Entes EVM-05C Quick Start Manual Download Page 7

7

VOLTAGE MONITORING

EVM-05C

At position ON:If any voltage of phase-neutral or phase-phase
or frequency exceed  1.5 times of set value,the output relay 1
is activated without any delay time, out 1 LED turns off and
related phase of Hi LEDs turn off.
If any voltage of phase-neutral or phase-phase or frequency
fall  1.5 times of set value,the output relay 2 is activated without
any delay time, out 2 LED turns off and related phase of Hi
LEDs turn off.
At position OFF: Instant Tripping function is canceled.

Press SET button for 3 secs.

Find SP menu
by scrolling
UP/DOWN
buttons.

Press SET
button.(SP Hi  is
displayed)

Press SET button.(INS trP of
is displayed)

In order to activate instant
tripping function, select ON
by scrolling up/down buttons.

Press SET button(INS trP is
displayed)

Press ESC button one by one until SAU SEt yES is
displayed.

Press SET button while SAU SEt yES is displayed.

SET

SET

SET

SET

ESC

SET

Find INS TRP menu by scrolling UP/DOWN buttons.

ACTIVATING INSTANT TRIPPING FUNCTION

The menu that the voltage transformer ratio is adjusted.
You can adjust the value between 1...2000. If the voltage
transformer is not used, the ratio is selected 1.

For example; voltage transformer ratio :34500/100

:345 is setted.

VOLTAGE TRANSFORMER RATIO:

Press SET button for 3 secs.

SET

SET

Press SET button

Enter 1st digit value
by scrolling
UP/DOWN buttons

(If you set 1st digit value
incorrect, you can set
again by pressing ESC
button.)

Enter 2nd digit value by scrolling UP/DOWN buttons

(If you set 2nd digit value incorrect, you can set again
by pressing ESC button.)

Press SET button

SET

ESC

SET

Press SET button after you enter the value

Press ESC button one by one until SAU SEt yES is
displayed.

Press SET button while SAU SEt yES is displayed.

SET

Enter 3rd digit value by scrolling
UP/DOWN buttons 

(If you set 3rd

digit value incorrect, you can set again by
pressing ESC button.)

Press SET button

SET

Enter 4th digit value by scrolling UP/DOWN buttons 

(If

you set 4th digit value incorrect, you can set again by
pressing ESC button.)

Press SET button

SET

CONNECTION TYPE OF SYSTEM

Con: 

The menu that is selected the connection type of

system. Two connection type is defined in the device.

If the system is 3 phases with neutral, we should

select the Star connection.

If the system is 3 phases without neutral, we should

select the Delta connection.

Press SET button for 3 secs.

Find Clr H-L  menu
by scrolling
UP/DOWN buttons.

Press SET button (Clr No is
displayed)

Press SET button (Clr H-L is
displayed)

Press  ESC button

Select yES by scrolling UP/DOWN
buttons

SET

SET

SET

ESC

The menu that is defined the user password and activated
the user password.
It is prevented to change the settings of the device by
unauthorized people by activating password.If you want
to use this function of device,you should activate the user
password.
Pýn menu contains 2 sub-menus.

The menu that is changed the user password
According to the factory settings, the password
is set to 1234.

The menu that is cleared the min. and max values
measured.

Press SET button for 3 secs.

Find Con menu by
scrolling UP/DOWN
buttons.
Press SET button
(Con StAr  is
displayed)

Press SET button (Con is
displayed)

Press ESC button one by one
until SAU SEt yES is displayed.

Press SET button while SAU SEt yES is displayed.

SET

SET

SET

ESC

SET

Select connection type by
scrolling UP/DOWN  buttons

SETTING THE CONNECTION TYPE OF SYSTEM

CLEARING MINIMUM AND MAXIMUM VOLTAGES

INSTANT TRIPPING FUNCTION

USER PASSWORD MENU

kV

Hz

V

L-L

V

L-N

SET

ESC

L1

L2

L3

kV

kV

OUTPUT 1

OUTPUT 2

VOLTAGE

MONITORING

True RMS

EVM-05C

H

H

H

L

L

L

H

L

kV

Hz

V

L-L

V

L-N

SET

ESC

L1

L2

L3

kV

kV

OUTPUT 1

OUTPUT 2

VOLTAGE

MONITORING

True RMS

EVM-05C

H

H

H

L

L

L

H

L

L1

SET

ESC

L2

L3

kV

kV

kV

Hz

OUTPUT 1

OUTPUT 2

V

L-L

V

L-N

H
L

H
L

H
L

H
L

VOLTAGE
MONITORING

EVM-05C

True RMS

L1

SET

ESC

L2

L3

kV

kV

kV

Hz

OUTPUT 1

OUTPUT 2

V

L-L

V

L-N

H
L

H
L

H
L

H
L

VOLTAGE
MONITORING

EVM-05C

True RMS

kV

Hz

V

L-L

V

L-N

SET

ESC

L1

L2

L3

kV

kV

OUTPUT 1

OUTPUT 2

VOLTAGE

MONITORING

True RMS

EVM-05C

H

H

H

L

L

L

H

L

kV

Hz

V

L-L

V

L-N

SET

ESC

L1

L2

L3

kV

kV

OUTPUT 1

OUTPUT 2

VOLTAGE

MONITORING

True RMS

EVM-05C

H

H

H

L

L

L

H

L

L1

SET

ESC

L2

L3

kV

kV

kV

Hz

OUTPUT 1

OUTPUT 2

V

L-L

V

L-N

H
L

H
L

H
L

H
L

VOLTAGE
MONITORING

EVM-05C

True RMS

L1

SET

ESC

L2

L3

kV

kV

kV

Hz

OUTPUT 1

OUTPUT 2

V

L-L

V

L-N

H
L

H
L

H
L

H
L

VOLTAGE
MONITORING

EVM-05C

True RMS

Summary of Contents for EVM-05C

Page 1: ...ury Disconnect all power before working on equipment When the device connected to the network do not remove the front panel Do not try to clean the device with solvent or the like Only clean the devic...

Page 2: ...connection Lo Hys 10 V Lo L 1 180 V Lo L 2 175 V Lo L 3 170 V is adjusted in star connection If the connection type is changed to the delta connection the device calculates these values as phase phas...

Page 3: ...ase in delta connection The voltage value can be adjusted 0 300 V in star connection and 0 500 V in delta connection If the value is set to zero 0 the low voltage warning is cancelled The max voltage...

Page 4: ...one until SAU SEt yES is displayed Press SET button while SAU SEt yES is displayed SET Enter 3rd digit value by scrolling UP DOWN buttons If you set 3rd digit value incorrect you can set again by pre...

Page 5: ...the end of the adjusted delay time Frq Ofd The hysteresis value can be adjusted 0 20 Hz The frequency of the system is measured from L 1 If the frequency of system is under the high set value Frq Hi o...

Page 6: ...ttons If you set 3rd digit value incorrect you can set again by pressing ESC button Press SET button SET Enter decimal digit value by scrolling UP DOWN buttons If you set decimal digit value incorrect...

Page 7: ...TEM Con The menu that is selected the connection type of system Two connection type is defined in the device If the system is 3 phases with neutral we should select the Star connection If the system i...

Page 8: ...ET button for 3 secs Find Pin menu by scrolling UP DOWN buttons Press SET button Pin Act is displayed SET SET SET SET Press SET button Enter 1st digit value by scrolling UP DOWN buttons If you set 1st...

Reviews: