32
7.2.5 Sensor
Selection:
SolidFlow 2.0 / PicoFlow / The Evaluation unit checks whether the
ProSens / SpeedFlow 2.0 / connected sensor corresponds to the set
Paddy / MaxxFlow HTC /
sensor.
DensFlow / SlideControl /
The measurement values are calculated and
M-Sens 2 / M-Sens 3 /
potential errors are displayed based on the
M-Sens WR2
set sensor.
Incorrect sensor selection leads to
communication denial.
7.3 Display
7.3.1
Sensor info
Selection:
ON /OFF
ON:
The key for querying sensor information
is shown on the display.
OFF:
The key for querying sensor
information is hidden on the display.
7.3.2 Process indicators
Selection:
ON /OFF
ON:
Process indicators are shown on the
display and indicated on the DIN Rail by
flashing twice.
OFF:
Process indicators are not output.
7.3.3 Backlight
Input:
0 min … 99 min
Display lighting in minutes
0 = Permanent lighting
99 = Time selection for lighting
7.3.4 Contrast
Input:
0 … 100 %
In the event of an inadequate display, the
contrast can be changed via the PC
software, if necessary.
7.4 Address
Input:
1 … 255
Modbus address of Evaluation unit, if this is
operated on a PLC or PC as a Modbus slave
(RS485 connection).
7.5
Baud rate
Selection:
Communication speed of the Evaluation unit if
4800 / 9600 /
operated on a PLC or PC as a Modbus slave.
19200 / 38400
7.6 Password
Input:
0 … 9999
0 = No password protection
XXXX = Four digit password that is queried
when calling up the menu on the display.
Automatic locking for five minutes after the
last display input.