Section 78
00-02-0997 (web only)
2019-10-07
- 16 -
Engine
Type
Specific Parameters Available
Mechanical
Speed Calibration
Overspeed
o
Shutdown
% Over High Speed
Fault at High Speed
o
Warning
% Over High Speed
Fault at High Speed
o
Disabled
Machine Hours
o
Set Machine Hours
o
Clear Machine Hours
Throttle Setup
Use the following to configure throttle settings.
System
Setting
Specific Parameters Available
Throttle
Throttle (Default: enabled)
o
Throttle Type
Display (Default)
Switch (Resistive Input 1 will be Throttle Switch UP,
Resistive Input 3 will be Throttle Switch DOWN)
Knob (Resistive Input 1 will be disabled, Resistive
Input 3 will be Throttle Knob)
o
Throttle Mode
For Types Display and Switch: Manual, Preset
For Type Knob: Manual
o
Setpoints
Ramp Rate Per Second
Inc/Dec Step Size
o
Low Speed Limit
o
High Speed Limit (with Overspeed at 5%)