AC Combiner Box Installation
If the Internet Connection Fails
After using any of these connection methods, if the Envoy-S does not connect to the Internet within five to
ten minutes after you attempt a connection, see “Internet Connection Issues” on page 27.
12. Send System Summary Report
When you have completed your system setup, you can generate and email a summary report.
a.
From Installer Toolkit, tap
Done
in the upper-right corner of the screen to disconnect from the Envoy.
Installer Toolkit will ask if you want to view a summary report.
b.
Tap
View Report
. The report displays Envoy and system information with a list of microinverter
serial numbers, their last power reports, and information about the grid profile applied to the
microinverters.
c.
Tap
to email the report to your office as a record of successful system installation or to the
utility for evidence of grid profile settings.
NOTE
: If your mobile device is connected to the Envoy using AP mode, the email stays in the
email app’s outbox to be sent when the mobile device reconnects to the Internet. To disconnect
from the Envoy network, go to Settings on your mobile device and disconnect from the Envoy-S
Wi-Fi network “Envoy_nnnnnn” (where “nnnnnn” represents the final six digits of the Envoy serial
number).
NOTE
: If you connect to an Envoy after associating it to a system, the report includes a system
name and address. For more information, refer to the
Enphase Installer Toolkit Operation Manual
at:
enphase.com/support
.
13. Re-Torque Connections and Secure the Door
WARNING
: Do not skip this step. You must re-torque all field wiring connections after one hour.
a.
Turn off power to AC combiner box at the main load center. Verify that all power is removed from the
system before attempting any wiring.
b.
Open the AC Combiner Box door.
c.
Remove the clear plastic dead front, and keep the screws and washers in a safe place.
d.
Measure voltage L1 to L2, L1 to N, and L2 to N to make sure there is no voltage present.
e.
Re-torque all field wiring connections one hour after first torque. See “Wiring Reference” on page 9
for required torque values.
f.
Close and secure the door of the combiner box so that it is protected against moisture and rain.