Envirco Hospi-Gard IsoClean 400 Installation, Operation And Maintenance Manual Download Page 3

Hospi-Gard

®

 IsoClean

®

 800 & 400

HEPA Filtration System

3

Innovators in Clean Air Technology

I n s t a l l a t i o n ,   O p e r a t i o n ,   &   M a i n t e n a n c e   M a n u a l

  

Introduction

Description

The  Hospi-Gard®  IsoClean®  is  a  portable,  self-contained  high  efficiency  particulate  air  (HEPA)  filtration  system  with  an  

optional ultraviolet lamp that helps to disinfect the filter face. The IsoClean® is designed to easily and economically create 

a negative pressure isolation room that will meet OSHA and CDC TB guidelines. The IsoClean®  can be used as a positive 

pressure clean air recirculating system in clinics, waiting rooms, hospital emergency rooms and other confined areas or as a 

partial or complete exhausting system to create a negative pressure isolation room for possible use with patients known or 

suspected of having TB, SARS, COVID-19, or other infectious diseases. The IsoClean®  is available in two different sizes: the 

IsoClean®  400 and the IsoClean®  800.  As a recirculating unit, the IsoClean®’s powerful motor/blower can deliver up to 370 

CFM (628 m

3

/hr) for the IsoClean®  400 and up to 800 CFM (1360 m

3

/hr) for the IsoClean®  800  to provide a large number 

of room air changes per hour to minimize the spread of airborne diseases to patients and health care workers. As a negative 

pressure unit, the air passing through the HEPA filter is filtered of 99.99% of particles at 0.3 micron and may be exhausted 

directly to the exterior through a window, or through a wall, simply by connecting flexible ducting to the 6 in. (152 mm) collar 

located on the top of the IsoClean®.

Features

•  Low Cost Isolation Room

The IsoClean® is an easy and economical solution for creating a negative pressure isolation room. Simply roll the 

IsoClean® into a standard room, connect flexible ducting to the 6 in. (152 mm) collar on the top of the unit for partial 

exhaust or to the optional 8 in. (204 mm) flanged collar for total exhaust, and vent the purified air to the exterior through 

a window or wall.

•  Flexible Applications

The versatile IsoClean® can be used as a clean air recirculating unit, a negative pressure unit, or as a split system 

to  create  both  negative  pressure  and  clean  air  recirculation  by  simultaneously  exhausting  some  of  the  air  out  while 

recirculating the remainder back into the room.

•  Small and Portable

The IsoClean® can be rolled from one room to another and easily fits into areas with limited floor space.

•  Simple Maintenance

Both HEPA filter and prefilter are easily accessible for replacement by authorized personnel.

• 

Adjustable Airflow

The IsoClean® provides effective air filtration for a wide variety of room sizes.  The IsoClean®  400 utilizes a solid state 

speed control with airflows ranging from 70 to 370 CFM (118 to 628 m

3

/hr).  The IsoClean®  800 utilizes a three position 

switch with airflows ranging from 560 to 800 CFM (951 to 1360 m3/hr).

•  Low-High Clean Air Circulation Pattern

Room air, along with airborne contaminants, is drawn into the intake grill at the bottom while the purified air is discharged 

at  a  high  velocity  from  the  exhaust  grill  located  at  the  top  of  the  IsoClean®  to  generate  a  sweeping,  low-to-high  air 

circulation pattern with adequate “reach” to optimize the clean breathing zone for patient and staff.

•  Quiet Operation

52 dBA on low, 56 dBA on medium, and 60 dBA on high speed measured 30 in. (762mm) from face of the unit.

Applications

Hospital

•  Negative Pressure Rooms

•  Emergency Rooms

•  Waiting Rooms

•  Sputum Induction

•  Aerosol Pentamidine Treatment

•  Intensive Care Units

• 

Bronchoscopy Rooms

•  Renal Dialysis Rooms

Summary of Contents for Hospi-Gard IsoClean 400

Page 1: ...Hospi Gard IsoClean 800 IsoClean 400 HEPA Filtration Systems INSTALLATION OPERATION AND MAINTENANCE MANUAL ENVIRCO Technical Support 800 884 0002...

Page 2: ...l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l Table of Contents Introduction 3 Installation 4 Operation 5 Maintenance Service 7 Troubleshooting 11 Wiring Diagram 12 Specifications...

Page 3: ...a negative pressure isolation room Simply roll the IsoClean into a standard room connect flexible ducting to the 6 in 152 mm collar on the top of the unit for partial exhaust or to the optional 8 in 2...

Page 4: ...ery unit is tested prior to shipment to verify airflow and that the unit is leak free 2 Place the unit in its final operating position 3 Lock the wheel locks on the casters to keep the unit from accid...

Page 5: ...EPA filter The airflow indicator should not be used as the only guide for when a filter change is necessary The unit should be checked at each use to ensure recommended room air changes per hour are b...

Page 6: ...ed to the top of the lsoClean for the unit to run in the 100 exhaust mode An optional 8 inch 203mm Exhaust Collar with Flange is available to convert the lsoClean unit to the 100 exhaust mode 1 Remove...

Page 7: ...FOR A NEGATIVE PRESSURE ISOLATION ROOM AND MONITORED TO ENSURE ITS CONTINUING PERFORMANCE Difficulty Achieving Negative Pressure The equipment may not be able to achieve or maintain negative pressure...

Page 8: ...AUTION DISCONNECTTHEUNITFROMTHEELECTRICALPOWERSOURCEBEFOREATTEMPTINGSERVICE DONOT WORKINSIDETHEISOCLEANUVWITHTHEUVLIGHTON PROPERREPLACEMENTOFUVCONTAINMENTBAFFLES AFTERMAINTENANCEISMANDATORYTOMAINTAINS...

Page 9: ...leakage and for filter loading The expected HEPA filter life should range from eighteen 18 months to two 2 years depending on the environment and prefilter maintenance schedule The filter indicator l...

Page 10: ...the switch and squeeze the snap in legs to remove switch from side of the unit 2 Install new switch by snapping it into the cutout and then connecting it to the white connector Speed Control Switch 1...

Page 11: ...een completed remove the HEPA filter The filter can now be disposed of as general waste Phenolic Decontamination ln facilities where the above decontamination procedures are prohibited or not feasible...

Page 12: ...igher airflow setting 4 Check power supply for proper voltage amperage and distribution frequency 5 Check for down stream obstructions or erratic isolation room ventilation balance 6 Replace HEPA filt...

Page 13: ...ard IsoClean 800 400 HEPA Filtration System 13 Innovators in Clean Air Technology I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l Wiring Diagrams Cont IsoClean 400 Wiring D...

Page 14: ...Filter Media 99 99 at 0 3 micron minimum efficiency Prefilter MERV8 multi pleat anti microbial pleated prefilter with frame Motor 1 3 HP 0 25 kW direct drive three speed continuous duty Exhaust Port 6...

Page 15: ...IsoClean 1 11055 8 inch A C Collar with Flange for 100 1 267745 001 Intake Grille Painted 1 37453 Exhaust Grille 1 61528 Minihelic Gauge 1 63360 Keylock 1 IsoClean 800 UV Part No Description Quantity...

Page 16: ...ge for 100 1 267745 001 Intake Grille Painted 1 37453 Exhaust Grille 1 61528 Minihelic Gauge 1 63360 Keylock 1 IsoClean 400 UV Part No Description Quantity 10950 005 IsoClean 400 120V UV 1 10960 005 I...

Page 17: ...d 10 x 10 x 8 800 ft3 12 x 12 x 8 1152 ft3 12 x 15 x 8 1440 ft3 12 x 15 x 9 1620 ft3 15 x 15 x 8 1800 ft3 15 x 20 x 8 2400 ft3 20 x 20 x 8 3200 ft3 800 Low 560 CFM 42 ACH 29 ACH 23 ACH 20 ACH 18 ACH 1...

Page 18: ...the Goods during the Warranty Period v Buyer providing Seller with a reasonable opportunity to examine the Goods and the aforementioned records and vi the absence of any unauthorized modification or r...

Page 19: ...Hospi Gard IsoClean 800 400 HEPA Filtration System 19 Innovators in Clean Air Technology I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l This page intentionally left blank...

Page 20: ...O M Industrial Cleanroom Products MAC 10 Original MAC 10 IQ MAC 10 LEAC2 MAC 10 LEDC MAC 10 RFAC Ducted Ceiling Module DCM RSR AC or DC Control Systems Hospital Healthcare Hospital Healthcare IsoClean...

Reviews: