Enpower smart switch installation and operation
© 2020 Enphase Energy Inc. All rights reserved.
141-00046-01
18
F. Use the included stowed conductors, as labeled, to wire the circuit breaker(s) for the Encharge
batteries, Enphase Combiner, and generator (reserved for future use¹) as needed. The stowed
conductors are provided with crimped-on ferrules with end caps to prevent accidental contact.
Remove the conductor end caps as needed.
G. Torque the breaker connections as listed on the previous page and in the conductor table on the
unit.
H. After all conductors are connected and secured, check that there are no exposed conductors or
stray wires.
I.
Gently arrange all the conductors and connectors inside the cabinet.
DANGER
! Risk of electric shock. The system is not ready to be energized! Do not close any
circuit breaker yet.
NOTE
: The polarity of L1 and L2 is swapped inside Eaton CSR series main breakers.
Installers should follow L1 and L2 on the following image when installing consumption CTs.
Reserved for
future use
Reserved for
future use