IP1938EN - 2017-12-07
6.2 Second level menu - BC (Basic Configurations)
-
use the keys
Ÿ
and
ź
to select the required function
-
press the ENTER key to confirm
Display
Application
Description
AC - Enabling of automatic closing.
OF - Disabled
ON - Enabled
C5 - Step-by-step/opening command operation.
1-5 - Step-by-step
1-3 - Opening
RM - Radio receiver operation.
1-5 - Step-by-step
1-3 - Opening
OD - Opening direction selection.
LF - Opens towards left.
RT - Opens towards right.
The opening direction is intended by viewing the automation from the side being
examined.
SS - Selection of automation status at power on.
OP - Open
CL - Closed
Indicates how the control panel considers automation when powered up or after a
POWER RESET command.
SO - Enabling reversal safety switch function.
OF - Disabled
ON - Enabled
When enabled (ON) with the automation blocked, if the contact 1-8 is open, any op-
eration is impossible.
When disabled (OF) with the automation blocked, if the contact 1-8 is open, it is pos-
sible to activate the opening operation.
NI - Enabling of NIO electronic antifreeze system.
OF - Disabled
ON - Enabled
When enabled (ON) it maintains the efficiency of the motors even in low tempera-
tures.
NOTE: for correct operation, the control panel must be exposed to the same ambient
temperature as the motors.
Do not use
PG - Enabling opening control reservation with interlocked barriers.
OF - Disabled
ON - Enabled
When enabled (ON), it requests the barrier 1 opening command if barrier 2 is en-
gaged in completing the operation.
BC
WARNING: it is necessary to set DIP5=OFF on the control panel in order to
make enabling/disabling of the NIO electronic anti-freeze system available
from the display module.
i
NOTE: it is possible that, owing to the type of automation and control panel, certain menus are not available.