enphase Q-BA-3-1P-60 Quick Install Manual Download Page 3

TROUBLESHOOTING

DANGER!

 Risk of electric shock. Some tasks are done with live 

circuits in an outdoor rooftop environment. Always wear proper 

personal protective equipment (PPE) for electrical and rooftop tasks.

One or More Branches Not Generating

Without removing the cover:
A)  Verify that voltage is within range at the PV breaker at the main panel 

when measuring from L1 to L2.

B)  Power off the PV circuit (aggregated ac circuit) and use a voltmeter to 

verify that the circuit is turned off. Use Lockout/Tagout procedures.

C)  On the roof, disconnect the Q Cable connectors from all (up to three) of 

the branch circuit bulkhead connectors on the Q Aggregator and seal 

connectors.

D)  Turn the PV circuit on at the main panel and again verify that 240V is 

present from L1 to L2.

E)  Using PPE, and taking care not to short the L1, L2 pins within each 

connector, use a voltage meter to determine if each connector on the Q 

Aggregator has 240V present from L1 to L2.

F)  If all connectors show proper voltage then the Q Aggregator is working 

correctly. 

G)  If some connectors exhibit proper voltage, but, after repeated testing, 

other connectors do not exhibit proper voltage, continue to the Q 

Aggregator board removal and replacement procedures.

H)  If all connectors do not show voltage and the main PV circuit from the 

main panel is active per step D, continue with the following troubleshoot-

ing procedure.

I)  Reconnect, secure, and check all connections.

All Circuits Appear Non-Functioning

A)  Verify that the PV breaker at the main panel reads 240V when measur-

ing from L1 to L2.

B)  Power off the PV circuit (aggregated ac circuit) and verify with voltmeter 

that the circuit is turned off. Use Lockout/Tagout procedures.

C)  At the Aggregator, open the Q Aggregator using a standard screwdriver 

blade on the four captured screws on the cover. 

D)  Use a voltmeter or electrical tester to verify that the circuit coming to the 

main lug of the Q Aggregator is not live.

E)  Inspect the Q Aggregator for evidence of loose connections at the main 

lug or look for evidence of multiple blown fuses. Keep in mind that fuse 

ends may be coated. It is best to test from the main lugs to the spade 

terminals.

F)  Remove tools and/or screws from the Q Aggregator, reactivate the PV 

circuit (aggregated ac circuit), and test for voltage on the conductors 

coming from main panel.

G)  If no voltage is coming from the main panel check your electrical wiring 

from the main panel.

H)  If there is voltage at Q Aggregator main lug, and if the wires appear to 

be stripped appropriately and terminated with orange handles down, 

continue to the Q Aggregator board removal and replacement proce-

dures.

Summary of Contents for Q-BA-3-1P-60

Page 1: ...en the Q Aggregator and main PV breaker Enphase disconnect tool C Protect your system with lightning and or surge suppression devices at the sub or main panel D Protect the Q Aggregator with a maximum 60 amp over current protection device OCPD E Size the AC wire gauge to account for voltage rise Select the correct wire size based on OCPD size and on the distance from the beginning of the Enphase Q...

Page 2: ...an flip the bracket for roof or block mounting When transitioning between rows secure the cable to the nearest rail to prevent cable damage A Install Q Aggregator on rail in a location that does not conflict with the module frame and module mounting hardware Allow a minimum of 1 9 cm 0 75 between the roof and the Q Aggregator Also allow 1 3 cm 0 50 between the back of the PV module and the top of ...

Page 3: ...edures H If all connectors do not show voltage and the main PV circuit from the main panel is active per step D continue with the following troubleshoot ing procedure I Reconnect secure and check all connections All Circuits Appear Non Functioning A Verify that the PV breaker at the main panel reads 240V when measur ing from L1 to L2 B Power off the PV circuit aggregated ac circuit and verify with...

Page 4: ... enter from an uphill direction and that moisture does not enter the Aggregator Water ingress will void the warranty for the Aggregator WARNING Do not expose any connectors to rain or condensation before the connectors are mated WARNING Install the Q Aggregator under the PV module to avoid direct exposure to rain UV and other harmful weather events mount the Q Aggregator off of the roof surface fo...

Reviews: