1.5 Relay output switching capabilities
Kind of load
Maximum Load
Electrical life
2 x 100W
20.000 (according to EN60669)
Incandescent lamp 120V AC
Gas discharge lamps / HQL-HQI / not
compensated*
60W 20.000
Gas discharge lamps / HQL-HQI /
compensated*
50W (14µF)
20.000
EGC Dynamic / dimmer*
1 x 18W
1 x 36W
25.000
Halogen lamp 120V AC
80W
20.000
12 x18W
25.000
4 x 36W
25.000
Not
compensated
cos
ϕ
0,4 – 0,6
2 x 58W
25.000
2 x 18W
20.000
Compensated
with capacitance
in parallel
1 x 36W
20.000
2 x 18W
20.000
Fluorescent lamp
120V AC
with conventional
ballasts
Compensated
fluorescent
DUO-circuit
1 x 36W
20.000
4 x 18W
20.000
2 x 36W
20.000
Fluorescent lamp
120V AC
with electronic
ballasts
Siemens /
Osram
EVG
1 x 58W
20.000
10A Min.
50.000
Resistive load
120V AC
cos
ϕ
=1
Max. capacitance at 120V AC
14 µF
Min. 5.000 (according to
EN60669)
Max. inrush current for max. 20ms at
120V AC
40 A
see above loads
©EnOcean GmbH, A. Anders
Page 8 of 18
RCM 255 User Manual V1.12