Envirco MAC 10 MDR16 Installation, Operation And Maintenance Manual Download Page 2

2

I n s t a l l a t i o n   &   O p e r a t i o n   M a n u a l

Innovators in Clean Air Technology   |   www.envirco.com 

MDR16 

MAC 10

® 

Remote Mount Fan Controller

APPLICATION

The MDR16 MAC10® Remote Mount Fan Filter Controller allows manual adjustment of industry standard 0-10VDC automation 

signals to control up to 16 ENVIRCO ECM based FFUs.  The MDR16 provides local or remote adjustment of the FFU output from 

1% to 100% of the motor’s control range.  A signal lamp on the control continuously flashes out the flow index.  Therefore, other 

instruments are not required to read the flow index (%).  The MDR16 can be configured for 0-10VDC, a 2-10VDC or a 4-20mA 

automation signals.  If desired, the MDR16 also can be used for stand-alone manual control by internal jumper configuration.

Signal Lamp Feedback

The MDR16 green front panel lamp continuously indicates the flow index setting for the entire group of FFUs being controlled.  After 

a pause, the lamp flashes out the tens digit, then the units digit of a number between 1 and 99.  Long flashes represent the tens digit 

and short flashes represent the units digit.  For example, a flow index of 23 flashes two longs, then three shorts.  Two extra-long 

flashes indicate a flow index of 0.  An extra-long flash and ten short flashes indicate a flow index of 100.  The lamp flashes the signal 

that was present when the flash sequence started.

Operating Control Modes

The MDR support group control of up to 16 ECM based ENVIRCO FFUs in two different modes, including a pure manual mode and 

a mode where the FFUs’ performance is slaved to an external automation control input.

Pure manual mode is a simple control capability that is enabled when internal 

Jumper #3

 named Manual Override is present.  

With 

Jumper #3

 present, the front panel adjust screw is the only way to control the FFU performance index.  With a small straight 

screwdriver to turn the front panel accessible potentiometer, the user can adjust the FFU performance index up or down.  The Signal 

Lamp will provide real-time feedback of the performance index set-point.

Alternatively, if internal 

Jumper #3

 is not present, automatic mode is selected, and the potentiometer has different functions.  In 

automatic mode (no 

Jumper #3

 present), the potentiometer will control the FFUs’ performance when the automation signal is not 

present.  This feature allows adjustment of the FFUs on a new installation until automation is installed.  Automation will finally start/

stop the motor five times, and LSO will be disabled.  Turning the potentiometer always overrides any automation signal, manually 

controlling the FFU for 15 minutes.  Control reverts to any connected automation signal when the 15 minute adjust timer expires.  

Cycling the power early will instantly reset to automatic mode if required.

There are two additional cases in automatic mode for the adjust function that are set by jumpers.  In automatic, the potentiometer is used 

to set the FFU default performance level when the automation signal is absent or the automation signal is outside its normal control range.

Internal Jumper Options

There are five configurable jumpers inside the MDR16 

control box.  There is a block of four jumpers: 

Jumpers 

#1, #2, #3 

and

 #4

, near the top left corner of the 

printed circuit board.  Configuration of 

Jumpers #1-4

 is 

accomplished by placing the jumper on or removing the 

jumper.   These jumpers should not be configured while 

the MDR is powered on.  A white dot on the printed 

circuit board denotes 

Jumper #1

.

Jumper #1

, if present, configures the MDR16 to provide 

a 10 second spin-up delay for the FFUs, in which the 

motor or motors will operate at a minimum speed for 

the first 10 seconds after power-up.

Jumper #2

,  if  present,  configures  the  MDR16  for 

automated input control.

Jumper #3

, Manual Override, permanently enables 

Lost Signal Override and allows use in manual mode.

Jumper #4

 has two functions.  It sets the control input 

range/mode  and  enables  stopping  the  FFUs  if  the 

Jumpers 1-4

Jumper 5

Go Vspd Vcom Signal Com Neu. 24Vac

1
2
3
4

ON

ON

ON

OFF

ECM 

Control

Automation

Input

Reviews: