6

IP2095 - 2015-05-12

nected;

-

repeat the same procedure for each moving unit in the system.

NOTE: it can take up to 20 s after power-on until the safety outputs are

switched on.

In case of using the GOPAVR-GOPAVRS unit just with the safety edges

connected to it (with no GOPAVT units memorized) perform the RESET

procedure decribed below and then simultaneously press buttons A and 

B for 3 s. W LEDs will turn off and the system will be ready for operation 

with local edges.

If any device is replaced, all the installed devices must be RESET and the 

configuration procedure repeated.

To RESET each device, do the following:

-

press button B for 3 s. Both of the SC LED indicators will flash;

-  press button B again for 3 s. Both of the SC LED indicators will flash.

Once the LED indicators have finished flashing, the unit has been reset.

WARNING: you must first RESET the fixed GOPAVR-GOPAVRS unit 

and then RESET all the mobile GOPAVT units.

7. Setting frequency

If you need to use an operating frequency which is different from the 

factory set frequency, you must open jumper JR2 before configuring all 

the devices (see chapter 6).

If the frequency has to be changed on a system already operating with 

the factory frequency, first 

all

 its moving units and the fixed unit must be 

reset (see chapter 6).

8. Checking operation and radio connection

To check the operating, give an opening or closing command and press 

each of the SOF sensitive edges. Check whether the movement of the 

gate/door is arrested or reversed (for mobile edges, check the switching 

on of SC LED on the moving unit in question and the W LED or acoustic 

signal on the fixed unit; for fixed edges, check that the relative SC LED 

on the fixed unit turns on). Once these operations have been successfully 

completed, make sure that the wing’s operational forces comply with that 

which is prescribed by the EN12453-EN12445 directives.

In order to operate efficiency, the radio connection between the various 

devices in an installation must be of a good quality.

You can check the quality of the radio connection between a GOPAVT 

moving unit and the corresponding fixed unit by doing the following:

-

simultaneously press button A and button B, until 1 beep is emitted

(for about 3 s), on the GOPAVT moving unit to be checked;

-

the GOPAVT moving unit performs 1 to 5 transmissions to the GOPAV-

GOPAVRS fixed unit every 15 s. If a SOF safety edge is pressed, these 

transmissions are signalled by a proportional number of acoustic

signals:

1x BEEP: optimum radio connection

5x BEEPs: problematic radio connection (the position or form of the 

antenna must be adjusted)

-

if the quality of the radio connection is poor, the position of the devices 

or the form of the antennas must be adjusted to find the configuration 

that gives the best radio connection;

-

repeat the procedure for all the GOPAVT units in the installation;

-

the same function is useful for constantly displaying alarm conditions 

on the GOPAVT unit in question;

-

the check function is automatically deactivated after 3 minutes.

If you cannot get a good quality radio connection using the above pro-

cedure, check the disturbance level in the communication channel by

doing the following:

-

simultaneously press button A and button B for about 3 s on the

GOPAVR/GOPAVRS fixed unit;

-

the LED indicators on the fixed unit come on. The number of lit LEDs 

is proportional to the quality of the communication channel:

0 lit LEDs:  very disturbed channel

6 lit LEDs:  excellent channel

WARNING: if the channel is very disturbed, it is advisable to try 

changing the operating frequency, see chapter 7.

9. Signals

Signal

Description

State of relay contacts

SC 

IN1 

Safety edge triggered or short-
circuited.

OUT1 and/or OUT2
OPEN

IN2 

OC 

IN1 

Alarm (interruption of the cir-
cuit) of the safety edge.

OUT1 and/or OUT2
OPEN

IN2 

IN1 

Safety edge triggered, short-
circuited or alarm emitted 
(interruption of circuit) near a 
GOPAVT unit.

OUT1 and/or OUT2
OPEN

IN2 

IN1 

Missing GOPAVT unit, battery 
removed from GOPAVT unit or 
on-going remote unit presence 
verification.

OUT1 and OUT2
OPEN

IN2 

IN1 

No GOPAVT units memorized.

IN2 

Buzzer 

Safety edge triggered (1 beep 
per second until pressed safety 
edge is released).

OUT1 and/or OUT2
OPEN

Malfunctioning alarm for 1 or 
more fixed or mobile safety 
edges (1 beep per second until 
fault is cleared).

OUT1 and/or OUT2
OPEN

Battery removed on 1 or more 
GOPAVT mobile unit alarms (1 
beep per second).

OUT1 and OUT2
OPEN

GOPAVT mobile unit malfunc-
tioning alarm (1 beep every 3 
seconds).

OUT1 and OUT2
OPEN

Low transmitter battery level 
alarm (1 beep every 20 se-
conds).

OUT1 and OUT2
CLOSED

Signal

Description

SC 

IN1 

Safety edge intervention or short-circuit.

IN2 

OC 

IN1 

Alarm (interruption of the circuit) of the safety edge.

IN2 

Buzzer  

Low battery.
Transmission to the GOPAVR-GOPAVRS fixed unit (with transmis-
sion check function activated, 1 to 5 beeps).

NOTE: signalling of malfunctioning on GOPAVT moving units takes place 

briefly at 15 s intervals. To display them constantly, use the check function 

described in chapter 8.

10. Maintenance program (every 6 months)

For the correct working:

-

keep the inside of the SOF safety edge clean and dry;

-

check operation as indicated in chapter 8;

-

replace the GOPAVT transmitter battery every 24 months or whenever

the flat battery alarm signal sets on.