Warning:

  Only  persons  licensed  to  work  with  gas  piping  may  make  the  necessary  gas  connections  to  this 

appliance.

Gas Line Connection:

 

•This fireplace is equipped with a certified flexible pipe located on the right side of the unit, terminating in a 3⁄8” 

male NPT fitting. Consult the local authorities for local codes or use the CAN/CGA B149 (1 or 2) installation code in 

Canada. In the US, gas installations follow either local codes or the current edition of the National Fuel Gas Code 

ANSI Z223.1.

•The efficiency of this unit is a product thermal efficiency rating determined under continuous operating conditions 

and was determined independently of any installed system.

The appliance and its’ shut-off valves must be disconnected from the gas supply piping system during any pressure 

testing where the pressure 

exceeds 

1⁄2 psig (3.45kPa) or the valve will be damaged.

The unit must be isolated from the gas 

supply  piping  system  by  closing  its’ 

individual manual shut off valve during 

any pressure testing of the gas supply 

piping system at pressures 

equal to or 

less than 

1⁄2 psig (3.45 kPa).

Always  check  for  gas  leaks  with 

a  soap  and  water  solution  after 

completing  the  required  pressure 

test.

16

Initial Installation

QUALIFIED INSTALLERS ONLY

Main Burner

Natural Gas

(in wc/kPa)

Propane Gas

(in wc/kPa)

Orifice:

#38 DMS

#52 DMS

Manifold Press:

3.8 / 0.95

11.0 / 2.74

Min. Manifold Press: 1.1 / 0.27

2.7 / 0.67

Max. Supply Press:

7.0 / 1.74

13.0 / 3.28

Min. Supply Press:

5.0 / 1.24

12.0 / 2.98

Max. BTU Input:

30,000/ 8.8kWh

28,500/ 8.2kWh

Min. BTU Input:

15,000/ 4.4kWh

14,000/ 4.1kWh

TO TEST VALVE PRESSURES:

The pressure taps are located on the top right of the valve.
• Turn set screw 1 turn counterclockwise to loosen.
• Place 5/16in (8mm) I.D. hose over the pressure taps.
• Check pressures using a manometer.
• When finished, release pressure, remove hose and tighten 

set screw.

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

Summary of Contents for FOCUS EG31-118

Page 1: ...s instructions If you cannot reach your gas supplier call the fire department WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage...

Page 2: ...o the current CAN CGA B149 installation code Canada or National Fuel Gas Code ANSI Z223 1 2 USA To prevent injury do not allow anyone who is unfamiliar with the stove to operate it To prevent injury i...

Page 3: ...ings 10 Maintaining Face and Surround Finishes 10 Initial Installation 11 Venting Fireplace Inserts 11 Preparing Your Focus For Installation 12 Fuel Conversion 13 Electrical Requirements 14 Installing...

Page 4: ...ns between 2000 ft 610 m and 4500 ft 1372 m NATURAL GAS PROPANE GAS INPUT 26 700 Btu h 7 76 kW h INPUT 26 700 Btu h 7 76 kW h ORIFICE SIZE 39 DMS ORIFICE SIZE 53 DMS In the USA these appliance are cer...

Page 5: ...trol panel and is attached to a rectangular metal sheet that is chained to the fireplace Mantle pillar to glass door 9 22 8 cm From floor to 8 wide mantle 38 96 5 cm Minimum non combustible surface in...

Page 6: ...ifying the louvers in any way can create hazardous situations either through poor venting or by overheating It is important that this unit has sufficient air circulation for proper venting and combust...

Page 7: ...nit NOTE Make sure the pilot light completely engulfs the thermocouple and that the burner lights completely Warning The gas valve has a lockout device that prevents the pilot burner from being re lit...

Page 8: ...r door as the unit will start to smoke and can irritate some people After the unit has gone through the first burn turn the unit off including the pilot let the unit get cold then remove the glass doo...

Page 9: ...lm on the glass This is a temporary problem It is therefore recommended that the glass be cleaned initially after the first two weeks of use Depending upon the amount of use cleaning should be require...

Page 10: ...g and light pilot with door open ADJUSTING VENTURI AIR SETTINGS When a plated surround or face is received it should be unpacked unwrapped carefully to avoid getting anything on the surface of the fin...

Page 11: ...d position must be installed The ENVIRO FOCUS may be installed and vented into any solid fuel fireplace that has been installed in accordance with the National Provincial State and local building code...

Page 12: ...quirements section 10 Place the assembled surround panel around the stove align the slots Push back then down to engage the surround panel hooks with the slots in the fireplace Install the decorative...

Page 13: ...the conversion kit STEP 6 Install the new pilot injector supplied with this conversion kit Simply screw the new injector inside the pilot hood and reinstall pilot hood by placing hood on the assembly...

Page 14: ...tray Slide tray to the left and lift out Remove brick panels see Removing and Installing Brick Panels 2 Remove the surround panel by lifting straight up and then pull out to free from the body of the...

Page 15: ...jury or property damage Drafthood Cover Plate Chimney Connector Air Channel Cover Plate x2 1 Remove the chimney connector 300 spill switch two 2 B vent air channels and B vent draft diverter plate 2 I...

Page 16: ...3 45kPa or the valve will be damaged The unit must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping s...

Page 17: ...e Place the rear log on the two back placement pins Install the left front log on the left placement pin with the narrow end of the log resting on the rectangular rest area Install the right front log...

Page 18: ...orts If a long delay is noted wait for the appliance to cool down Open the front door of the appliance Carefully reposition the embers making sure that the burner ports are not plugged or blocked Open...

Page 19: ...ntact dealer Burners will not remain lit Problem with thermopile circuit Check gas line pressure Check for flame impingement in thermopile If low see Pilot will not remain lit Check thermopile for min...

Page 20: ...EG31 072 Log Set With Embers Pre S N 12663 EG31 074 Brick Liner Ceramic Part Part Description EG31 075 Burner Switch Bracket EG31 089 Window Channel Tape EG31 090 1 Piece Glass With Tape EG31 091 Stee...

Page 21: ...402 Cast front only no surround glass valve door or clip on Painted 50 403 Cast front only no surround glass valve door or clip on Antique White 50 404 Cast front only no surround glass valve door or...

Page 22: ...r EC 069 Leveling Bracket Piezo Igniter EC 023 Burner Switch EC 026 Fan Controller EC 039 Painted Door EG31 092 Glass with Tape EG31 090 Rating Label Main Orifice EC 022 Ceramic Brick Liner EG31 074 B...

Page 23: ...L M O U N T I N G B R A C K E T S Q U A R E F L U S H F A S C I A P A I N T E D E G 3 1 1 1 2 G O L D E G 3 1 1 1 2 N I C K E L 5 0 4 8 7 A R C H E D F L U S H F A S C I A P A I N T E D E G 3 1 1 0 6...

Page 24: ...Pearl Grey Cast Iron Bay Face and Surround Wedgwood Blue Cast Iron Bay Face and Surround Westport Green 50 811 Cast Iron Bay Face and Surround Antique Chestnut Cast Iron Sides Cast Iron Bay Window Cas...

Page 25: ...correct conditions Sherwood Industries Ltd offers a two year warranty on all the electrical components and gas components against manufacturing defects Paint is also covered against flaking This offer...

Page 26: ...____________________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy N...

Reviews: