LEDRU LED 0-10V Zone Controller Installation Guide  

© 2018 EnOcean GmbH    V3.0 

LEDRU-W-EO / LEDRU-W-AU  DD08 and up 

  Page 

 

controller

 

timeout the system will switch 
back to the previous state. 

 

 

6.

 

Functional behavior 

0-10V Interface 

The minimum output voltage is 

MinVoltageLevel

 (default 

1.0V); the maximum output voltage is 

MaxVoltageLevel

 

(default 10.0V).  

Dimming below 

MinVoltageLevel 

or above

 MaxVoltageLevel 

is not possible.  

Level and ramp percentage levels refer to the interval 
between 

MinVoltageLevel

 (1%) and 

MaxVoltageLevel

 (100%). 

An output level of 0% equals OFF state.  

Switches only 

Short click (<0.7s) on “I” button: Light comes ON and 
brightens to most recent dimming value stored before 
device was switched OFF or to the 

FixedOutputLevel

 value 

(default=75%) if 

EnableFixedOn

=enabled (default=disabled).  

If a light level sensor is linked, then light will be set 
according to its input (see below). The minimum initial light 
level in this case is 

MinVoltageLevel

 (default 1.0V). 

Double click (<0.7s) on “I” button: Light is switched ON at 

MaxVoltageLevel

 (default 10.0V). 

Short click (<0.7s) or double click (<0.7s) on “0” button: The 
current light level is stored, light is dimmed down to 

MinVoltageLevel

 and then switched OFF. 

Ramp up (

RockerSwitchOnSpeed

) and ramp down 

(

RockerSwitchOffSpeed

) speeds for rocker switch operation 

are configurable (default 20% per second). 

Press and hold “I” / “0” button: Light is brightened / dimmed 
until button is released or 

MinVoltageLevel

 / 

MaxVoltageLevel 

is reached.  

Ramp up (

RockerDimUpSpeed

) and ramp down 

(

RockerDimDownSpeed

) speeds for rocker dim operation are 

configurable (default 20% per second).  

Rocker-based dimming can be disabled by setting 

RockerDimEnable

 = OFF. In this case light will be switched 

ON / OFF immediately upon pressing the “I” / “O” button. 

Light can be switched OFF automatically in absence of a 
linked occupancy sensor if no user (switch) action occurs 
during a period defined by 

RockerSwitchAutoOffTimer

.  

This feature can be disabled by setting 

RockerSwitchAutoOffTimer 

= 0. This feature is automatically 

disabled if an occupancy sensor is present. In this case, 
automatic switch OFF of the light will be performed based 
on the input from the occupancy sensor as described below. 

 

Occupancy Sensors only – Auto Off Timers

 

If at least one sensor detects motion, Light level is set to 

Auto On Light Level

 (default 100%).  Default setting 

(

OccAutoOn = disabled) 

is disregarded in this scenario. 

If none of the linked occupancy sensors reports motion for a 
period defined by 

Auto Off Time1

 (default 10min) then light 

is set to 

Auto Off Level 1

 (default 50%) and timer 2 starts 

with Auto Off Time 2 (default 5min). 

Auto Off Level 1 

is 

always relative to the current light level when timer 1 did 
elapse. For instance, if the Auto On Light Level had been 
changed to 80%, the resulting absolute light level for timer 2 
is 40%, cutting the level in half (with 

Auto Off Level 1

 =50% 

= default). If Timer 2 has elapsed, the light level will be 
switched to 

Auto Off Level 2

 (default 0%). 

Any motion detected by any linked occupancy sensor will 
reset both timers and the light level back to timer 1 level. 

Ramp up (

SensorRampUpSpeed

) speed for Auto ON and 

ramp down (

SensorRampDownSpeed

) speed for Auto OFF 

are configurable (default 20% per second). 

 

Occupancy Sensors and Switches

 

Light can be switched ON / OFF manually, function as 
described above.  Time-based automatic switch OFF (as 
defined by 

RockerSwitchAutoOffTimer

) is always disabled if 

at least one occupancy sensor is linked. 

While no presence is reported by any of the linked 
occupancy sensors and no switch input is received, both 
Auto Off Timers will act as described above. Any input will 
reset both Auto Off Timers.  

Light will be automatically turned back ON to timer 1 value 
if occupancy is reported within the 

VacancyGraceTimer

 

period (default 45s) after such Auto OFF event even if the 
Auto ON function is disabled. 

The system can also be configured (

OccAutoOn = 

Enabled) 

to automatically switch ON the light as described above. 

Summary of Contents for LEDRU

Page 1: ...wireless remote commissioning to link devices and set parameters Specifications typ values Power Supply 120V 277V VAC 60 Hz Maximum Load General Purpose 16A 120 277VAC Resistive 16A 120 277VAC Tungsten 960W 120VAC Ballast LED Driver 600W 120VAC 0 10V output Tolerances 3 4 1 10V range Current sinking 35mA sourcing 20mA Power Consumption 1W full load 0 35W quiescent Surge Protection 3kV line to line...

Page 2: ...which of the two installation methods is most appropriate A Installed inside the electrical box NOTE For best performance remove the antenna from its slot and elongate it outside and away from the box B Installed using the threaded connector i Insert the threaded connector through a diameter knockout ii Thread the 5 module wires inside the electrical box and through the lock nut 4 Connect the wire...

Page 3: ...es Transmitters switches and sensors can provide input data to the LED controller Transceivers Gateways or controllers can exchange data and commands with the LED controller An LED controller is also capable of controlling other LED controllers in a Master Slave scenario To establish links the LED controller must be powered and within wireless range of the device it is to be linked with Inbound li...

Page 4: ...D starts toggling indicating that linking unlinking mode is active The connected load will toggle between 10 and 90 2 Shortly press the DIM button This will cause the LED Controller to transmit a link message teach in message identifying the status message EEP used by it 3 Press the LRN button again for 1 second or wait 30 seconds to return to normal operation Setting the minimum output voltage le...

Page 5: ...od defined by RockerSwitchAutoOffTimer This feature can be disabled by setting RockerSwitchAutoOffTimer 0 This feature is automatically disabled if an occupancy sensor is present In this case automatic switch OFF of the light will be performed based on the input from the occupancy sensor as described below Occupancy Sensors only Auto Off Timers If at least one sensor detects motion Light level is ...

Page 6: ... DaylightingMode to 2 level mode via remote commissioning The thresholds for switching between the two levels are defined by PhotoOnThres and PhotoOffThres Repeater function The LED controller provides the option to activate one level repeat only original telegrams or two level repeat original telegrams or telegrams that were repeated once repeater mode for EnOcean radio telegrams By default Repea...

Page 7: ...an switch the light back ON in Auto ON Mode after the user switched it OFF 15 min OccAutoOffTime1 Time after which current light level will be relatively changed by AutoOffLevel1 10 min OccAutoOffTime2 Time after which lights will be switched to AutoOffLevel2 5 min OccAutoOffLevel1 Factor applied to current light 50 level if AutoOffTimer1 elapses Range 0 200 OccAutoOffLevel2 Output value to which ...

Page 8: ...rn telegram from a linked device is received while in operating mode the 0 10V output will toggle once between 10 and 90 ON enabled Switch diming curve Defines four different diming curved Linear curve Enable relay on permanently Relay out line voltage will not be cut off if enabled Disabled Accumulated uptime value Accumulated time for output On n a Average output value Average output dim level o...

Reviews: