9. INSTALLER MENU
Enter the installer menu: Select
with the joystick.
Press the return button
for 10 seconds.
Select the parameter you want to adjust with the joystick
Confirm selection by pressing the joystick
The current value is blinking. Now you can adjust the value with the joystick
Save by pressing the joystick
Restore the factory setting for the selected parameter by pressing the return button
Parameter
Installer menu
No
Name Parameter description
Factory setting
Alternative
setting
10
LAnG
Language
EnGLISH
FrAnCAIS
11
⁰C
Temperature unit
⁰C
⁰F
12
Air
Temperature readout measured by intern sensor.
Note that the readouts represent raw data and must
not be used as an indication of actual room tempera-
ture.
13
Flor
Temperature readout measured by extern sensor.
14
FL.Li
Limitation scheme for the external sensor.
No limitation
Lo
: Minimum limit
Hi
: Maximum limit
Lo Hi
: Combined
minimum and
maximum limit
15
FL.Li
Lo
Minimum limitation temperature.
This parameter is only shown when one of the limita-
tion schemes is selected.
18 ⁰C
From
5 ⁰C
to
[
FL.Li Hi – 0.5
]
16
FL.LI
Hi
Maximum limitation temperature.
This parameter is only shown when one of the
limitation schemes is selected.
28 ⁰C
From [
FL.Li Lo +
0.5
] to
37 ⁰C
17
rEGU
Control algorithm
Bp
PI control
HYSt
On / Off control
18
bp
Proportional band for PI control [⁰C]
2.0
Adjustable
0.1 ⁰C … 12.7 ⁰C
19
tCy
Cycle time for PI control [minutes]
10
Adjustable
1 … 120
20
tOn
Minimum time for load switch on during the control
cycle [minutes].
2
Adjustable
0 … tCy / 120
21
tOFF
Minimum time for load switch off during the control
cycle [minutes]
2
Adjustable
0 … tCy / 120
28
rESET
Factory settings
Press the joystick
until the
display is shut off
29
End
Exit the installer menu.