If the user has switched the light OFF (by a linked switch) 
then it can be turned ON again by occupancy sensor input 
only after 

OccAutoOnDelay

 (default 15 minutes). 

 

 

Light Level Sensor

 

One light level sensor can be linked to enable open-loop 
dimming for daylight harvesting. The system then adjusts 
the output light level according to incoming natural light.  

The light level sensor should therefore be placed at a 
position facing the window or skylight where it is not or only 
minimally influenced by light from the fixtures. 

If a light level sensor is linked, the LED controller will by 
default activate daylight harvesting with continuous open 
loop dimming according to a user-defined dimming curve 
based on 5 configurable supporting points and 

RampSpeed

.  

Each of these 5 supporting points defines the output light 
level (

OUT1

 … 

OUT5

) to be set by the LED controller for a 

given reported natural light level (

LEV1

 … 

LEV5

).  

For natural light levels below LEV1, output light level OUT1 
is set. Likewise, for natural light levels above LEV5, output 
light level OUT5 is set. Linear interpolation is used between 
the defined points (e.g. between LEV1/OUT1 and 
LEV2/OUT2). 

Setting the output light level to 0 will cause the output of 
LEDR to go to OFF state. 

If the output has been switched on by an occupancy Auto 
on event, the

 Auto On Light Level

 value will replaced by the 

dimming curve output value. 

If the dimming curve defined light level has been adjusted 
by user rocker interaction, the selected light level will be 
temporary maintained for a period defined by 

LlsAdjustmentDelay 

(default 15 minutes).  

The light level sensor can alternatively be used to activate an 
automatic switching mode between 0% (OFF) and 100% 
(

MaxVoltageLevel)

 based on light intensity (twilight switch). 

This can be achieved by configuring 

DaylightingMode

 to  

2-level mode via remote commissioning.  

The thresholds for switching between the two levels are 
defined by 

PhotoOnThres

 and 

PhotoOffThres

.   

Repeater function 

The LED controller provides the option to activate one-level 
(repeat only original telegrams) or two-level (repeat original 
telegrams or telegrams that were repeated once) repeater 
mode for EnOcean radio telegrams.  

By default (

RepeatLinkedDevicesOnly

=ON) only messages 

from linked devices are repeated. Setting this parameter to 0 
will cause all messages to be repeated.

 

Note:

 2-level repeating function and repeating of all 

messages (

RepeatLinkedDevicesOnly

=OFF) should only be 

used if really needed! Otherwise the system function can be 
compromised by collisions of telegrams. 

Status messages 

The LED controller will transmit a status message  
defined by the selected outbound EEP for every change of 
its output state or after 

StatusMessageTimer 

has elapsed.  

By setting 

StatusMessageTimer

 to 0 status messages can be 

switched off completely. By setting it to

 

0xFFFF only event 

based messages will be sent. 

 

 

 

7.

 

Troubleshooting 

 

Problem 

Solution Checklist 

The device does not power up

 

 

Check the wiring for errors 

 

Check the circuit breaker 

 

Use a voltage meter to confirm power

 

 

The device does not control 
linked load

 

 

Click the DIM button to open/close 
the relay manually  

 

Turn off the power and then restore it

 

 

Cannot link a device

 

 

Move closer to the device; it may be 
out of range 

 

Try linking a different device 

 

Check for environmental conditions 
that interfere with RF signals 

 

Verify the maximum number of 32 
inbound devices has not been 
exceeded and not more than 1 Light 
Level sensor has been linked 
 

The device does not respond to 
wireless messages or selected 
settings

 

 

Check for environment or range issues 

 

Verify the device is linked  

 

Extend the antenna to amplify the 
range: remove it from the groove in 
the module, and straighten it.

 

 

 

Contains:   

FCC: SZV-TCM515U  

 

 

 

IC: 5713A-TCM515U

 

 

This device complies with part 15 of the FCC rules and Industry Canada ICES-003.  
Operation is subject to the following two conditions: (1) This device may not cause 

Summary of Contents for LEDRU

Page 1: ...wireless remote commissioning to link devices and set parameters Specifications typ values Power Supply 120V 277V VAC 60 Hz Maximum Load General Purpose 16A 120 277VAC Resistive 16A 120 277VAC Tungsten 960W 120VAC Ballast LED Driver 600W 120VAC 0 10V output Tolerances 3 4 1 10V range Current sinking 35mA sourcing 20mA Power Consumption 1W full load 0 35W quiescent Surge Protection 3kV line to line...

Page 2: ...which of the two installation methods is most appropriate A Installed inside the electrical box NOTE For best performance remove the antenna from its slot and elongate it outside and away from the box B Installed using the threaded connector i Insert the threaded connector through a diameter knockout ii Thread the 5 module wires inside the electrical box and through the lock nut 4 Connect the wire...

Page 3: ...es Transmitters switches and sensors can provide input data to the LED controller Transceivers Gateways or controllers can exchange data and commands with the LED controller An LED controller is also capable of controlling other LED controllers in a Master Slave scenario To establish links the LED controller must be powered and within wireless range of the device it is to be linked with Inbound li...

Page 4: ...D starts toggling indicating that linking unlinking mode is active The connected load will toggle between 10 and 90 2 Shortly press the DIM button This will cause the LED Controller to transmit a link message teach in message identifying the status message EEP used by it 3 Press the LRN button again for 1 second or wait 30 seconds to return to normal operation Setting the minimum output voltage le...

Page 5: ...od defined by RockerSwitchAutoOffTimer This feature can be disabled by setting RockerSwitchAutoOffTimer 0 This feature is automatically disabled if an occupancy sensor is present In this case automatic switch OFF of the light will be performed based on the input from the occupancy sensor as described below Occupancy Sensors only Auto Off Timers If at least one sensor detects motion Light level is ...

Page 6: ... DaylightingMode to 2 level mode via remote commissioning The thresholds for switching between the two levels are defined by PhotoOnThres and PhotoOffThres Repeater function The LED controller provides the option to activate one level repeat only original telegrams or two level repeat original telegrams or telegrams that were repeated once repeater mode for EnOcean radio telegrams By default Repea...

Page 7: ...an switch the light back ON in Auto ON Mode after the user switched it OFF 15 min OccAutoOffTime1 Time after which current light level will be relatively changed by AutoOffLevel1 10 min OccAutoOffTime2 Time after which lights will be switched to AutoOffLevel2 5 min OccAutoOffLevel1 Factor applied to current light 50 level if AutoOffTimer1 elapses Range 0 200 OccAutoOffLevel2 Output value to which ...

Page 8: ...rn telegram from a linked device is received while in operating mode the 0 10V output will toggle once between 10 and 90 ON enabled Switch diming curve Defines four different diming curved Linear curve Enable relay on permanently Relay out line voltage will not be cut off if enabled Disabled Accumulated uptime value Accumulated time for output On n a Average output value Average output dim level o...

Reviews: