Take a moment to plan for the sensor’s successful operation and 

optimal communication with the other system components. 

 

Fix the sensor a little behind knee position under the table top, 

with a distance of 70 to 90 cm between the floor and the sensor. 

 

Provide a minimum clearance of 4 ft. (1.2 m) away from any 

heat source, like heating radiators, forced air, or ventilation 

systems.  

 

Consider the construction materials (such as metal) in the 

space and obstacles that may interfere with RF signals. 

 

 

 

 
 

Sensor Range 

A single occupancy sensor provides sufficient coverage for one 

seat area. For people counting in a room multiple sensors will be 

required. 

 

 

 
 
The occupancy sensor can be mounted at the sub-desk surface 

with the double sided adhesive. If needed, screws can also be 

used to fix the mounting plate. 
NOTE: Sometimes it’s easier to link the sensor before it is 

mounted sub-desk. Refer to the “Linking” section. 
1.

 

Remove the sensor from packaging. 

2.

 

Remove the mounting plate from the sensor. 

3.

 

Insert the CR2032 battery under the clip with the positive 

pole (+) up and press it in place. 

4.

 

Define where you want to install the occupancy sensor (see 

“Planning”). 

5.

 

Decide which of the two installation options is appropriate 

(gluing or screwing). 

6.

 

Fix the mounting plate. 

7.

 

Attach the sensor to the mounting plate.  

8.

 

Slide the sensor on the mounting plate until it snaps into 

place.   

 

 

9.

 

Confirm the sensor is properly positioned to detect motion - 

refer to the “Walk Test” section. 

 

 

Safety Instructions 

 
Intended use: 
 
This product is intended for indoor usage in closed dry rooms. The product must not 

be used in any relation with equipment that supports, directly or indirectly, 

human/animal health or life or with applications that can result in danger for people, 

animals or real value. The product is not suitable for use in mechanically or 

environmentally challenging environments including (but not limited to) environments 

with heavy vibrations, mechanical shocks, very high humidity, very dusty or in explosive 

atmosphere. The installation and assembly of electrical equipment may only be 

performed by a skilled electrician.  

Basic safety instructions:  
Risk of suffocation! Do not leave the packaging material lying around. Children could 

swallow the small parts and choke on them. Install and operate product according to 

user manual and do not modify product. The product should not be exposed to rapid 

temperature changes shortly before or during operation; condensation of moisture has 

to be avoided. Wrong cleaning may damage the product; we suggest cleaning with 

soft and damp tissue.  

Disposal:  
Product: Dispose of the used components at an official collection point for electronic 

waste or at your local dealer.  Packing: Please use the recycling operators known to 

you. Germany: WEEE-Reg.-No.: DE 93770561 

 

 

Planning  

Installing

 

estimated time: 5 minutes

 

Summary of Contents for Easyfit EOSD

Page 1: ...adio telegrams will be sent out until the timer expires After the timer has expired the unit will transmit occupancy upon new motion detection An unoccupied message will be sent if no motion is detected for an extended period sending the first at 10 minutes then again at 30 minutes A heartbeat message can also be enabled see Optional Settings Specifications typ values Power Supply CR2032 battery R...

Page 2: ... 7 Attach the sensor to the mounting plate 8 Slide the sensor on the mounting plate until it snaps into place 9 Confirm the sensor is properly positioned to detect motion refer to the Walk Test section Safety Instructions Intended use This product is intended for indoor usage in closed dry rooms The product must not be used in any relation with equipment that supports directly or indirectly human ...

Page 3: ...he transceiver to which the sensor is linked Refer to the Linking section of the receiver installation guide to complete the linking setup process Use the walk test to confirm that motion is within the sensor s range NOTE Before starting the test ensure the battery is inserted for 5 minutes at least If the sensor does not have a sufficient power it cannot enter into the test mode No LED light or 1...

Page 4: ... inserted properly Sensor is activated when there is nothing to detect Verify there is 4 ft 1 2 m clearance from heat sources that may disturb sensing Reduce sensitivity setting by moving the PIR sensitivity switch on the back from REG to LOW the left hand position Linked device does not respond to wireless messages Force motion message by pressing Set button Check for environment or range issues ...

Reviews: