Operation - overvoltage control
When you turn the LED flash to allow monitoring of their operation.
Press the button during the startup phase of the generator until the green LED lights up permanently (which indicates that the voltage is within
the calibration levels). At this point, release the button; If the voltage is within limits, the state of the outputs is this: NO output 5-6 | 4-5 NC
output.
If the value of the voltage goes beyond the limits of the calibration set has:
- MIN yellow LED lights when the voltage is lower than the set limit; MAX LED lights red when the voltage is greater than the calibration set;
- Elapsed trip time T1, the output contact of the relay goes into alarm (5-6 NC output, output 4-5 NO).
Operation - Voltage Display
The three LEDs on the front panel indicate the value of the output voltage.
LED V MIN
(yellow)
LED V NOM
(green)
LED V MAX
(red)
Voltage value
V NOM = 230V
V NOM = 400V
On
below to 210V
below to 360V
On
On
from 210V to 220V
from 360V to 380V
On
from 220V to 235V
from 380V to 400V
On
On
from 235V to 245V
from 400V to 440V
On
exceeding a 245V
exceeding to 440V
Time adjustment of intervention
You can adjust the operating time of the device.
To adjust the tempo of intervention:
- Stop the generator and make sure that the EN0546 is no longer supplied;
- Using a flat screwdriver, remove the front keypad of the device by leveraging on
the bottom edge;
- Act using the screwdriver on the trimmer positioned between the red LED and
green LED; the adjustment of the intervention time ranges from 0.1 to 10 seconds;
turning the trimmer clockwise, the response time is increased; turning it
counterclockwise, the trip time is decreased.
- Replace the keyboard and press gently to close the tool;
- Restart the generator.
rev 1.1
2
EN0546
Position
of the trimmer
response
time
(behind the
front panel)