© Entrematic
Group AB 2017
October 2017
6021140A — Industrial HVLS Fans
35
Before doing any electrical work, make certain the power
is disconnected and properly locked or tagged off. Failure
to do so may result in death or serious injury. All electrical
troubleshooting and repair must be done by a qualified
technician and meet all applicable codes. Do not route
control wiring for any other device through this control
box. Ensure that the voltage and phase of the incoming
power agrees with the label located on top of the VFD
box and fan. Be certain power is off when wiring to the
control box. Failure to do so could result in electrical
shock, death or serious injury.
ELECTRICAL SCHEMATICS,
continued
°
6021100
6021103
VOLTAGE
230V/1PH/50 60HZ 230V/1PH/50 60HZ
FLA
13.1A
14.3A
FUSE
KTKR15
KTKR20
MOTOR
1.5HP, FLA @
265V/60HZ
2HP, 5.1FLA @
265V/60HZ
LINE REACTOR
N/A
N/A
VFD
200 230/1PH
2HP/1.5/2.0A
200 230/1PH
2HP/1.5KW/7.0A
O/L
2.6
6.8
SIZING CHART
Fig. 43
1PH WIRING DETAILS