from them when using combustible materials. Consider 

Option 5: Valance

 to work in 

conjunction with this option.

2"

51mm

Minimum

6"

152mm

Minimum

Wall Mounted Object

 2" MIN 

Figure 38B: Open Chase Iso View

Option 3: Side Discharge (built-out installations) - 

Construct the framing in a way that provides 

a minimum 17

 

inch (432mm) by 2

1/2

 inch (64mm) opening on each side of the chase. The top of the 

opening must be 1 1/2” from the top of the chase (see Figures 37A & 37B)

Note: If you wish to construct the CSS air discharge part way up a tall wall then it is essential to build a 

false ceiling inside the chase at the desired height to direct the rising heat out of the gap. 

Figure 37B: Side Discharge Iso View

0 to 1 

½”

[38mm] Maximum

17” [432mm]

½

” [64mm]

Figure 37A: Option 3 Side Discharge

Summary of Contents for G39GI

Page 1: ...ion and service must be performed by a qualified installer service agency or the gas supplier Version Fran aise www enviro com fr html C 4001609 W A R R A N T Y R E G I S T R A T I O N e n v i r o c o...

Page 2: ...immediately Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service m...

Page 3: ...st be performed by a qualified installer service agency or gas supplier This installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA...

Page 4: ...emoval 17 Burner Removal 17 Fuel Conversion 18 Initial Installation 20 Introduction 20 Unit Install Preparation 20 Placement and Framing 22 Finishing a Fireplace 23 Cool Surface Activation 24 Cool Sur...

Page 5: ...21 88 CSA 2 33 VENTED GAS FIREPLACE HEATERS CSA 2 17 GAS FIRED APPLIANCES FOR HIGH ALTITUDES This ENVIRO G39 Fireplace Has been certified for use with either natural gas or propane see rating label Is...

Page 6: ...important information for your fireplace is on this label as well as the model specific serial number which you will need for warranty information The sheet is located inside the cabinet under the gas...

Page 7: ...has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING IN...

Page 8: ...Radio frequency 315 MHz Integrated Fireplace Controller IFC Supply voltage AC IN 120 V 60 Hz Battery Backup IN 6 Vdc 200mA four 1 5 V AA batteries Spark voltage frequency 10kV 1Hz Comfort modulating f...

Page 9: ...battery back up if there is a power outage Only main burner control can be used while operating with the battery back up auxiliary components such as the convection fan cannot be used Use the reset b...

Page 10: ...ce Press the ON OFF key on the transmitter to turn the fireplace off The IFC will confirm your command with a single beep The pilot light IPI and the main burner will turn off The pilot will remain li...

Page 11: ...vel Operating Instructions Room Thermostat Transmitter Operation The remote transmitter acts as a room thermostat The thermostat can be set to a desired temperature to control the comfort level in a r...

Page 12: ...The life span of the batteries depends on various factors such as battery quality ignition attempts remote usage and power outage duration Figure 12 Key Lock Key lock This function will lock the keys...

Page 13: ...decrease the restriction More details can be found in the venting section of this manual Caution Wear heat resistent gloves when making adjustments to the air shutter Perform adjustments after 15 minu...

Page 14: ...ount of use the glass should require cleaning no more than two or three times a season WARNING Do not clean the glass when it is hot Cleaning The Firebox Carefully remove the glass they are fragile Ge...

Page 15: ...ick wipe with denatured alcohol on a soft cloth BEFORE lighting the fireplace Never clean the face when it is hot Do not use other cleaners as they may leave a residue which can become permanently etc...

Page 16: ...remove the glass door if the fireplace is not completely cold WARNING Never operate the fireplace with the glass door removed Figure 19 Door Cover Removal Door Cover Removal To remove the door cover...

Page 17: ...e the seven 7 remaining T 20 screws securing the glass media tray see Figure 21 Lift up and out Figure 22 Front Burner Removal The burners will need to be removed for maintenance and fuel conversion F...

Page 18: ...all applicable codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire explosion or production of carbon monoxide may resul...

Page 19: ...ng the remote Confirm the inlet and manifold gas pressures are within the acceptable range using a manometer see Initial Installation Gas Line Connection and Testing If this unit has been installed at...

Page 20: ...his manual 4 5 3 2 1 Diagram 1 Additional Parts Unit Install Preparation Review the diagram below to familiarize yourself with the parts included with the unit Please review the following instructions...

Page 21: ...Figure 27 Nailing Flange Flat Figure 28 Nailing Flange Assembled Non combustible board Install the supplied non combustible facing board with eight 8 supplied 8 32 x 75 fasteners using a 1 4 inch soc...

Page 22: ...sions see Figure 23 The fireplace must be placed on a strong and level surface The gas line must be run to the right side of the fireplace there is a 3 8 NPTM fitting to connect the gas line to The el...

Page 23: ...hing edge comes wrapped in foam on top of the unit This finishing edge is 1 deep and will accommodate finishing materials of 1 or more in thickness The 0 5 Finishing edge installed on the unit will ne...

Page 24: ...g WARNING IT IS ESSENTIAL THAT THE CHASE IS VENTED IN A MANNER THAT RELIEVES THE ADDITIONAL HEAT ENTERING THE CHASE ENSURE ONE OF THE AVAILABLE FRAMING OPTIONS HAVE BEEN CONSTRUCTED IN ACCORDANCE WITH...

Page 25: ...ble is mandatory Image shows single layer finishing material using the short finishing edge Standard Extended Install Using the supplied long finishing edge non combustible material may be layered on...

Page 26: ...gap at the top of the facing wall It is essential that these dimensions are respected and not deviated away from them when using combustible materials inside or outside the chase see Figure 36A Optio...

Page 27: ...nction with this option 2 51mm Minimum 6 152mm Minimum Wall Mounted Object 2 MIN Figure 38B Open Chase Iso View Option 3 Side Discharge built out installations Construct the framing in a way that prov...

Page 28: ...alance A valance may be desired to accentuate or hide the CSS outlet Consider framing option 1 or 4 to utilize the valance feature This is an optional decorative feature that covers up the CSS outlet...

Page 29: ...e dimensions required to safely operate the fireplace Plan your entire installation before proceeding These are minimum dimensions associated with natural gas only adjust the ceiling dimensions by add...

Page 30: ...5 1003mm MIN NG 13 1 2 343mm 1 2 4 102mm MIN Recess Installation These are the minimum allowable dimensions required to safely operate the fireplace Plan your entire installation before proceeding Th...

Page 31: ...are the minimum allowable framing dimensions required to safely operate the fireplace in a corner install Plan your entire installation before proceeding Figure 43 Corner Installation 1 25mm 15 382mm...

Page 32: ...7 8 9 10 11 12 13 14 M A N T E L H E I G H T M A N T E L D E P T H Minimum Mantle Clearances 8 MANTEL 4 MANTEL 52 51 50 49 48 47 46 44 45 12 MANTEL Diagram 2 Mantel Graph Floor Protection Figure 44 A...

Page 33: ...eral minutes for the flame to stabilize after ignition under extreme vent configurations It is recommended for vent lengths that pass through unheated spaces garages attics crawl spaces be insulated t...

Page 34: ...ALLATION NOTES Do not bend flex vent over 90 degrees All horizontal runs should have a minimum 1 4 6mm rise per foot for optimal performance Do not allow the inner flex pipe to contact the outer pipe...

Page 35: ...distance of 7 178mm from the finishing edge of the fireplace to an adjacent wall composed of combustible material Mantel It is not necessary to install a mantel but if one is desired the guidelines a...

Page 36: ...ions and highly recommended for CSS installations Recess Installation Always maintain minimum clearances see Figure 49 The total depth of the TV and wall mount as well as the recess depth will determi...

Page 37: ...extended above me ter regulator assembly I 3 ft 91 cm 3 ft 91 cm Radial clearance around service regulator vent outlet Table 4 Vent Termination Clearances Vent Termination Restrictions WARNING Follow...

Page 38: ...combustibles must be maintained around any vertical vent pipe Around a horizontal vent pipe the clearance to combustibles should be 3 76 mm above and 1 25 mm on the sides and bottom When combustible...

Page 39: ...46DVA 18 4DT 18 4D18 18 pipe length 46DVA 24 4DL2 4DT 24 4D2 4D24 24 pipe length 46DVA 36 4DL3 4DT 36 4D3 4D36 36 pipe length 46DVA 48 4DL4 4DT 48 4D4 4D48 48 pipe length 46DVA 60 60 pipe length 46DV...

Page 40: ...be subtracted Restrictor Setting Find the point on the graph where your vent configuration will terminate Remember to consider elbows in the HORIZONTAL plane account for horizontal distance as stated...

Page 41: ...climate and altitude may alter what restrictor is required for your particular application Figure 53 LP Vent Graph 6 1 83m 2 0 61m 4 1 83m 10 3 05m 15 4 57m 15 1 52m 20 6 1m 20 6 1m 25 7 62m 30 9 14m...

Page 42: ...izontal the restrictor level is at its maximum see Figure 54 The proper setting is crucial for an efficient burn and best possible flame appearance It may be necessary to deviate from the recommended...

Page 43: ...the termination screws onto the flat portion of the standoff which provides an air space between the wall and the vent termination The air gap prevents excessive heat from possibly melting the vinyl s...

Page 44: ...Do not pack air spaces with insulation Step 2 Set the fireplace in the desired location Drop a plumb bob down from the ceiling to the fireplace flue exit and mark the location where the vent will pen...

Page 45: ...2 13 Over 18 12 to 20 12 7 5 2 29 Over 20 12 to 21 12 8 2 44 Figure 58 Height of Vertical Termination Reference Table 8 45 elbows x2 Wall strap Plumber s tape connected to wal strap Figure 60 Use of W...

Page 46: ...rmal efficiency rating determined under continuous operating conditions and was determined independently of any installed system Figure 61 Fully Labeled Gas Valve See Dexen User Manual for G39GID valv...

Page 47: ...rols label all wires prior to disconnection Wiring errors can cause improper and dangerous operation Verify proper operation after servicing If any of the original wire supplied with the appliance mus...

Page 48: ...Remove surround panel and glass door see Maintenance and Service section Step 2 Spread the glass media provided out on the media tray Create a thin and uniform layer over the tray bed Caution Avoid ex...

Page 49: ...Flame lifting Leak in vent pipe Check for leaks in vent connections Improper vent configuration Check vent configuration with manual Terminal may be re circulating flue gases Check to see if terminal...

Page 50: ...3791 10 Pro ame 2 Remote Transm er 50 3028 11 Porcelain Liners 50 3498 Table 12 Op ons List G39 Door Complete ceramic 50 3564 12 G39 Slim Face Black Painted 50 3430 G39 Slim Face Grey Powdercoat 50 3...

Page 51: ...51 Parts Diagram 1 2 3 4 5 6 12 7 8 11 10 9...

Page 52: ...52 Notes...

Page 53: ...een mesh Exclusions An expanded list of exclusions is available at www enviro com help warranty html This warranty does not cover Damage as a result of improper usage or abuse Damage caused from over...

Page 54: ...________________________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yy...

Reviews: