2
OTHER ISSUES:
Not Enough or Too Much Water Flow
•
C
HECK AND ADJUST YOUR WATER PRESSURE AS APPROPRIATE
–
RECOMMENDED OPTIMUM DYNAMIC
FLUSHING PRESSURE IS
350
K
P
A
–
400
K
P
A
,
MAXIMUM PRESSURE IS
500
K
P
A
;
•
FLOW VALVE MAY REQUIRE ADJUSTMENT
–
FLOW CAN BE ADJUSTED WITH REGULATOR VALVE SCREW
ABOVE THE SOLENOID VALVE
–
(
SEE DIAGRAM BELOW
):
Issue
–
Early Activation when Toilet is in Use
•
P
RODUCT IS DESIGNED TO INITIALISE AND ACTIVATE FLUSH CYCLE DEPENDING ON LENGTH OF TIME USER
IS PRESENT IN ACTIVATION ZONE AND HAS A CONFIRMATION TIME OF
5
SECONDS
.
IF USER MOVES OUT
OF THE SENSOR ZONE WHILST USING TOILET
,
THE FLUSH CYCLE WILL ACTIVATE
;
•
FOR USER COMFORT
–
THE MANUAL OVERRIDE BUTTON CAN BE PRESSED TO ALLOW FLUSHING ON
DEMAND
.
Issue
–
Sensing Distance Not Adequate
•
D
ETECTION ZONE IS PRE
-
SET AT
750-800
MM
.
IF THIS IS NOT ADEQUATE
,
THE FLUSH VALVE SETTINGS
MAY REQUIRE SET
-
UP
/
ADJUSTMENT
(
SEE DIAGRAM BELOW
).
I
MPORTANT
-
CARE NEEDED AS
ADJUSTMENT SCREW CAN BREAK IF MISTREATED
.