8. USER MENU
Enter the user menu: Select
with the joystick.
Maintain the joystick on the left direction
for 5 seconds.
Select the parameter you want to adjust with the joystick
Confirm selection by pressing the joystick
The current value is blinking. Now you can adjust the value with the joystick
Save by pressing the joystick
Restore the factory setting for the selected parameter by pressing the return button
Parameter
User menu
No
Name Parameter description
Factory setting
Alternative
setting
01
SEnS
Sensor selection
Sens Air Only
Internal sensor
Sens Flor Only
*
External sensor
02
CAL
Air
Calibrate internal sensor.**
Procedure: Before calibration, operate the thermo-
stat with same temperature setting for at least one
day. Put a thermometer at the same height as the
thermostat (approx. 1.5 m above the floor) and give it
enough time to stabilize. Press the joystick and enter
the value that is read out from the thermometer. Save
by pressing the joystick.
Note! The heating element managed by the thermo-
stat must be in operation during the calibration.
no
Not calibrated
done
Calibrated
03
CAL
SoL
Calibrate external sensor.
Procedure: Before calibration, operate the thermo-
stat with same temperature setting for at least one
day. If the external sensor is used as floor sensor, put
the thermometer on the floor and give it enough time
to stabilize. Press the joystick and enter the value that
is read out from the thermometer. Save by pressing
the joystick.
Note! The heating element managed by the thermo-
stat must be in operation during the calibration.
no
Not calibrated
done
Calibrated
04
1rst
Heat
Drying function for concrete floors.
When activated, this function starts a drying program
that lasts for 21 days. During the first 24 hours the
heating is on 2 hours totally. For each following day,
another 1 hour of heating is added. The temperature
is limited to 20 ⁰C during the program. The function is
not stopped due to possible power breaks.
no
Not activated
21
Activated
05
LoAd
Connected load [W] to the thermostat.
Connect max. 2300W load, when the internal sensor
is selected.
If you connect a load 2300W - 3600W, use an exter-
nal power relay (contactor). Adjust the parameter to
“
0000
”.
1500
Adjustable
0
to
2300
in steps
of
50
09
End
Exit the user menu.
The program version is displayed.
Press the joystick
* Alternative settings depend on parameter 14 in the installers menu.
** The parameter is not shown if another sensor is selected.