© 2019 EnOcean | www.enocean.com
User Manual May 2019 | Page 27/49
USER MANUAL
Scavenger Transmitter Module
STM 330 / STM 331 STM 331U / STM 332U / STM 333U
(Stepcode DE and later)
Due to security features additional parameters apply for STM 330 / STM 331.
Parameter
Configuration
via programming interface
Mode changes
By default the change between transport, standard and
secure is enable. The configuration can be changed to
transport/standard modes (enhance secure disable) or to
transport/enhance secure modes (standard disable).
CMAC Length
CMAC length 3 bytes (default)
Private Key
AES 128 key which is used for data encryption.
Subkey 1
Subkey derivated from private key.
Subkey 2
Subkey derivated from private key.
Set initial RLC
Initial value of the RLC (0 by default).
Please refer to the EnOcean Security Specification for details
http://www.enocean.com/en/security-specification/
3.10
Radio telegram
3.10.1
Default configuration and standard mode
In default configuration and standard mode STM 33x transmits a radio telegram according
to EnOcean Equipment Profile A5-02-05 (Temperature sensor 0-40 °C) as defined in the
EnOcean Equipment Profiles (EEP) specification.
In standard mode STM 33x can be configured to following EEPs:
STM 33x: A5-02-05, A5-02-30, A5-10-05, A5-10-03
STM 33x with HSM 100 extension: A5-04-01, A5-10-10, A5-10-12
By pressing the LRN button 1 s in standard mode a 4BS teach-in telegram is transmitted.
After pressing the LRN button for 5 seconds a signal telegram (data: 0x0E) will be sent and
the module enters the transport mode. For details see EnOcean Alliance EEP specifica-
tion(Stepcode >=DE). In this mode the module does not send telegrams.
For details please refer to the EnOcean Equipment Profiles specification.
http://www.enocean-alliance.org/eep/