enphase Q-BA-3-1P-60 Quick Install Manual Download Page 2

      Replace the Cover

A )  Make sure that the drain holes on the bottom of the Q Aggregator are 

free from debris. 

B )  Check the seal on all sides for trapped debris. Remove any debris, if 

needed.

C )  Replace the cover on the Q Aggregator and torque screws to 1.1 N m 

(9.7 in-lbs).

D )  Check that the Q Aggregator is properly sealed.
E )  Cap any unused branch circuit connections.
The Q Aggregator is now ready for branch circuit connections. 

DANGER!

 Never connect a single branch circuit to multiple branch 

circuit connections on the Q Aggregator.

6

4

INSTALLATION

      Plan the Location

A )  Select a location that will be under the modules when the array is 

complete, but that will also be accessible for making connections later.

B )  Ensure that you can bring conduit into the Q Aggregator from the upper 

left or right side where indicated by pilot hole indents.

BEST PRACTICE

: Lay out your cable runs before determining the  

Q Aggregator location.

WARNING:

 Ensure the conduit does not enter from an uphill 

direction and that moisture does not enter the Aggregator. 

Water 

ingress will void the warranty for the Aggregator.

2

      Drill a Hole for Conduit

A )  Prep conduit with an offset to approximate area and position the Q 

Aggregator to double check your drill location.

B )  Remove the Q Aggregator cover and drill a hole for up conduit: Typical 

openings are 2.2 cm, 2.8 cm, or 3.5 cm (0.885”, 1.115”, or 1.362”), but 

check the conduit fittings you are using to verify size.

WARNING

: Take care not to damage the circuit board.

C )  Dump or blow out any debris from this drilling operation.

3

To remove a sealing cap or AC connector, you must use an 

Enphase disconnect tool.

Each Q Aggregator includes one bulkhead connector cap. You can 

purchase additional caps from your distributor. 

      Attach the Q Aggregator to the PV Rail

WARNINGS

• Install the Q Aggregator under the PV module to avoid direct exposure 

to rain, UV, and other harmful weather events. 

• Mount the Q Aggregator with adequate clearance from the roof 

surface for rain and snow resistance.

• Always install the Q Aggregator with the label side up. Do not mount it 

upside down. You can flip the bracket for roof or block mounting.

• When transitioning between rows, secure the cable to the nearest rail 

to prevent cable damage.

A )  Install Q Aggregator on rail in a location that does not conflict with the 

module frame and module mounting hardware. Allow a minimum of 1.9 

cm (0.75“) between the roof and the Q Aggregator. Also allow 1.3 cm (0.50“) 

between the back of the PV module and the top of the Q Aggregator.

B )  Install the Q Aggregator on the rail and mount loosely.
C )  Use a fittings rated for outdoor use to secure the conduit or Q cable to 

the Q Aggregator.

D )  Provide an AC connection (home run) from the Enphase Q Aggregator 

back to the electricity network connection using equipment and 

practices as required by local jurisdictions. 

E )  Tighten rail connections to 80 in-lbs (9 N m), and make sure that conduit 

fittings are secured and water tight. 

F )  Secure and check all connections.

      Wire the Q Aggregator

A )  Pull the line conductors and ground up to the Q Aggregator.
B )  Strip the two line conductors (18 mm/0.7” strip length) using the guide 

on the upper surface of the cage clamp style main lugs.

C )  Secure the conductors (12 AWG to 4 AWG max) in these lugs and make 

sure that the orange handles are in the fully down position.

D )  Strip and bring the ground wire inside the Q Aggregator to the ground 

lug. This ground lug passes through to outside for use in grounding the 

rack and modules as needed. 

E )  Secure racking ground to the ground lug. 
F )  Torque the ground connections as follows: 

•  14-10 AWG:  2.25 N m (20 in-lbs)

•  8 AWG:  2.82 N m (25 in-lbs)

•  6-4 AWG:  3.95 N m (35 in-lbs)

G )  Check your connections for soundness.
You have completed the wiring for up to three plug and play branch circuits 

in your system.

5

      Plan the Connections

A )  Plan for the following connections:

•  One maximum 60 A home run: Pass the home run cable through wet/

dry-rated conduit gland, and secure in the cage clamp lugs to the terminal 

connectors. Use standard home run conduit size (1/2, 3/4, or 1-inch). 

•  Up to three 20 A branch circuits: Three bulkhead mounted connectors 

allow for the direct connection of the Q Cable. 

•  PV Array ground: The ground lug connection that passes through the 

enclosure allows you to connect racking and module ground to the main 

panel ground. The Aggregator contains no parts requiring a ground.

1

Summary of Contents for Q-BA-3-1P-60

Page 1: ...en the Q Aggregator and main PV breaker Enphase disconnect tool C Protect your system with lightning and or surge suppression devices at the sub or main panel D Protect the Q Aggregator with a maximum 60 amp over current protection device OCPD E Size the AC wire gauge to account for voltage rise Select the correct wire size based on OCPD size and on the distance from the beginning of the Enphase Q...

Page 2: ...an flip the bracket for roof or block mounting When transitioning between rows secure the cable to the nearest rail to prevent cable damage A Install Q Aggregator on rail in a location that does not conflict with the module frame and module mounting hardware Allow a minimum of 1 9 cm 0 75 between the roof and the Q Aggregator Also allow 1 3 cm 0 50 between the back of the PV module and the top of ...

Page 3: ...edures H If all connectors do not show voltage and the main PV circuit from the main panel is active per step D continue with the following troubleshoot ing procedure I Reconnect secure and check all connections All Circuits Appear Non Functioning A Verify that the PV breaker at the main panel reads 240V when measur ing from L1 to L2 B Power off the PV circuit aggregated ac circuit and verify with...

Page 4: ... enter from an uphill direction and that moisture does not enter the Aggregator Water ingress will void the warranty for the Aggregator WARNING Do not expose any connectors to rain or condensation before the connectors are mated WARNING Install the Q Aggregator under the PV module to avoid direct exposure to rain UV and other harmful weather events mount the Q Aggregator off of the roof surface fo...

Reviews: